Serviceline Industrial Sensors
Serviceline Explosion Protection

Not available for purchase

This product has been replaced.Go to replacement product HiC2851
Not available for purchase
Not available for purchase

Switch Amplifier HiC2851

HiC2851
  • 1-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Input for approved dry contacts or SN/S1N sensors
  • Active voltage output
  • Passive transistor output (resistive acc. to EN 60947-5-6)
  • Line fault transparency (LFT)
  • Up to SIL3 acc. to IEC 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  HiC2851

General specifications
Signal typeDigital Input
Supply
ConnectionSL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage19 ... 30 V DC
Ripple≤ 10 %
Rated current≤ 55 mA
Power dissipation≤ 800 mW
Power consumption≤ 1300 mW
Input
ConnectionSL2: 5a(+), 5b(-)
Open circuit voltage/short-circuit currentapprox. 8.4 V DC / approx. 11.7 mA
Lead resistancemax. 50 Ω , consider capacitances and inductances
Switching point1-signal: I > 2.8 mA
0-signal: I < 2.1 mA
Response delay≤ 1 ms
Output
ConnectionSL1: 8a(+), 7a(-); 10a(+), 9a(-)
Rated voltageoutput II: typ. 8 V DC, max. 22 V DC
Output Iactive voltage output, short-circuit proof
0-signal: 0 V
1-signal: 20 ... 31 V DC at max. 15 mA
fault: 0 V
Output IIpassive transistor output (resistive)
0-signal: 14 kΩ ± 10 %
1-signal: 1.8 kΩ ± 10 %
fault: > 100 kΩ
Fault indication output
ConnectionSL1: 6b
Output typeopen collector transistor (internal fault bus)
Transfer characteristics
Switching frequency
Output I≤ 50 Hz
Output II≤ 50 Hz
Galvanic isolation
Output/power supplyfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Output/Outputfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Indicators/settings
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Conformity
Electromagnetic compatibilityNE 21:2006
For further information see system description.
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 180 g
Dimensions12.5 x 106 x 128 mm (0.5 x 4.2 x 5.1 inch)
Height128 mm
Width12.5 mm
Length106 mm
Mountingon termination board
Codingpin 1 and 2 trimmed
For further information see system description.
Data for application in connection with hazardous areas
EU-type examination certificateBASEEFA 07 ATEX 0302X , for additional certificates see www.pepperl-fuchs.com
MarkingEx-Hexagon II (1)G [Ex ia] IIC , Ex-Hexagon II (1) D [Ex ia] IIIC , Ex-Hexagon I (M1) [Ex ia] I
InputEx ia
Voltage10.5 V
Current17.1 mA
Power45 mW (linear characteristic)
Supply
Maximum safe voltage253 V AC (Attention! Um is no rated voltage.)
Output
Maximum safe voltage253 V AC (Attention! Um is no rated voltage.)
CertificatePepperl+Fuchs
MarkingEx-Hexagon II 3G Ex nA IIC T4 Gc
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 94/9/ECEN 60079-0:2012 ; EN 60079-11:2012 ; EN 60079-15:2010
International approvals
FM approval
Control drawing16-534FM-12 (cFMus)
UL approval
Control drawing116-0364
IECEx approvalIECEx BAS 07.0097X
Approved for[Ex ia Ga] IIC, [Ex ia] I , [Ex ia] IIIC
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210121
ECLASS 12.027210121
ECLASS 11.027210121
ECLASS 10.0.127210121
ECLASS 9.027210121
ECLASS 8.027210121
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: HiC2851

Product Documentation: HiC2851

Language Selection:
Safety and Security DocumentationLanguageFile TypeFile Size
Safety ManualENGPDF328 KB
Manuals
System ManualENGPDF5438 KB

Design / Simulation: HiC2851

Language Selection:
CADLanguageFile TypeFile Size
CAD 2-D / CAD 2-DALLZIP16364 KB
CAE
EPLAN macros H-System devices (EMA) / EPLAN-Makros Geräte H-System (EMA)ALLZIP3536 KB

Approvals: HiC2851

Language Selection:
CertificatesCert No.LanguageFile TypeFile Size
Baseefa IECEx Certificate of ConformityIECEx BAS 07.0097XALLLINK---
Canada FMCoC 3033219CALLPDF682 KB
Europe Baseefa ATEX Category (M1) ATEX Category (1) GDBaseefa 07 ATEX 0302XALLPDF1615 KB
Europe Pepperl+Fuchs ATEX Category 3 G CertificatePF 09 CERT 1440 XALLPDF208 KB
USA FMCoC 3033219ALLPDF678 KB
Control Drawings
Control drawing UL / Control drawing UL   ALLPDF154 KB
Control drawing FM / Control drawing FM   ALLPDF112 KB