Power supply K26-STR-24VDC-2A

K26-STR-24VDC-2A
  • 2 A output load
  • 110 - 250 VAC supply voltage
  • 24 V DC output voltage
  • Continuous short-circuit and continuous open-circuit proof
  • LED operating display
  • SELV-Output
  • Compact design
  • 89 % efficiency level
  • Suitable for AS-Interface power supply in gateway-integrated data decoupling

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  K26-STR-24VDC-2A

Product Description
Power supply, 24 V DC, 2 A
General specifications
UL File NumberE223176
Indicators/operating means
LED POWERLED green
Electrical specifications
Fusing2.5 AT
Capacity factor0.45 capacitive at 230 VAC
0.5 capacitive at 120 VAC
Rated operating voltage94 ... 265 V AC
Rated operating current1.1 A (120 VAC)
0.6 A (230  VAC)
Supply frequency47 ... 63 Hz
Efficiency89 %
Nominal voltage110 ... 250 V AC
Peak inrush current< 1.5 A2s
Output
Current limit2.5 A
Voltage24 V ± 3 %
Current0 ... 2 A
Residual ripplemax. 50 mV
Holdup time> 70 ms/230 VAC
> 10 ms/120 VAC
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 55011:2009, EN 61000-6-2:2001, EN 61000-6-3:2001 EN 61000-6-1:2002, EN 61000-6-4:2002; DIN 61000-3-3:2006
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Degree of protectionIEC 60529:2001
Standard conformity
Electromagnetic compatibilityEN 55011:2009, EN 61000-6-2:2001, EN 61000-6-3:2001, EN 61000-3-2:2006, EN 61000-6-1:2002, EN 61000-6-4:2002; DIN 61000-3-3:2006
Electrical safetyAccording to VDE 0805:2006/EN 61010-1:2010/IEC 950:2006
Ambient conditions
Ambient temperature-10 ... 70 °C (14 ... 158 °F) with free convection
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Degree of protectionIP20
Protection classII
ConnectionConnection terminals, max. conductor cross-section
0.5 ... 2.5 mm2
stripped length 10 mm
Mass207 g
MountingSnap onto 35 mm standard rail compliant with DIN EN 60715:2001

Classifications

SystemClasscode
ECLASS 13.027040301
ECLASS 12.027040301
ECLASS 11.027040301
ECLASS 10.0.127040301
ECLASS 9.027040301
ECLASS 8.027040301
ECLASS 5.127040301
ETIM 9.0EC002540
ETIM 8.0EC002540
ETIM 7.0EC002540
ETIM 6.0EC002540
ETIM 5.0EC002540
UNSPSC 12.139121004

Details: K26-STR-24VDC-2A

Function

The particularly narrow power supply provides direct current with an output voltage of 24 V DC ± 3 % and provides optimum utilization of space in the control cabinet.

The wide range input enables operation with an input voltage of 94 to 265 V AC with an improved efficiency of 89 %.

The power supply is continuous open-circuit and continuous short-circuit proof. An LED indicates operation (power).

The device features a convenient mounting rail attachment.

Design / Simulation: K26-STR-24VDC-2A

Language Selection:
CADLanguageFile TypeFile Size
CAD 3-D / CAD 3-DALLSTP82 KB
CAD Portal / CAD PortalALLLINK---

Approvals: K26-STR-24VDC-2A

Language Selection:
CertificatesCertificate No.LanguageFile TypeFile Size
US CA ULCoC E223176 RptRef E223176-20061107ALLPDF443 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-6842ALLPDF172 KB
Free Download: White Paper on TCP-Based Communication Protocols (PDF)

This free PDF white paper compares the different TCP-based communication protocols (AMQP, OPC UA, MQTT, REST API) that have found their way up and are considered the enablers of IIoT and Industry 4.0. Get your free download now!

AS-Interface Product Range

Get to know our full range of AS-Interface products.