Serviceline Industrial Sensors
Serviceline Explosion Protection

RFID evaluation unit IC-KP2-1HB17-2V1D

IC-KP2-1HB17-2V1D
  • LED status indicator of bus communication and read/write head
  • Network loop through by means of integrated 2 port switch

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  IC-KP2-1HB17-2V1D

Product Description
IDENTControl Compact control interface with Ethernet interface for TCP/IP, PROFINET, EtherNet/IP, and MODBUS TCP protocols
General specifications
Number of read/write headsmax. 1
UL File NumberE87056
MTBF70 a (Operation at +40 °C)
Indicators/operating means
LED Link/Trafficgreen: network connection
yellow: flashes in rhythm with the transmitted data
LED 1Status indicator for read/write head
green: command at read/write head active
yellow: approx. 1 second long, if command was successfully executed
LED CH1green: read head detected
red: Configuration error
LED PWR/ERRgreen: power on
yellow: system is starting
red: PROFINET bus failure
Rotary switchAddress setting
Electrical specifications
Rated operating voltage20 ... 30 V DC , PELV
Ripple≤ 10 % at 30 V DC
Current consumption≤ 2 A incl. read/write head
Power consumption3.5 W Without read/write heads
Galvanic isolationbasic insulation acc. to DIN EN 50178, rated insulation voltage of 50 Veff
Interface 1
Physical Ethernet
ProtocolSMTP
HTTP
TCP/IP (Port 10000)
MODBUS/TCP
EtherNet/IP
PROFINET IO
Transfer rate10 MBit/s or 100 MBit/s
Interface 2
Physical Ethernet
ProtocolSMTP
HTTP
TCP/IP (Port 10000)
MODBUS/TCP
EtherNet/IP
PROFINET IO
Transfer rate10 MBit/s or 100 MBit/s
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61000-6-2
EN 61000-6-4
RoHS
Directive 2011/65/EU (RoHS)IEC/EN 63000
Standard conformity
Degree of protectionIEC 60529
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Climatic conditionsair humidity max. 96 %
Salt spray resistant to EN 60068-2-52
Shock and impact resistanceOscillation (Sine): 5 g, 10 - 1000 Hz to EN 60068-2-6
Shock (Half-sine): 30 g, 11 ms in accordance with EN 60068-2-27
Mechanical specifications
Degree of protectionIP67
ConnectionRead/write heads: shielded, 4-pin, M12 connector
Power supply: M12 connector
Protective earth: M4 earthing screw
Ethernet: M12 plug connection
Material
Housingpowder coated aluminum
Installationscrew fixing
Massapprox. 300 g
Dimensions
Height42 mm
Width62 mm
Length137 mm

Classifications

SystemClasscode
ECLASS 13.027280401
ECLASS 12.027280401
ECLASS 11.027280401
ECLASS 10.0.127280401
ECLASS 9.027280401
ECLASS 8.027280401
ECLASS 5.127280401
ETIM 9.0EC002998
ETIM 8.0EC002998
ETIM 7.0EC002998
ETIM 6.0EC002998
ETIM 5.0EC002998
UNSPSC 12.143211710

Details: IC-KP2-1HB17-2V1D

Function

The RFID identification system IDENTControl Compact from Pepperl+Fuchs offers a vast number of benefits compared to other systems, thanks to its innovative design. The control interfaces IDENTControl and IDENTControl Compact make up the core of the system.

With its integrated interfaces to all commercially available fieldbus systems such as PROFIBUS, PROFINET, Ethernet, EtherCAT, CC-Link, serial connections (RS 232 or RS 485) and numerous connection options for read/write heads available for frequency ranges LF, HF and UHF, the IDENTControl Compact control interface can be easily and flexibly adapted to your requirements.

LEDs on the front of the housing indicate bus communication, connected read/write heads and active read/write commands. Reliability of the application is further increased by using trigger sensors.

The system is equally suited for use in control cabinets and field use in IP67. The interface to the higher-level fieldbus is integrated in the housing, and all connections are designed such that they are pluggable. This enables simple installation and quick, problem-free replacement in case of device failure. The consistent EMC design, with metal housing, grounding and shielded wires, offers a high degree of reliability.

