Serviceline Industrial Sensors
Serviceline Explosion Protection

Temperature Converter HiC2081

HiC2081
  • 1-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Thermocouple, RTD, potentiometer or voltage input
  • Linearized output 4 mA ... 20 mA, sink/source
  • Sensor breakage detection
  • Configurable by PACTware
  • Line fault detection (LFD)
  • Up to SIL 2 acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Datasheet excerpt: Technical data of  HiC2081

General specifications
Signal typeAnalog input
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
ConnectionSL1: 1a, 1b(-); 2a, 2b(+)
Rated voltage20 ... 30 V DC bus powered via Termination Board
Ripplewithin the supply tolerance
Power dissipation≤ 0.98 W
Power consumptionmax. 0.98 W
Interface
Programming interfaceprogramming socket
Input
Connection sidefield side
ConnectionSL2: 5a(+), 1a(+), 1b(-), 5b(-)
RTDtype Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995)
type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94)
type Cu10, Cu50, Cu100 (P50353-92)
type Ni100 (DIN 43760)
Measuring currentapprox. 200 µA with RTD
Types of measuring2-, 3-, 4-wire connection
Lead resistancemax. 50 Ω per line
Measurement loop monitoringsensor breakage, sensor short-circuit
Thermocouplestype B, E, J, K, N, R, S, T (IEC 584-1: 1995)
type L (DIN 43710: 1985)
type TXK, TXKH, TXA (P8.585-2001)
Cold junction compensationexternal and internal
Measurement loop monitoringsensor breakage
Potentiometer0 ... 20 kΩ (2-wire connection), 0.8 ... 20 kΩ (3-wire connection)
Types of measuring3-wire connection
Voltageselectable within the range -100 ... 100 mV
Input resistance≥ 1 MΩ (-100 ... 100 mV)
Output
Connection sidecontrol side
ConnectionSL1: 8a(+), 7a(-)
OutputAnalog current output
Current range0 ... 20 mA or 4 ... 20 mA
Fault signaldownscale 0 or 2 mA, upscale 21.5 mA (acc. NAMUR NE43)
Sourceload 0 ... 550 Ω
open-circuit voltage ≤ 18 V
SinkVoltage across terminals 5 ... 30 V. If the current is supplied from a source > 25 V,
series resistance of ≥ (V - 25)/0.0215 Ω is needed, where V is the source voltage.
The maximum value of the resistance is (V - 5)/0.0215 Ω.
Fault indication output
ConnectionSL1: 6b
Output typeopen collector transistor (internal fault bus)
Transfer characteristics
Deviation
After calibrationPt100: ± (0.06 % of measurement value in K + 0.1 % of span + 0.1 K (4-wire connection))
thermocouple: ± (0.05 % of measurement value in °C + 0.1 % of span + 1 K (1.2 K for types R and S)) , includes ± 0.8 K fault of the cold junction compensation (CJC)
mV: ± (50 µV + 0.1 % of span)
potentiometer: ± (0.05 % of full scale + 0.1 % of span, (excludes faults due to lead resistance))
Influence of ambient temperaturePt100: ± (0.0015 % of measurement value in K + 0.006 % of span)/K ΔTamb*)
thermocouple: ± (0.02 K + 0.005 % of measurement value in °C + 0.006 % of span)/K ΔTamb*)), influence of cold junction compensation (CJC) included
mV: ± (0.01 % of measurement value + 0.006 % of span)/K ΔTamb*)
potentiometer: ± 0.006 % of span/K ΔTamb*)
*) ΔTamb = ambient temperature change referenced to 23 °C (296 K)
Influence of supply voltage< 0.01 % of span
Influence of load≤ 0.001 % of output value per 100 Ω
Reaction timeworst case value (sensor breakage and/or sensor short circuit detection enabled)
mV: 1 s, thermocouples with CJC: 1.1 s, thermocouples with fixed reference temperature: 1.1 s, 3- or 4-wire RTD: 920 ms, 2-wire RTD: 800 ms, Potentiometer: 2.05 s
Galvanic isolation
Output/supply, programming inputfunctional insulation, rated insulation voltage 50 V AC
There is no electrical isolation between the programming input and the supply.
The programming cable provides galvanic isolation so that ground loops are avoided.
Indicators/settings
Display elementsLEDs
Control elementsDIP switch
Factory settingouput: current source 4 ... 20 mA
input: Pt100, 4-wire, temperature range -200 ... 850 C (73 ... 1123 K)
Configurationvia DIP switches
via PACTware
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2012
EN 61326-3-2:2008
Degree of protectionIEC 60529:2001
Protection against electrical shockUL 61010-1:2012
Ambient conditions
Ambient temperature-20 ... 70 °C (-4 ... 158 °F)
Relative humidity5 ... 90 %, non-condensing up to 35 °C (95 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 100 g
Dimensions12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch) (W x H x D)
Height106 mm
Width12.5 mm
Depth128 mm
Mountingon termination board
Codingpin 1, 2 and 4 trimmed
For further information see system description.
Data for application in connection with hazardous areas
EU-type examination certificateBASEEFA 14 ATEX 0129 X
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Input[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Voltage9 V
Current13.1 mA
Power30 mW
Analog outputs, power supply, collective error
Maximum safe voltage250 V (Attention! This is not the rated voltage.)
Interface
Maximum safe voltage250 V (Attention! The rated voltage is lower.), RS 232
CertificateBASEEFA 14 ATEX 0130 X
MarkingEx-Hexagon II 3G Ex nA IIC T4 Gc
Galvanic isolation
Input/Other circuitssafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
FM approval
Control drawing116-0429 (cFMus)
UL approval
Control drawing116-0391 (cULus)
IECEx approval
IECEx certificateIECEx BAS 14.0071X
IECEx BAS 16.0003X
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex nA IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210129
ECLASS 12.027210129
ECLASS 11.027210129
ECLASS 10.0.127210129
ECLASS 9.027210129
ECLASS 8.027210190
ECLASS 5.127210107
ETIM 9.0EC002919
ETIM 8.0EC002919
ETIM 7.0EC002919
ETIM 6.0EC002919
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: HiC2081

