Serviceline Industrial Sensors
Sales phone: 0161 622 6308
Tech phone: 0161 622 6311
Fax: 0161 624 6537
Serviceline Explosion Protection
Sales phone: 0161 622 6309
Tech phone: 0161 622 6313
Fax: 0161 624 6537

Solenoid Driver KFD2-VM-Ex1.35.L

KFD2-VM-Ex1.35.L
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Output 15.3 V DC at 17 mA
  • 3 logic inputs with AND/OR logic
  • Service port for isolator function test

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  KFD2-VM-Ex1.35.L

General specifications
Signal typeDigital Output
Supply
ConnectionPower Rail or terminals 11+, 12-
Rated voltage20 ... 30 V DC
Ripple≤ 10 %
Rated current≤ 52 mA
Power dissipationtyp. 1.2 W
Power consumption< 1.5 W
Input
Connection sidecontrol side
Connectionterminals 7+, 8+, 9+
Signal level1-signal: 15 ... 30 V DC ; input current: approx. 2.3 mA at 24 V DC
0-signal: 0 ... 5 V DC or open input
Response delay5 ... 30 ms (typical 10 ms)
Output
Connection sidefield side
Internal resistormax. 410 Ω
Currenttyp. 18 mA
Voltagetyp. 16 V
Limitcurrent IE: ≥ 17 mA; typ. 18 mA
voltage UE: ≥ 15.3 V; typ. 16 V
Open loop voltagemin. 22.3 V
Connectionterminals 4+, 6-
Output current17 mA
Output signalThese values are valid for the rated operating voltages from 20 ... 30 V DC.
Transfer characteristics
Switching frequency15 Hz
Galvanic isolation
Input/power supplynot available
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2012
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 120 g
Dimensions20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) (W x H x D) , housing type B1
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificatePTB 00 ATEX 2132
MarkingEx-Hexagon II (1)GD [Ex ia] IIC [circuit(s) in zone 0/1/2]
OutputEx ia
Voltage25.2 V DC
Current67.2 mA
Power423.5 mW (linear characteristic)
Supply
Maximum safe voltage253 V AC/125 V DC without jumper 10-11, 60 V with jumper 10-11 (Attention! Um is no rated voltage.)
Input
Maximum safe voltage60 V (Attention! Um is no rated voltage.)
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Output/power supplysafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210101
ECLASS 12.027210190
ECLASS 11.027210190
ECLASS 10.0.127210190
ECLASS 9.027210190
ECLASS 8.027210190
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121008

Details: KFD2-VM-Ex1.35.L

Function

This isolated barrier is used for intrinsic safety applications. It supplies power to solenoids and other similar loads.

It is controlled by two "OR" and one "AND" configured logic input.

At full load, 15.3 V at 17 mA is available for the hazardous area load. The output signal has a resistive characteristic.

An override/test jack feature is available on the front plate of the device.

By engaging the service plug, the logic inputs are bypassed and the output is energized. The operation of this test feature is indicated by a red LED.

Informative Literature: KFD2-VM-Ex1.35.L

Language Selection:
LiteratureLanguageFile TypeFile Size
Application Report - Biological Cleaning of Wastwater and Secondary Sedimentation StageENGPDF566 KB
Application Report - Energy Generation in Wastwater Treatment PlantsENGPDF532 KB
Application Report - Generating Electricity in Coal-Fired Power PlantsENGPDF412 KB
Application Report - Sand Trap and Preliminary Sedimentation StageENGPDF448 KB
Application Report - Screening Systems in Sewage Treatment PlantsENGPDF577 KB
Application Report - Sicherer Brennstofftransport in KohlekraftwerkenENGPDF391 KB
Application Report - Water Inlet in Wastewater Treatment PlantsENGPDF526 KB

Product Documentation: KFD2-VM-Ex1.35.L

Language Selection:
Product informationLanguageFile TypeFile Size
Application Guideline Solenoid DriversENGPDF734 KB
Safety and Security Documentation
Instruction manualENGPDF49 KB
Manuals
ManualENGPDF3685 KB

Design / Simulation: KFD2-VM-Ex1.35.L

Language Selection:
CADLanguageFile TypeFile Size
CAD 3-D / CAD 3-DALLSTP105 KB
CAD Portal / CAD PortalALLLINK---
CAE
EPLAN macro EDZ / EPLAN Makro EDZALLEDZ56 KB

Approvals: KFD2-VM-Ex1.35.L

Language Selection:
CertificatesCertificate No.LanguageFile TypeFile Size
Europe PTB ATEX Category (1) GDPTB 00 ATEX 2132ALLPDF554 KB
Pepperl+Fuchs Functional Safety AssessmentFS-0065PF-20A ALLPDF69 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-1949AALLPDF52 KB

Associated Products: KFD2-VM-Ex1.35.L

Matching System Components

Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 2 m (6 foot), simple to customize to application space, Eliminates daisy-chainspa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 0.8 m (2.6 ft), simple to customize to application space, Eliminates daisy-chainspa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 1.6 m (5 foot), simple to customize to application space, Eliminates daisy-chainspa
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Cable trunking with integrated Power Rail UPR-03, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Provides DC supply voltage to all equipped K-System modules, Standard length 1.8 m (5.8 ft), simple to customize to application space, With end caps UPR-E, cover and mounting aidspa
Accessories
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces greenpa
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces bluepa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.