Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
Product Description |
---|
G10 ultra compact module, 4 outputs |
General specifications | ||
---|---|---|
Node type | A/B node | |
AS-Interface specification | V3.0 | |
Required gateway specification | V3.0 | |
UL File Number | E223772 "For use in NFPA 79 Applications only" | |
MTBF | 382 a | |
Indicators/operating means | ||
LED FAULT | error display; LED red red: communication error or address is 0 red flashing: Output supply overload |
|
LED AS-i | AS-Interface voltage; LED green | |
Electrical specifications | ||
Rated operating voltage | 18.5 ... 31.6 V from AS-Interface | |
Rated operating current | ≤ 40 mA / max. 150 mA | |
Protection class | III | |
Surge protection | Ue: Over voltage category III, safe isolated power supplies (PELV) | |
Output | ||
Number/Type | 4 electronic outputs, PNP, overload and short-circuit proof | |
Supply | from AS-Interface | |
Voltage | ≥ (Ue - 7.0 V) | |
Current loading capacity | ≤ 100 mA Total current , overload and short-circuit protected | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 62026-2:2013 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 62026-2:2013 | |
Electrical safety | IEC 61140:2004 | |
Emitted interference | EN 61000-6-4:2011 | |
AS-Interface | EN 62026-2:2013 | |
Noise immunity | EN 61000-6-2:2005 EN 62026-2:2013 | |
Programming instructions | ||
Profile | S-7.A.7 | |
IO code | 7 | |
ID code | A | |
ID1 code | 7 | |
ID2 code | 7 | |
Data bits (function via AS-Interface) | ||
D0 | ||
D1 | ||
D2 | ||
D3 | ||
Parameter bits (programmable via AS-i) | function | |
P0 | communication monitoring P0 = 1 (default settings), monitoring = ON, i.e. if communication fails, the outputs are de-energised P0 = 0, monitoring = OFF, if communication fails, the outputs maintain their condition |
|
P1 | not used | |
P2 | Synchronous mode P2 = 0 synchronous mode on P2 = 1 synchronous mode off (default settings) |
|
P3 | not used | |
Approvals and certificates | ||
UL approval | cULus Listed, Type 1 enclosure | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -25 ... 80 °C (-13 ... 176 °F) | |
Shock and impact resistance | 30 g, 11 ms in 6 spatial directions 3 shocks 10 g, 16 ms in 6 spatial directions 1000 shocks |
|
Vibration resistance | 0.75 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles | |
Mechanical specifications | ||
Degree of protection | housing: IP67 IP67 / IP68 / IP69K with flat cable VAZ-FK-S-* M12 socket: IP67/IP68/IP69K |
|
Connection | AS-Interface: AS-Interface flat cable Outputs & matching connector: M12 connector, 5-pin, A-coded, acc. to IEC 61076-2-101:2012 |
|
Material | ||
Contacts | CuSn / Au | |
Housing | PBT PC | |
Body | PUR, black | |
Cable | PUR | |
Mounting screw | Stainless steel 1.4305 / AISI 303 | |
Cable | ||
Sheath diameter | ∅4.8 mm | |
Color | black | |
Cores | 5 x 0.34 mm2 | |
Length | 1 m | |
Mass | 81 g | |
Tightening torque, fastening screws | 1.65 Nm | |
Tightening torque, cable gland | 0.4 Nm | |
Dimensions | ||
Height | 21.5 mm | |
Width | 27.7 mm | |
Length | 40.5 mm |
System | Classcode |
---|---|
ECLASS 13.0 | 27242604 |
ECLASS 12.0 | 27242604 |
ECLASS 11.0 | 27242604 |
ECLASS 10.0.1 | 27242604 |
ECLASS 9.0 | 27242604 |
ECLASS 8.0 | 27242604 |
ECLASS 5.1 | 27242604 |
ETIM 9.0 | EC001599 |
ETIM 8.0 | EC001599 |
ETIM 7.0 | EC001599 |
ETIM 6.0 | EC001599 |
ETIM 5.0 | EC001599 |
UNSPSC 12.1 | 39121535 |
The AS-Interface G10 ultra-compact module is suitable for the remote connection of signal elements within very limited space. Up to 3 light and one siren element can be connected to the module. The one-piece enclosure has the protection degree IP68/IP69K.
The AS-Interface flat cable is contacted via pointy, gold-plated contact pins. The exact location of the pins on the lead is ensured by the swivel mechanism. Actuators are connected to the module via M12 sockets.
Multiple LEDs indicate the current status of the AS-Interface strand and are used for diagnosis.
Brief Instructions | Language | File Type | File Size |
---|---|---|---|
Instruction leaflet / Beipackzettel | ALL | 185 KB |
Certificates | Cert No. | Language | File Type | File Size |
---|---|---|---|---|
Worldwide AS-International Association AS-Interface | 126901 | ALL | 117 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-2573B | ALL | 115 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
|
AS-Interface Switch Cabinet Module KE5 – Simple Handling and Improved Manageability
The unique housing design of the new KE5 switch cabinet module enables distinct visibility and simplifies mounting, wiring, and maintenance inside switch cabinets and junction boxes.