Informative Literature: IC-KP2-1HB17-2V1D

Language Selection:
LiteratureLanguageFile TypeFile Size
Application Report - RFID Systems in Industrial Metal StampingENGPDF1773 KB
Application Report - Safe Assignment of Workpiece and ToolENGPDF204 KB

Product Documentation: IC-KP2-1HB17-2V1D

Language Selection:
Brief InstructionsLanguageFile TypeFile Size
Brief Instructions - IC-KP2-*ENGPDF2285 KB
Manuals
Manual IC-KP2-1HB17-2V1DENGPDF3608 KB
Manual Read / Write Ranges and Passing Speeds RFIDENGPDF3640 KB

Design / Simulation: IC-KP2-1HB17-2V1D

Language Selection:
CADLanguageFile TypeFile Size
CAD 3-D / CAD 3-DALLSTP1681 KB
CAD Portal / CAD PortalALLLINK---

Approvals: IC-KP2-1HB17-2V1D

Language Selection:
CertificatesCert No.LanguageFile TypeFile Size
Canada, USA ULCoC UL-CA-L87056-31-61115002-0 / UL-US-L87056-11-61115002-0ALLPDF561 KB
Korea Radio ApprovalMSIP-REI-PF1-ICKP21HB172V1DALLPDF361 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0687EALLPDF111 KB
UK Declaration of Conformity (P+F) / UK-Konformitäterklärung (P+F)DOC-6844ALLPDF108 KB

