Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
Product Description |
---|
PROFINET IO to Modbus Gateway 2-port DIN rail DB9 |
General specifications | ||
---|---|---|
UL File Number | E360395 | |
Functional safety related parameters | ||
MTBF | 46.3 a | |
Indicators/operating means | ||
LED indication | see manual | |
Electrical specifications | ||
Rated operating voltage | 5 ... 30 V DC | |
General information | Redundant power | |
Nominal voltage | 24 V DC | |
Interface | ||
Interface type | Software selectable interfaces: RS-232 , RS-422 , RS-485 (2 and 4-wire) | |
Physical | 2 x DB9 | |
Protocol | MODBUS RTU | |
Supported baud rates | 300 bps to 230Kbps | |
Interface 1 | ||
Interface type | Industrial Ethernet | |
Physical | 1 x RJ45 | |
Protocol | PROFINET IO | |
Additional protocols | ARP, BOOTP, DHCP/RARP, HTTP, HTTPS, SSH, SSL/TLS, ICMP, RFC 1006 (ISO over TCP), SNMP (MIB-II), TCP/IP & UDP socket services, Telnet, and TFTP, and supports IP multicast data transmission | |
Transfer rate | 10/100 Mbps | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61000-6-2:2005 , EN 610006-4:2007 , EN 610006-4/A1:2011 | |
RoHS | EN IEC 63000:2018 | |
Standard conformity | ||
Degree of protection | NEMA TS2 | |
Electrical safety | CSA C22.2 No. 60950 / UL60950 |
|
Emitted interference | EN 61000-6-4, EN 55032, FCC Part 15 Subpart B, ICES-003, AS/NZS CISPR 32 | |
Noise immunity | EN 61000-6-2 , EN 55024 | |
Ambient conditions | ||
Ambient temperature | -40 ... 75 °C (-40 ... 167 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | max. 95 % | |
Altitude | 0 ... 3048 m | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | Power Supply: screw terminals Fieldbus: 1 x RJ45 Inputs/outputs: 2 x DB9 |
|
Material | ||
Housing | Polyamide, UL94V-0 | |
Mass | 136g | |
Dimensions | ||
Height | 99.1 mm | |
Width | 22.9 mm | |
Length | 116.8 mm | |
Construction type | Cabinet module | |
Mounting | DIN mounting rail |
System | Classcode |
---|---|
ECLASS 13.0 | 27242608 |
ECLASS 12.0 | 27242608 |
ECLASS 11.0 | 27242608 |
ECLASS 10.0.1 | 27242608 |
ECLASS 9.0 | 27242608 |
ECLASS 8.0 | 27242608 |
ECLASS 5.1 | 27242608 |
ETIM 9.0 | EC001597 |
ETIM 8.0 | EC001597 |
ETIM 7.0 | EC001597 |
ETIM 6.0 | EC001597 |
ETIM 5.0 | EC001597 |
UNSPSC 12.1 | 32151705 |
The ICDM-RX/EN1 gateway enables the connection of serial devices (RS-232 / RS-422 / RS-485) such as barcode scanners, RFID readers and weigh scales to both PROFINET IO and Modbus networks. It combines an PROFINET IO interface with a Modbus gateway functionality and a built-in programmable data mapping sub-system, that ties everything together and doubles as a Modbus concentrator. The embedded web pages provide extensive diagnostics, intuitive and flexible configuration options, secure interfaces and numerous maintenance options. The result is a highly flexible gateway that allows full integration of PROFINET IO controllers into simple or complex Modbus networks. PROFINET IO controllers such as PLCs, HMIs, SCADAs and OPC servers can communicate to almost any Modbus gateway or client, either locally or remotely.
Literature | Language | File Type | File Size |
---|---|---|---|
Product Information - Serial Gateways - DeviceMaster® | ENG | 1227 KB |
Manuals | Language | File Type | File Size |
---|---|---|---|
Manual ICDM-RX/PN1 | ENG | 7747 KB | |
ICDM-RX/ Hardware Installation and Configuration | ENG | 12995 KB |
Certificates | Cert No. | Language | File Type | File Size |
---|---|---|---|---|
Canada, USA UL UL | E360395 | ALL | LINK | --- |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-4273A | ALL | 110 KB | |
UK Declaration of Conformity (P+F) / UK-Konformitäterklärung (P+F) | DOC-7588 | ALL | 105 KB | |
Australia Declaration of Conformity | ACMA Supplier’s declaration of conformity | ALL | 298 KB |
Device Description Files/Drivers | Release Info | File Type | File Size |
---|---|---|---|
PROFINET GSDML and firmware files for ICDM-RX/PN1 Module / PROFINET GSDML und firmware Dateien für ICDM-RX/PN1 Module | 2024-09 v1.0.8 | ZIP | 1398 KB |
Software Tools | |||
PortVision DX v6.02 / PortVision DX v6.02 | 2020-08 | ZIP | 29584 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|