Serviceline Industrial Sensors
Serviceline Explosion Protection

Frequency Converter with Direction and Synchronization Monitor KFU8-UFT-Ex2.D

KFU8-UFT-Ex2.D
  • 2-channel isolated barrier
  • Universal usage at different power supplies
  • Dry contact or NAMUR inputs
  • Input frequency 1 mHz ... 1 kHz
  • Current output 0/4 mA ... 20 mA
  • Relay contact and transistor output
  • Start-up override
  • Configurable by PACTware or keypad
  • Line fault detection (LFD)

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  KFU8-UFT-Ex2.D

General specifications
Signal typeDigital Input
Supply
Connectionterminals 23, 24
Rated voltage20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz
Rated currentapprox. 130 mA
Power dissipation2.2 W / 3.5 VA
Power consumption2.5 W / 5 VA
Interface
Programming interfaceprogramming socket
Input
Connection sidefield side
Connectioninput I: terminals 1+, 3-
input II: terminals 4+, 6-
input III: terminals 13+, 14- (control input 1)
input IV: terminals 15+, 14- (control input 2)
Input I, II2-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact
Open circuit voltage/short-circuit current8.2 V / 10 mA
Pulse durationmin. 250 µs , overlap on direction of rotation signal: ≥ 125 µs
Input frequencyrotation direction monitoring 0.001 ... 1000 Hz slip monitoring 10 ... 1000 Hz
Line fault detectionbreakage I ≤ 0.15 mA; short-circuit I > 6.5 mA
Input III, IV
Active/PassiveI > 4 mA (for min. 100 ms) / I < 1.5 mA
Open circuit voltage/short-circuit current18 V / 5 mA
Output
Connection sidecontrol side
Connectionoutput I: terminals 10, 11, 12
output II: terminals 16, 17, 18
output III: terminals 19+, 20-
output IV: terminals 21+, 20-
output V: terminals 7-, 8+
Output I, IIsignal , relay
Contact loading250 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A
Mechanical life5 x 107 switching cycles
Energized/De-energized delayapprox. 20 ms / approx. 20 ms
Output III and IVsignal , electronic output, passive
Contact loading40 V DC
Signal level1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof)
0-signal: switched off (off-state current ≤ 10 µA)
Output Vanalog
Current range0 ... 20 mA or 4 ... 20 mA
Open loop voltagemax. 24 V DC
Loadmax. 650 Ω
Fault signaldownscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43)
Transfer characteristics
Input I and II
Measuring range0.001 ... 1000 Hz
Resolutionslip monitoring: 1% frequency measurement: 0,1% of measured value; but >0.001Hz
Accuracyslip monitoring: 1% frequency measurement: 0.5% of measured value; but >0.001Hz
Measuring timefrequency measurement: < 100 ms
Influence of ambient temperature0.003 %/K (30 ppm)
Output I, II
Response delay≤ 200 ms
Output V
Resolution< 10 µA
Accuracy< 30 µA
Influence of ambient temperature0.005 %/K (50 ppm)
Accuracy0.1 %
Galvanic isolation
Input I, II/other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Input III, IV/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output I, II/other circuitsreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Mutual output I, II, IIIreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Mutual output I, II, IV reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III, IV/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Output III, IV/input III, IVbasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output III, IV/Vbasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Output V/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Interface/power supplyreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Interface/output III, IVbasic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff
Indicators/settings
Display elementsLEDs , display
Control elementsControl panel
Configurationvia operating buttons
via PACTware
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
InputEN 60947-5-6:2000
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Mass300 g
Dimensions40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) (W x H x D) , housing type C2
Height119 mm
Width40 mm
Depth115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateTÜV 99 ATEX 1471
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
Supply
Maximum safe voltage253 V AC / 125 V DC (Attention! Um is no rated voltage.)
Input I and IIterminals 1+, 3-; 4+, 6-: Ex ia
Voltage Uo10.1 V
Current Io13.5 mA
Power Po34 mW (linear characteristic)
Input III and IVterminals 13+, 14-; 15+, 14- non-intrinsically safe
Maximum safe voltage Um40 V (Attention! Um is no rated voltage.)
Output I, IIterminals 10, 11, 12; 16, 17, 18 non-intrinsically safe
Maximum safe voltage253 V (Attention! The rated voltage can be lower.)
Contact loading253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load (TÜV 99 ATEX 1471)
Output III and IVterminals 19, 20, 21 non-intrinsically safe
Maximum safe voltage Um40 V (Attention! Um is no rated voltage.)
Output Vterminals 8+, 7- non-intrinsically safe
Maximum safe voltage Um40 V DC (Attention! Um is no rated voltage.)
InterfaceRS 232
Maximum safe voltage40 V (Attention! Um is no rated voltage.)
Galvanic isolation
Input I, II/other circuitssafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018 , EN 60079-11:2012
International approvals
FM approval
Control drawing16-538FM-12
IECEx approval
IECEx certificateIECEx TUN 04.0007
IECEx marking[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210128
ECLASS 12.027210128
ECLASS 11.027210128
ECLASS 10.0.127210128
ECLASS 9.027210128
ECLASS 8.027210190
ECLASS 5.127210121
ETIM 9.0EC002918
ETIM 8.0EC002918
ETIM 7.0EC002918
ETIM 6.0EC002918
ETIM 5.0EC002475
UNSPSC 12.139121007

Details: KFU8-UFT-Ex2.D

Function

This isolated barrier is used for intrinsic safety applications. It analyzes 2 digital signals (NAMUR sensor/mechanical contact) from a hazardous area and functions as a rotation direction indicator, slip monitor, frequency monitor or synchronization monitor.