Software: IC-KP2-1HB17-2V1D

Language Selection:
Device Description Files/DriversRelease InfoFile TypeFile Size
EtherNet/IP: EDS and Icon files / EtherNet/IP: EDS- und Icon-DateienZIP8 KB
PROFINET IO: GSDML file IC-KP2-1HB17-2V1D / PROFINET IO: GSDML-Datei IC-KP2-1HB17-2V1D08/2011ZIP9 KB
Add-On Instructions for RSLogix 5000 for use with IDENTControl / Inbetriebnahmedatei_a5/19/2022ZIP10372 KB
Function Blocks for Omrom PLCs with Ethernet/IP / Software Tool_a7/2014ZIP370 KB
Function block Step 7 Classic for the evaluation unit IC-KP2-1HBx with the RFID heads IQH1-...-V1 for complete reading and writing of the IQC21 data carrier / Funktionsbaustein Step 7 Classic für die Auswerteeinheit IC-KP2-1HBx mit den RFID-Köpfen IQH1-...-V1 zum vollständigen Lesen und Schreiben des IQC21 DatenträgersV1.1ZIP2115 KB
Function block Step 7 Classic for the evaluation unit IC-KP2-1HBx with the RFID heads IQH1-...-V1 for complete reading and writing of the IQC22 data carrier / Funktionsbaustein Step 7 Classic für die Auswerteeinheit IC-KP2-1HBx mit den RFID-Köpfen IQH1-...-V1 zum vollständigen Lesen und Schreiben des IQC22 DatenträgersV1.1ZIP2113 KB
Function block Step 7 Classic for the evaluation unit IC-KP2-1HBx with the RFID heads IQH1-...-V1 for complete reading and writing of the IQC24 data carrier / Funktionsbaustein Step 7 Classic für die Auswerteeinheit IC-KP2-1HBx mit den RFID-Köpfen IQH1-...-V1 zum vollständigen Lesen und Schreiben des IQC24 DatenträgersV1.1ZIP2120 KB
Function block Step 7 Classic for the evaluation unit IC-KP2-1HBx with the RFID heads IQH1-...-V1 for complete reading and writing of the IQC33 data carrier / Funktionsbaustein Step 7 Classic für die Auswerteeinheit IC-KP2-1HBx mit den RFID-Köpfen IQH1-...-V1 zum vollständigen Lesen und Schreiben des IQC33 DatenträgersV1.1ZIP2124 KB
Function block Step 7 Classic for the evaluation unit IC-KP2-1HBx with the RFID heads IQH1-...-V1 for complete reading and writing of the IQC35 data carrier / Funktionsbaustein Step 7 Classic für die Auswerteeinheit IC-KP2-1HBx mit den RFID-Köpfen IQH1-...-V1 zum vollständigen Lesen und Schreiben des IQC35 DatenträgersV1.1ZIP2114 KB
Function block Step 7 Classic for the evaluation unit IC-KP2-1HBx with the RFID heads IQH1-...-V1 for reading and writing of the IQC37 data carrier / Funktionsbaustein Step 7 Classic für die Auswerteeinheit IC-KP2-1HBx mit den RFID-Köpfen IQH1-...-V1 zum Lesen und Schreiben des IQC37 DatenträgersV1.1ZIP2121 KB
Function block TIA Portal (S7-1200/1500) for IC-KP2-1HB (Profinet + Profibus) with IPH-...-V1, IQH1-...-V1 or IUH-...-V1 RFID heads with single-frame protocol / Funktionsbaustein TIA Portal (S7-1200/1500) für IC-KP2-1HB (Profinet + Profibus) mit IPH-...-V1, IQH1-...-V1 oder IUH-...-V1 RFID-Köpfen mit Single-Frame ProtokollV3.0ZIP23798 KB
Function block TIA Portal (S7-1200/1500) for the evaluation units IDENTControl IC-KP2-1HB (Profinet + Profibus) when using IQH3-...-V1 RFID heads with single-frame protocol / Funktionsbaustein TIA Portal (S7-1200/1500) für die Auswerteeinheiten IDENTControl IC-KP2-1HB (Profinet + Profibus) bei der Verwendung von IQH3-...-V1 RFID-Köpfen mit Single-Frame ProtokollV1.1ZIP10357 KB
Function block TIA Portal (S7-1200/1500) for the evaluation units IDENTControl IC-KP2-1HB (Profinet + Profibus) when using IUH-F190-V1-FR and IUH-F192-V1-FR RFID heads with multi-frame protocol. / Funktionsbaustein TIA Portal (S7-1200/1500) für die Auswerteeinheiten IDENTControl IC-KP2-1HB (Profinet + Profibus) bei der Verwendung von IUH-F190-V1-FR und IUH-F192-V1-FR RFID-Köpfen mit Multi-Frame Protokoll.V1.0ZIP17056 KB
Function block TIA Portal (S7-300/400) for the evaluation units IDENTControl IC-KP2-1HB (Profinet + Profibus) when using IPH-...-V1, IQH1-...-V1 or IUH-...-V1 RFID heads with single-frame protocol. / Funktionsbaustein TIA Portal (S7-300/400) für die Auswerteeinheiten IDENTControl IC-KP2-1HB (Profinet + Profibus) bei der Verwendung von IPH-...-V1, IQH1-...-V1 oder IUH-...-V1 RFID-Köpfen mit Single-Frame Protokoll.V4.0ZIP9719 KB
Function blocks TIA Portal (S7-1200/1500) for the evaluation units IDENTControl IC-KP2-1H (Profinet + Profibus) to read and write of the complete user memory of different data carriers using the single frame protocol. / Funktionsbausteine TIA Portal (S7-1200/1500) für die Auswerteeinheiten IDENTControl IC-KP2-1H (Profinet + Profibus) zum Lesen und Schreiben des kompletten Nutzdatenbereichs verschiedener Datenträger unter Verwendung des Single-Frame Protokolls.V1.0ZIP6498 KB
Simatic S7 function block V3.0 Profinet connection IC-KP2-1HB17-2V1D / Simatic S7 Funktionsbaustein V3.0 Profinet Anbindung IC-KP2-1HB17-2V1DV3.0 2014-01-28ZIP1127 KB
Step 7 function block S7-300/400 for IC-KP2-1HB17 (Profinet) and IC-KP2-1HB6 (Profibus) MultiFrame protocol UHF-System / Step 7 Funktionsbaustein S7-300/400 für IC-KP2-1HB17 (Profinet) und IC-KP2-1HB6 (Profibus) MultiFrame Protokoll UHF-SystemV1.4ZIP8208 KB
Step 7 function block S7-400 with CP for TCP/IP communication IC-KP2-1HB17-2V1D MultiFrame protocol UHF-System / Step 7 Funktionsbaustein S7-400 mit CP für TCP/IP Kommunikation IC-KP2-1HB17-2V1D MultiFrame Protokoll UHF-SystemV2.3ZIP1300 KB
Step 7 function block S7-400 with CP for TCP/IP communication IC-KP2-1HB17-2V1D SingleFrame protocol UHF-System / Step 7 Funktionsbaustein S7-400 mit CP für TCP/IP Kommunikation IC-KP2-1HB17-2V1D SingleFrame Protokoll UHF-SystemV2.1.1ZIP1274 KB
Software Tools
RFID-Supervisor Demosoftware to setup IDENTControl with Ethernet interface / RFID-Supervisor Demosoftware zur Ansteuerung IDENTControl mit Ethernet SchnittstelleV1.8.1ZIP12205 KB
Software RFIDControl Demo / Software RFIDControl DemoV 1.5.3ZIP5467 KB

Associated Products: IC-KP2-1HB17-2V1D

Accessory of
UHF read/write head for hazardous areas, for IDENTControl, Canada, USA, and Mexicofa
Accessories

Cordset M12 socket straight to M12 plug angled A-coded, 4-pin, PUR cable grey, shieldedfa

Female cordset single-ended M12 straight A-coded, 4-pin, PUR cable grey, shieldedfa
Cordset M12 socket straight to M12 plug angled A-coded, 4-pin, PUR cable grey, shieldedfa
Mounting aid for DIN railfa
Cordset M12 socket straight to M12 plug angled A-coded, 4-pin, PUR cable grey, shieldedfa
Visit the RFID Hub

Visit our "RFID Hub"—this special website is a knowledge base for RFID. Get answers on frequently asked questions and learn about typical RFID applications …