Serviceline Industrial Sensors
Serviceline Explosion Protection

FieldBarrier Junction Box F.FB0.T**.***.1.0.***.***.****

F.FB0.T**.***.1.0.***.***.****
  • 4, 8 or 12 outputs Ex ia
  • Brushed enclosure, IP66
  • Configurable cable entries for trunk and spurs
  • Packaged certified solution
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • Installation in Zone 1

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  F.FB0.T**.***.1.0.***.***.****

Product Description
FieldBarrier Junction Box, Brushed Stainless Steel
General specifications
Design / MountingOutside installation
Installed componentsFieldBarrier RD0-FB-Ex4.COM
For technical data on installed electronic component see data sheet.
Conformity
Degree of protectionEN 60529
Impact resistanceEN 60079-0
Ambient conditions
Ambient temperature-40 ... 60 °C (-40 ... 140 °F)
Storage temperature-40 ... 70 °C (-40 ... 158 °F)
Relative humidity< 75 % (annual mean)
< 95 % (30 d/year), no moisture condensation
Impact resistance7J
Mechanical specifications
Enclosure coverHinged door with captive retaining screws
Degree of protectionIP66
Cable entrycable gland and stopping plug options see separate table
Material
HousingStainless steel 1.4404 / AISI 316L
Surfacebrushed
SealSilicone, fire-resistant, one piece, foamed
Material thicknessenclosure body, enclosure cover, mounting plate: 1.5 mm
Dimensions(W x H x D)
300 x 230 x 160 mm (1 x RD0-FB-Ex4.COM)
380 x 380 x 220 mm (2 x RD0-FB-Ex4.COM)
480 x 380 x 220 mm (3 x RD0-FB-Ex4.COM)
Mountingthru-holes Ø 7 mm
Groundinggrounding bolt M6 , brass, nickel-plated
Data for application in connection with hazardous areas
EU-type examination certificatePTB 07 ATEX 1061 X (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com
MarkingEx-Hexagon II 2(1)G Ex db eb mb [ia] IIC T4 Gb
Ex-Hexagon II 2(1)D Ex tb [ia Da] IIIC T135°C Db
Note: The marking is based on the maximum value and can be reduced depending on the selected options accordingly.
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-1:2014+AC:2018 , EN IEC 60079-7:2015+A1:2018 , EN 60079-11:2012 , EN 60079-18:2015+Cor.2018 , EN 60079-31:2014
International approvals
IECEx approvalIECEx PTB 07.0036 X , suitable Junction Box on request
INMETRO approvalTÜV 13.1143
General information
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242610
ECLASS 12.027242610
ECLASS 11.027242610
ECLASS 10.0.127242610
ECLASS 9.027242610
ECLASS 8.027242610
ECLASS 5.127242601
ETIM 9.0EC001601
ETIM 8.0EC001601
ETIM 7.0EC001601
ETIM 6.0EC001601
ETIM 5.0EC001604
UNSPSC 12.139121008

Details: F.FB0.T**.***.1.0.***.***.****

Function

This Junction Box is a device coupler with FieldConnex ® FieldBarriers for Zone 1. Devices can be located in Zone 0. The number of outputs and size can be selected.

Brushed stainless steel 316L provides high corrosion and impact resistance at a very wide temperature range.

Trunk and spur entries can be selected individually from a range of cable glands and stopping plugs. A breather is included by default. Tag plate, grounding bar, surge protection for the trunk, and bus termination are available as options.

This junction box is available pre-wired, with all accessories, for fast ordering, delivery, site installation, and commissioning.

Informative Literature: F.FB0.T**.***.1.0.***.***.****

Language Selection:
LiteratureLanguageFile TypeFile Size
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronENGPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingENGPDF470 KB

Product Documentation: F.FB0.T**.***.1.0.***.***.****

Language Selection:
Safety and Security DocumentationLanguageFile TypeFile Size
Instruction manualENGPDF140 KB
Manuals
ManualENGPDF928 KB

Approvals: F.FB0.T**.***.1.0.***.***.****

Language Selection:
CertificatesCert No.LanguageFile TypeFile Size
Europe PTB ATEX Category 2 G ATEX Category 2 DPTB 07 ATEX 1061 XALLPDF500 KB

Associated Products: F.FB0.T**.***.1.0.***.***.****

Matching System Components
FieldConnex® Fieldbus, Fieldbus barrier, module for DIN rail mounting, 4 outputs Ex ia IIC, FieldBarrier in Zone 1/Div. 2, Instruments in Zone 0...1/Div. 1, Short circuit current limitation per output, For FOUNDATION Fieldbus H1 and PROFIBUS PA, IECEx approval, Dust protection, International, Europe, USA, Canada, Device coupler location: Zone 2 - high-power trunk
Zone 1 - high-power trunk
Division 2 - high-power trunk
Division 1 - high-power trunkpa