This isolated barrier is used for intrinsic safety applications.

This device accepts thermocouples (TC), millivolts, potentiometers, or resistance temperature detectors (RTD) from a hazardous area and converts them to an isolated, linearized analog output in the safe area.

The output can be selected as a current source or current sink with a switch.

Line fault detection of the field circuit is indicated by a red LED and an output on the fault bus. The fault conditions are monitored via a Fault Indication Board.

The device is easily configured by the use of the PACTware configuration software.

This device mounts on a HiC Termination Board.

Datasheet: HiC2081

DatasheetFile TypeFile Size
Datasheet HiC2081PDF997 KB
Fiche de données HiC2081PDF1006 KB
Datenblatt HiC2081PDF1000 KB
Datasheet HiC2081PDF1049 KB
Hoja de datos HiC2081PDF1007 KB

CAD+CAE: HiC2081

CADFile TypeFile Size
CAD 3-D / CAD 3-DSTP2770 KB

Approvals+Certificates: HiC2081

CertificatesFile TypeFile Size
Baseefa IECEx Certificate of ConformityLINK---
Baseefa Type n Zone 2 IECEx Certificate of ConformityLINK---
Brasil TUV Rheinland BrazilPDF1177 KB
Canada FMPDF328 KB
China SITIIAS CCC Ex CertificatePDF1069 KB
Europe Baseefa ATEX Category (1) D ATEX Category (M1) ATEX Category (1) GPDF656 KB
Europe Baseefa ATEX Category 3 GPDF511 KB
Korea KOSHAPDF609 KB
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378PDF427 KB
USA FMPDF330 KB
United Arab Emirates SGS Gulf Limited ECASExPDF603 KB
United Arab Emirates SGS Gulf Limited ECASExPDF854 KB
United Kingdom UKEX Category (1) G UK-Type Examination Certificate UKEX Category (M1) UKEX Category (1) DPDF176 KB
Control Drawings
Control drawing FM / Control drawing FMPDF88 KB
Control drawing UL / Control drawing ULPDF59 KB
Declaration of Conformity
EU Declaration of Conformity (P+F)PDF237 KB
EU Declaration of Conformity (P+F)PDF232 KB
EU Declaration of Conformity (P+F)PDF230 KB
EU Declaration of Conformity (P+F)PDF232 KB
UK Declaration of Conformity (P+F)PDF201 KB
EU Declaration of Conformity (P+F)PDF228 KB
EU Declaration of Conformity (P+F)PDF229 KB
EU Declaration of Conformity (P+F)PDF229 KB
EU-Konformitäterklärung (P+F)PDF232 KB
EU Declaration of Conformity (P+F)PDF237 KB
EU Declaration of Conformity (P+F)PDF228 KB
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)PDF229 KB
EU Declaration of Conformity (P+F)PDF231 KB
EU Declaration of Conformity (P+F)PDF228 KB
EU Declaration of Conformity (P+F)PDF229 KB
EU Declaration of Conformity (P+F)PDF231 KB
EU Declaration of Conformity (P+F)PDF232 KB
EU Declaration of Conformity (P+F)PDF231 KB
EU Declaration of Conformity (P+F)PDF229 KB
