OCT300-M1K-N2 Diffuse mode sensor, NAMUR
Key Benefits at a Glance
- ATEX-, IECEX approval for zone 20 (Dust) and zone 1 (Gas)
- Intrinsically safe, Ex op is ia IIC T6 Gb/IIIC T 135 °C Da
- Adjustable sensor head
- Scratch resistant mineral glass lens




Note
All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
EN
- DE
- EN
- ES
- FR
- ZH
Technical data of OCT300-M1K-N2
Diffuse mode sensor, NAMUR, special design, 300 mm detection range, infrared light, light/dark on, DC version, NAMUR output, terminal compartment |
Detection range | 0 ... 300 mm | |
Adjustment range | 70 ... 300 mm | |
Reference target | standard white 200 mm x 200 mm | |
Light source | IRED , 880 nm | |
Light type | modulated infrared light | |
Ambient light limit | ≤ 40000 Lux sun light ≤ 30000 Lux halogen light | |
Temperature influence | ≤ 0.5 mm/K |
MTTFd | 1319 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % |
Function indicator | LED yellow: switching state | |
Control elements | Sensing range adjuster |
Operating voltage | UB | 6 ... 20 V DC (Ri approx. 0 Ohm) |
Ripple | 5 % | |
Time delay before availability | tv | 20 ms |
Switching type | light/dark on, programmable | |||||||
Signal output | 1 NAMUR output NC/NO programmable | |||||||
Switching voltage | 8 V DC (Ri approx. 1 kΩ) | |||||||
Switching frequency | f | ≤ 100 Hz | ||||||
Current consumption | ||||||||
| ||||||||
Response time | 5 ms | |||||||
Repeat accuracy | R | ≤ 0.5 % of the sensing range |
Product standard | EN 60947-5-2 |
Standard conformity | |||||
|
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -40 ... 80 °C (-40 ... 176 °F) |
Degree of protection | IP20 | ||||||||||
Connection | M16 terminal compartment, core cross section ≤ 2.5 mm2 | ||||||||||
Material | |||||||||||
| |||||||||||
Mass | 100 g | ||||||||||
Dimensions | |||||||||||
|
EC-Type Examination Certificate | PTB 01 ATEX 2203 X | ||||||||||
Applicant | Pepperl+Fuchs GmbH, Lilienthalstrasse 200, 68307 Mannheim, Germany | ||||||||||
CE marking | CE0102 | ||||||||||
ATEX marking | Zone 1: ![]() | ||||||||||
Directive conformity | 2014/34/EU | ||||||||||
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 EN 60079-28:2007 | ||||||||||
Effective internal capacitance Ci | max. 75 nF | ||||||||||
Effective internal inductance Li | negligibly small | ||||||||||
General | The apparatus must be operated in accordance with the data provided in the datasheet and this operating instruction. In particular, the maximum rated voltage and the temperature range must be adhered to. The special conditions must be adhered to! The EU-type examination certificate has to be observed. | ||||||||||
Ambient temperature | The temperature ranges, according to temperature class, are given in the EC-Type Examination Certificate. | ||||||||||
Installation, commissioning | The associated apparatus must, as a minimum, fulfill the requirements for degree of protection ia and for Groups II or III, as appropriate for the operating conditions. Due to the possible risk of ignition that can occur as a result of faults and/or transient currents in the equipotential bonding system, galvanic isolation in the supply and signal current circuit is preferred. Associated apparatus without galvanic isolation may only be used if the appropriate requirements as set out in IEC 60079-14 are met. The intrinsic safety is only assured in connection with an appropriate related apparatus and according to the proof of intrinsic safety. | ||||||||||
Maintenance | No modifications must be undertaken on apparatus, which is operated in hazardous areas. Repairs to such apparatus are not permissible. | ||||||||||
Special conditions | |||||||||||
|
EC-Type Examination Certificate | ZELM 03 ATEX 0196 X | |||||||||||||
Applicant | Pepperl+Fuchs GmbH, Lilienthalstrasse 200, 68307 Mannheim, Germany | |||||||||||||
CE marking | CE0102 | |||||||||||||
ATEX marking | Zone 20/21: ![]() | |||||||||||||
Directive conformity | 2014/34/EU | |||||||||||||
Standards | EN 60079-0:2012+A11:2013 EN 60079-11:2012 EN 60079-28:2007 | |||||||||||||
Effective internal capacitance Ci | max. 1200 nF | |||||||||||||
Effective internal inductance Li | negligibly small | |||||||||||||
General | The apparatus must be operated in accordance with the data provided in the datasheet and this operating instruction. In particular, the maximum rated voltage and the temperature range must be adhered to. The special conditions must be adhered to! The EU-type examination certificate has to be observed. | |||||||||||||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |||||||||||||
