Serviceline Industrial Sensors
Serviceline Explosion Protection

HART MUX Secondary Module KFD0-HMS-16

KFD0-HMS-16
  • 16-channel
  • No external power required
  • HART field device input (revision 5 to 7)
  • Used with HART MUX primary module KFD2-HMM-16
  • Up to SIL 3 acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  KFD0-HMS-16

Product Description
HART MUX Secondary Module
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Supply
Connectionvia 14-channel flat cable from the KFD2-HMM-16 primary module
HART signal channels (non-intrinsically safe)
ConformityHART field device input (revision 5 to 7)
Connection26-pin flat cable for analog connections
14-pin flat cable for primary module/secondary module connection between KFD2-HMM-16 and KFD0-HMS-16
Leakage current< 3 µA at -20 ... 85 °C (-4 ... 185 °F)
Terminating resistorexternal 230 ... 500 Ω standard (up to 1000 Ω possible)
Output voltage≥ 400 mV ss (with the terminator resistance specified above)
Output resistance100 Ω or smaller, capacitive coupling
Input impedanceaccording to HART specification
Input voltage range0.08 ... 4 V ss ; typ. ± 5.2 V as local reference
Indicators/settings
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 65 °C (-4 ... 149 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 100 g
Dimensions20 x 93 x 115 mm (0.8 x 3.7 x 4.5 inch) (W x H x D) , housing type B1
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
CertificatePF 07 CERT 1143 X
MarkingEx-Hexagon II 3G Ex nA IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-15:2010
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210190
ECLASS 12.027210190
ECLASS 11.027210190
ECLASS 10.0.127210190
ECLASS 9.027210190
ECLASS 8.027210190
ECLASS 5.127242692
ETIM 9.0EC001601
ETIM 8.0EC001601
ETIM 7.0EC001601
ETIM 6.0EC001601
ETIM 5.0EC001597
UNSPSC 12.139121008

Details: KFD0-HMS-16

Function

The HART MUX secondary module operates up to 16 analog field devices. The secondary module can be operated only with the HART MUX primary module KFD2-HMM-16 and is powered by the primary module across a 14- pin flat cable connection.

Up to 15 secondary modules can be connected to the primary module.

The secondary module address is set with a 16- position rotary switch (addresses 1 ... 16). If only one secondary module is connected to the primary module, then the secondary module address should be 1. If multiple secondary modules are connected, secondary modules must be assigned addresses in ascending order.

The analog signals are fed into the secondary module by means of a 26-pin flat cable. Sixteen leads are reserved for the HART signal of the analog measurement circuits. The remaining 10 leads are assigned to ground.

Informative Literature: KFD0-HMS-16

Language Selection:
LiteratureLanguageFile TypeFile Size
Application Report - Biological Cleaning of Wastwater and Secondary Sedimentation StageENGPDF566 KB
Application Report - Generating Electricity in Coal-Fired Power PlantsENGPDF412 KB
Application Report - Sand Trap and Preliminary Sedimentation StageENGPDF448 KB
Application Report - Screening Systems in Sewage Treatment PlantsENGPDF577 KB

Product Documentation: KFD0-HMS-16

Language Selection:
Safety and Security DocumentationLanguageFile TypeFile Size
Instruction manualENGPDF47 KB
Manuals
Manual KFD*-HM*-16ENGPDF8323 KB

Design / Simulation: KFD0-HMS-16

Language Selection:
CADLanguageFile TypeFile Size
CAD 3-D / CAD 3-DALLSTP105 KB
CAD Portal / CAD PortalALLLINK---
CAE
CAE EPLAN Data Portal / CAE EPLAN Data PortalALLLINK---
EPLAN macro EDZ / EPLAN Makro EDZALLEDZ60 KB

Approvals: KFD0-HMS-16

Language Selection:
CertificatesCert No.LanguageFile TypeFile Size
Europe Pepperl+Fuchs Certificate of Compliance ATEX Category 3PF 07 CERT 1143 XALLPDF209 KB
exida Functional Safety AssessmentP+F 02/4-11 R006ALLPDF348 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0777DALLPDF1040 KB
UK Declaration of Conformity (P+F) / UK-Konformitäterklärung (P+F)DOC-5294AALLPDF1037 KB

Software: KFD0-HMS-16

Language Selection:
Device Description Files/DriversRelease InfoFile TypeFile Size
DTM Collection HART-Multiplexer / DTM Collection HART-Multiplexer2.0.1.208ZIP13306 KB
Software Tools
PACTware 4.1 SP6 / PACTware 4.1 SP64.1.0.53ZIP43327 KB
PACTware 5.0 / PACTware 5.05.0.5.31ZIP44203 KB

Associated Products: KFD0-HMS-16

Matching System Components

Connection board for K-System HART Multiplexer, 16-channel, Interface for series connection or parallel connection, Integrated, switchable 220 Ω resistor, Connection via screw terminalspa
System board for Schneider Electric, Tricon series by Triconex, TAN48 approval, HART Termination Board (ETP) for Tricon v10 AI module, For 16-channel AI cards 3700, 3700A, 3703E and 3721, 16-channel, Field side: pluggable screw terminals, green, Control side: ELCO socket, 56-pinpa
System board for Schneider Electric, Tricon series by Triconex, HART Termination Board (ETP) for Tricon AO module, For 8-channel AO card 3805E, 8-channel, Field side: pluggable screw terminals, green, Control side: ELCO socket, 56-pinpa
Matching System Components

16-channel, 24 V DC supply (Power Rail), HART field device input (revision 5 to 7), Up to 15 KFD0-HMS-16 HART MUX secondary modules can be connected, Up to SIL 3 acc. to IEC/EN 61508pa
K-System accessory, Connection cable for KF*-HM*-16 to Termination Board, 26-pin ribbon cablepa
Universal DTM host platform, For all DTMs of Pepperl+Fuchs, Approved FDT/DTM technology, Free of charge, Download from Pepperl+Fuchs websitepa
Device DTM, For HART multiplexers, Communication DTMpa
Communication DTM, Frame application, like e. g. PACTware, must be installed separatelypa
Human machine interface, For HiDMux2700, For KFD2-HMM-16/KFD0-HMS-16pa
K-System accessory, Connection cable for KFD2-HMM-16 to up to 15 KFD0-HMS-16, 14-pin ribbon cablepa
K-System accessory, Connection cable for KF*-HM*-16 to Termination Board, 26-pin ribbon cablepa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.

Functional Safety Hub from Pepperl+Fuchs

Several hundred products with a SIL/PL assessment, free tools, and brochures in one place: the "Functional Safety Hub" is your starting point when you have to implement safety functions.