Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
Supply | ||
---|---|---|
Rated voltage | 25 ... 28 V DC SELV/PELV | |
Ripple | max. 10 % | |
Fusing | 1 A | |
Power dissipation | ≤ 500 mW | |
Interface | ||
Type | multiplexer connection : IDC plug, 26-pin | |
Redundancy | ||
Supply | Redundancy available. The supply is monitored and fused. | |
Signal lines | ||
Rated current | max. 30 mA per channel | |
Indicators/settings | ||
Display elements | - LED PS-A (Termination Board power supply), green LED - LED PS-B (Termination Board power supply), green LED |
|
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2017 For further information see system description. |
|
Degree of protection | IEC 60529:2001 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | 0 ... 50 °C (32 ... 122 °F) | |
Storage temperature | -15 ... 50 °C (5 ... 122 °F) | |
Relative humidity | ≤ 93 % non-condensing | |
Shock resistance | 15 g , 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | ||
Field side | pluggable screw terminals , green | |
Control side | ELCO socket, 56-pin HART : 2 x IDC plug, 26-pin |
|
Supply | screw terminals , green | |
Core cross section | 0.5 ... 2.5 mm2 (20 ... 12 AWG) | |
Material | ||
Housing | PVC | |
Mass | approx. 300 g | |
Dimensions | 126 x 123 x 59 mm (5.0 x 4.9 x 2.3 inch) (W x H x D) | |
Height | 123 mm | |
Width | 126 mm | |
Depth | 59 mm | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
Certificate | PF 11 CERT 1933 X | |
Marking | II 3G Ex nA IIC T4 Gc | |
Directive conformity | ||
Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-15:2010 | |
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27210120 |
ECLASS 12.0 | 27210120 |
ECLASS 11.0 | 27210120 |
ECLASS 10.0.1 | 27210120 |
ECLASS 9.0 | 27210120 |
ECLASS 8.0 | 27210120 |
ECLASS 5.1 | 27210120 |
ETIM 9.0 | EC001485 |
ETIM 8.0 | EC001485 |
ETIM 7.0 | EC001485 |
ETIM 6.0 | EC001485 |
ETIM 5.0 | EC001485 |
UNSPSC 12.1 | 39121008 |
The function of the HART Termination Board as well as the connector pin assignment exactly fit the requirement of Triconex systems.
The HART termination board has pluggable screw terminals to connect HART field devices.
The 26-pin flat cable K-HM26 is used for connection of each HART Multiplexers KFD*-HM*-16 to the termination board.
The design permits the fast and reliable installation in the system cabinet.
Manuals | Language | File Type | File Size |
---|---|---|---|
Manual KFD*-HM*-16 | ENG | 8323 KB |
Certificates | Cert No. | Language | File Type | File Size |
---|---|---|---|---|
Europe Pepperl+Fuchs Certificate of Compliance ATEX Category 3 | PF11CERT1933 X | ALL | 189 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-1070D | ALL | 107 KB |
Matching System Components | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
Accessories | ||||||
|
||||||
|
||||||
|