EU Declaration of Conformity (P+F)PDF232 KB
EU Declaration of Conformity (P+F)PDF229 KB
EU Declaration of Conformity (P+F)PDF228 KB
EU Declaration of Conformity (P+F)PDF228 KB
EU Declaration of Conformity (P+F)PDF231 KB

Software: HiC2081

Device type managers (DTM)File TypeFile Size
DTM Collection Interface Technology 2 / DTM Collection Interface Technology 2ZIP32633 KB
Software Tools
PACTware 4.1 SP6 / PACTware 4.1 SP6ZIP43327 KB
PACTware 5.0 / PACTware 5.0ZIP44203 KB

Associated Products: HiC2081

Accessory of

System board for Schneider, Foxboro FBM series, For 8 modules, For 8-channel cards FBM201/214(b)/216(b) (AI), FBM215/218/237 (AO), FBM204/205 (AO/AI), FBM244 (AI/AO), FBM247/248 (UIO), 24 V DC supply, Recommended modules: HiC2025(A) (AI), HiC2025ES (AI), HiC2031 (AO), HiC2081 (TI), HiC2831R5 (DI), HiC2883 (DO), HiC2441 (UIO), Hazardous area: screw terminals, blue, Non-hazardous area: Sub-D connector (male), 25-pin, Number of modules: 8, Signal type: Universal, Manufacturer: Foxboropa
System board for Schneider, Foxboro FBM series, For 16 modules, For 16-channel AI card FBM211, 24 V DC supply, Recommended modules: HiC2025(A) (AI), HiC2025ES (AI), HiC2081 (TI), Hazardous area: screw terminals, blue, Non-hazardous area: Sub-D connector (male), 37-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Foxboro, Control system type: FBMpa
System board for Schneider Electric, Tricon CX series by Triconex, TAN48 approval, For 16-channel universal I/O card 3902(A)X and AO card 3809(A)X, For 16 modules, Supported signal types: DI/DO/AI/TI/AO/UIO, 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: Sub-D connector (male), 50-pin, Up to SIL 3 acc. to IEC/EN 61508, Number of modules: 16, Signal type: Analog output
Universal, Manufacturer: Triconex, Control system type: Tricon CXpa
System board for Schneider Electric, Tricon CX series by Triconex, TAN48 approval, For 32-channel (16+16) AI cards 3722X and 3723X, For 16 modules, Recommended modules: HiC2025(A) (AI), HiC2025ES (AI), HiC2081 (TI), 24 V DC supply, Hazardous area: pluggable screw terminals, blue, Non-hazardous area: ELCO socket, 56-pin, Number of modules: 16, Signal type: Analog input, Manufacturer: Triconex, Control system type: Tricon CXpa
Matching System Components
Device DTM, For K-, E- and H-System, Frame application, like e. g. PACTware, must be installed separatelypa
Universal DTM host platform, For all DTMs of Pepperl+Fuchs, Approved FDT/DTM technology, Free of charge, Download from Pepperl+Fuchs websitepa
Isolated USB interface cable, Used with K-, E- and H-System devices, Used with PACTwarepa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.