Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
Product Description |
---|
Advanced diagnostic module with relay output for fieldbus power hub physical layer diagnostics |
General specifications | ||
---|---|---|
Design / Mounting | Motherboard based | |
Installation in hazardous area | Zone 2 / Div. 2 | |
Supply | ||
Rated voltage | 19.2 ... 35 V | |
Rated current | 40 ... 25 mA | |
Power dissipation | max. 1 W | |
Fieldbus connection | ||
Number of segments | 4 | |
Fieldbus type | FOUNDATION Fieldbus/PROFIBUS PA | |
Rated voltage | 9 ... 32 V | |
Indicators/operating means | ||
LED PRI PWR | green: on, primary bulk power supply connected | |
LED SEC PWR | green: on, secondary bulk power supply connected | |
LED Seg 1...4 | yellow: bus activity; yellow 2 Hz flashing: Maintenance required; red 2 Hz flashing: specification limit violated; red: hardware error | |
Fault signal | VFC alarm 1 A, 50 V DC, normally closed | |
DIP switch | fieldbus type , redundant supply , Signal level , Noise level , Jitter | |
Galvanic isolation | ||
Fieldbus segment/Fieldbus segment | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | ||
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | < 95 % non-condensing | |
Shock resistance | 15 g 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Pollution degree | max. 2, according to IEC 60664 | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Core cross section | motherboard specific | |
Housing material | Polycarbonate | |
Degree of protection | IP20 | |
Mass | approx. 100 g | |
Dimensions | ||
Height | 106 mm | |
Width | 18 mm | |
Depth | 128 mm | |
Mounting | motherboard mounting | |
Data for application in connection with hazardous areas | ||
Certificate | TÜV 04 ATEX 2500 X | |
Marking | II 3 G Ex nA IIC T4 Gc | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
FM certificate | FM 19 US 0015 X and FM 19 CA 0011 X | |
FM marking | AEx/Ex ec IIC T4 | |
IECEx approval | ||
IECEx certificate | IECEx TUN 13.0038X | |
IECEx marking | Ex nA IIC T4 Gc | |
Certificates and approvals | ||
Marine approval | DNV A-14038 | |
Patents | This product may be covered by the following patent: US7,698,103 | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27242692 |
ECLASS 12.0 | 27242692 |
ECLASS 11.0 | 27242692 |
ECLASS 10.0.1 | 27242692 |
ECLASS 9.0 | 27242692 |
ECLASS 8.0 | 27242692 |
ECLASS 5.1 | 27242692 |
ETIM 9.0 | EC001604 |
ETIM 8.0 | EC001604 |
ETIM 7.0 | EC001604 |
ETIM 6.0 | EC001604 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121008 |
Designed as a plug-in module for the FieldConnex® Power Hub, the Advanced Diagnostic Module (ADM) with relay output is a monitoring tool for the physical layer of up to four fieldbus segments. Passive input circuits leave the physical layer untouched, avoiding alteration of the signal.
The ADM indicates unwanted conditions via voltage-free contact. It provides physical layer diagnostics "plug-and-play", without additional engineering. If desired, the values for maintenance and out-of-specification limit ranges are configurable via DIP switches. LED signals indicate that a limit has been exceeded. For commissioning and troubleshooting, a comprehensive diagnostic module such as the FieldConnex(R) mobile ADM (see DM-AM-KIT) is recommended.
Literature | Language | File Type | File Size |
---|---|---|---|
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-Synchrotron | ENG | 361 KB | |
Application Report - Digital Communication in Steel-Plate Manufacturing | ENG | 470 KB | |
Application Report - Fieldbus Power Supply Compatible with Process Industry Applications | ENG | 229 KB |
Safety and Security Documentation | Language | File Type | File Size |
---|---|---|---|
Instruction manual | ENG | 224 KB | |
Manuals | |||
Manual HD2-DM-A.RO Advanced Diagnostic Module Relais Output | ENG | 767 KB |
Certificates | Cert No. | Language | File Type | File Size |
---|---|---|---|---|
Canada FM | FM 19 CA 0011X | ALL | 356 KB | |
China SITIIAS CCC | 2020322310003510 (Singapore) | ALL | 1330 KB | |
DNV Marine | TAA0000272 | ALL | 100 KB | |
Europe TUV Nord ATEX Category 3 G | TÜV 04 ATEX 2500X | ALL | 1498 KB | |
India PESO (India) CCOE | A/P/HQ/KA/104/5874 (P507650) | ALL | 101 KB | |
USA FM | FM 19 US 0015X | ALL | 213 KB | |
Worldwide TUV Nord Ex nA nC IECEx nA | IECEx TUN 13.0038X | ALL | LINK | --- |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-0756C | ALL | 1040 KB |
Matching System Components | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
Matching System Components | ||||||
|
Get your free ADM Integration Package for your DCS System!
ABB 800xA Integration Package Download