Each proximity sensor or switch controls a passive transistor output. The 2 relay outputs indicate if the input signal is above or below the trip value or the rotational direction.

The analog output can be programmed to be proportional to the input frequency or slip differential.

The unit is easily programmed by the use of a keypad located on the front of the unit or with the PACTware™ configuration software.

Line fault detection of the field current is indicated by a red LED.

For additional information, refer to the manual and www.pepperl-fuchs.com.

Informative Literature: KFU8-UFT-Ex2.D

Language Selection:
LiteratureLanguageFile TypeFile Size
Application Report - Biological Cleaning of Wastwater and Secondary Sedimentation StageENGPDF566 KB
Application Report - Energy Generation in Wastwater Treatment PlantsENGPDF532 KB
Application Report - Generating Electricity in Coal-Fired Power PlantsENGPDF412 KB
Application Report - Sand Trap and Preliminary Sedimentation StageENGPDF448 KB
Application Report - Screening Systems in Sewage Treatment PlantsENGPDF577 KB
Application Report - Sicherer Brennstofftransport in KohlekraftwerkenENGPDF391 KB
Application Report - Water Inlet in Wastewater Treatment PlantsENGPDF526 KB

Product Documentation: KFU8-UFT-Ex2.D

Language Selection:
Brief InstructionsLanguageFile TypeFile Size
Operator card KF**-UFT-**2.D / Bedienkarte KF**-UFT-**2.DALLPDF831 KB
Safety and Security Documentation
Instruction manualENGPDF166 KB
Manuals
Manual KF**-UFT-(Ex)2.DENGPDF1611 KB
ManualENGPDF3685 KB
Installation and configuration guide Device Type Manager (DTM)ENGPDF8665 KB

Design / Simulation: KFU8-UFT-Ex2.D

Language Selection:
CADLanguageFile TypeFile Size
CAD 3-D / CAD 3-DALLSTP2722 KB
CAD Portal / CAD PortalALLLINK---
CAE
CAE EPLAN Data Portal / CAE EPLAN Data PortalALLLINK---
EPLAN macro EDZ / EPLAN Makro EDZALLEDZ81 KB

Approvals: KFU8-UFT-Ex2.D

Language Selection:
CertificatesCertificate No.LanguageFile TypeFile Size
Australia Test SafeANZEx 17.3006XALLPDF6788 KB
Brasil TUV Rheinland BrazilTÜV 14.0357ALLPDF1122 KB
Canada FMFM22CA0016XALLPDF364 KB
China SITIIAS CCC Ex Certificate2020322316001449 (Singapore)ALLPDF1320 KB
DNV MarineTAA00001WXALLPDF106 KB
Europe TUV Nord ATEX Category (1) D ATEX Category (M1) ATEX Category (1) GTÜV 99 ATEX 1471ALLPDF682 KB
India PESO (India) CCOEA/P/HQ/KA/104/5784 (P478911)ALLPDF75 KB
South Africa MASCMASC MS/17-0881ALLPDF700 KB
USA FMCoC 3009603ALLPDF40 KB
Ukraine SERTIS ExSC 21.0646 XALLPDF12351 KB
United Kingdom CML UK-Type Examination Certificate UKEX Category (1) D UKEX Category (1) G UKEX Category (M1)CML 22UKEX2510ALLPDF140 KB
Worldwide TUV Nord IECEx Certificate of ConformityIECEx TUN 04.0007ALLLINK---
Control Drawings
Control drawing FM / Control drawing FM   ALLPDF156 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-2760AALLPDF80 KB

Software: KFU8-UFT-Ex2.D

Language Selection:
Device Description Files/DriversRelease InfoFile TypeFile Size
DTM Collection Interface Technology 2 / DTM Collection Interface Technology 21.4.110.77ZIP---
Software Tools
PACTware 4.1 SP6 / PACTware 4.1 SP64.1.0.53ZIP43327 KB
PACTware 5.0 / PACTware 5.05.0.5.31ZIP44203 KB
PACTware 6.X / PACTware 6.X6.1ZIP335938 KB

Associated Products: KFU8-UFT-Ex2.D

Matching System Components
Device DTM, For K-, E- and H-System, Frame application, like e. g. PACTware, must be installed separatelypa
Universal DTM host platform, For all DTMs of Pepperl+Fuchs, Approved FDT/DTM technology, Free of charge, Download from Pepperl+Fuchs websitepa
Isolated USB interface cable, Used with K-, E- and H-System devices, Used with PACTwarepa
Cable trunking is integrated in the mounting profile, Safe spacious separation of field and control signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Universal DTM host platform, For all DTMs of Pepperl+Fuchs, Approved FDT/DTM technology, Free of charge, Download from Pepperl+Fuchs websitepa
Accessories
1-channel, Dry contact input, For line fault detection (LFD)pa
1-channel, Precision resistor, Conversion of 0 mA ... 20 mA/0 V ... 5 Vpa
1-channel, Precision resistor, Conversion of 4 mA ... 20 mA/2 V ... 10 Vpa
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces greenpa
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces bluepa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.