Installation, commissioning | The associated apparatus must, as a minimum, fulfill the requirements for degree of protection ia and for Groups II or III, as appropriate for the operating conditions. Due to the possible risk of ignition that can occur as a result of faults and/or transient currents in the equipotential bonding system, galvanic isolation in the supply and signal current circuit is preferred. Associated apparatus without galvanic isolation may only be used if the appropriate requirements as set out in IEC 60079-14 are met. This certificate does not guarantee that the components installed in the partition isolate the zones completely from one another. Appropriate measures must be taken when the partition is set up to ensure the zones are completely isolated. | |||||||||||||
Maintenance | No modifications must be undertaken on apparatus, which is operated in hazardous areas. Repairs to such apparatus are not permissible. | |||||||||||||
Special conditions | ||||||||||||||
|
Certificate number | IECEx PTB 12.0060 X | ||||||||||
Applicant | Pepperl+Fuchs GmbH, Lilienthalstrasse 200, 68307 Mannheim, Germany | ||||||||||
IECEx marking | Zone 1: II 2G Ex ia op is IIC T6...T1 Gb | ||||||||||
Standards | IEC 60079-0:2011 IEC 60079-11:2011 IEC 60079-28:2006 | ||||||||||
Effective internal capacitance Ci | max. 75 nF | ||||||||||
Effective internal inductance Li | negligibly small | ||||||||||
General | The apparatus must be operated in accordance with the data provided in the datasheet and this operating instruction. In particular, the maximum rated voltage and the temperature range must be adhered to. The special conditions must be adhered to! The IECEx certificate must be observed. | ||||||||||
Ambient temperature | The temperature ranges, according to temperature class, are given in the EC-Type Examination Certificate. | ||||||||||
Installation, commissioning | The associated apparatus must, as a minimum, fulfill the requirements for degree of protection ia and for Groups II or III, as appropriate for the operating conditions. Due to the possible risk of ignition that can occur as a result of faults and/or transient currents in the equipotential bonding system, galvanic isolation in the supply and signal current circuit is preferred. Associated apparatus without galvanic isolation may only be used if the appropriate requirements as set out in IEC 60079-14 are met. The intrinsic safety is only assured in connection with an appropriate related apparatus and according to the proof of intrinsic safety. | ||||||||||
Maintenance | No modifications must be undertaken on apparatus, which is operated in hazardous areas. Repairs to such apparatus are not permissible. | ||||||||||
Special conditions | |||||||||||
|
Certificate number | IECEx ZLM 12.0005X | |||||||||||||
Applicant | Pepperl+Fuchs GmbH, Lilienthalstrasse 200, 68307 Mannheim, Germany | |||||||||||||
IECEx marking | Ex ia IIIC T135°C Da | |||||||||||||
Standards | IEC 60079-0:2011 IEC 60079-11:2011 | |||||||||||||
Effective internal capacitance Ci | max. 1200 nF | |||||||||||||
Effective internal inductance Li | negligibly small | |||||||||||||
General | The apparatus must be operated in accordance with the data provided in the datasheet and this operating instruction. In particular, the maximum rated voltage and the temperature range must be adhered to. The special conditions must be adhered to! The IECEx certificate must be observed. | |||||||||||||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |||||||||||||
Installation, commissioning | The associated apparatus must, as a minimum, fulfill the requirements for degree of protection ia and for Groups II or III, as appropriate for the operating conditions. Due to the possible risk of ignition that can occur as a result of faults and/or transient currents in the equipotential bonding system, galvanic isolation in the supply and signal current circuit is preferred. Associated apparatus without galvanic isolation may only be used if the appropriate requirements as set out in IEC 60079-14 are met. This certificate does not guarantee that the components installed in the partition isolate the zones completely from one another. Appropriate measures must be taken when the partition is set up to ensure the zones are completely isolated. | |||||||||||||
Maintenance | No modifications must be undertaken on apparatus, which is operated in hazardous areas. Repairs to such apparatus are not permissible. | |||||||||||||
Special conditions | ||||||||||||||
|