Download the complete datasheet as a PDF:
Product Description |
---|
Power supply, 24 to 30 V DC, 10 A |
General specifications | ||
---|---|---|
UL File Number | E223176 | |
Indicators/operating means | ||
LED Overload | Red LED lights up for overload, flashes for hiccup mode |
|
LED PWR | LED green | |
Potentiometer | Top: Output current limitation (covered by a dummy plug) Bottom: Output voltage adjustment |
|
Electrical specifications | ||
Fusing | 6.3 AT | |
Capacity factor | approx. 0.6 (Depending on input voltage) | |
Rated operating voltage | 115/230 V AC (for 115 V range, jumper) Range: 93 to 132 V AC/187 to 265 V AC |
|
Rated operating current | 4.0 A (115 V) 1.9 A (230 V) |
|
Supply frequency | 47 ... 63 Hz | |
Efficiency | approx. 89 % | |
Output | ||
Current limit | approx. 12 A | |
Voltage | 30 V ± 1 % Adjustment range 22.5 ... 29.5 V AC |
|
Current | 0 ... 10 A | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 55011, EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4, EN 61000-3-2 class A, EN 61000-3-3, EN 61010-1 | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Degree of protection | IEC 60529:2001 | |
Standard conformity | ||
Electromagnetic compatibility | EN 55011, EN 61000-6-1, EN 61000-6-2 | |
Standards | Harmonic waves: EN 61000-3-2 Class A Interference suppression: EN 55022, EN 55011 Class B Electrostatic discharge (ESD): IEC 61000-4-2 (8 kV contact discharge, 15 kV air discharge) Electromagnetic fields: IEC 61000-4-3 (10 V/m) Burst: IEC 61000-4-4 (4 kV input, 2 kV output/capacitively coupled) Surge: IEC 61000-4-5 (4 kV asymmetrical, 4 kV symmetrical) Conducted interference: IEC 61000-4-6 (10 V, 150 kHz to 80 MHz) |
|
Ambient conditions | ||
Ambient temperature | -10 ... 70 °C (14 ... 158 °F) with free convection | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Protection class | I, Protective conductor connection necessary | |
Connection | Connection terminals, max. conductor cross-section 0.5 to 2.5 mm2 Stripping length 5 to 6 mm |
|
Mass | approx. 1200 g | |
Dimensions | ||
Height | 132.5 mm | |
Width | 70 mm | |
Length | 140 mm | |
Mounting | DIN mounting rail |
System | Classcode |
---|---|
ECLASS 13.0 | 27040301 |
ECLASS 12.0 | 27040301 |
ECLASS 11.0 | 27040301 |
ECLASS 10.0.1 | 27040301 |
ECLASS 9.0 | 27040301 |
ECLASS 8.0 | 27040301 |
ECLASS 5.1 | 27040301 |
ETIM 9.0 | EC002540 |
ETIM 8.0 | EC002540 |
ETIM 7.0 | EC002540 |
ETIM 6.0 | EC002540 |
ETIM 5.0 | EC002540 |
UNSPSC 12.1 | 39121004 |
The slim-line power pack provides a direct voltage in an even larger adjustable output voltage range of 23 ... 30 V DC, while optimizing the space available in the control cabinet.
The current limit can be adjusted via an internal potentiometer. In addition to an LED showing the operational status (power), a red LED (overload) signals overloads on the output side.
The connecting leads on the input side are safely covered with the plastic cover after installation. The device features a convenient DIN rail fastening.
CAD | Language | File Type | File Size |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 100 KB |
CAD Portal / CAD Portal | ALL | LINK | --- |
Certificates | Certificate No. | Language | File Type | File Size |
---|---|---|---|---|
US CA UL | CoC E223176 RptRef E223176-20061107 | ALL | 443 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-6842 | ALL | 172 KB |