Frequency voltage current converter, 40 kHz version |
Functional safety related parameters | ||
---|---|---|
MTTFd | 100 a | |
Supply | ||
Rated voltage | 200 ... 230 V AC ; 100 … 130 V AC; 50/60 Hz 20 VDC ... 30 VDC |
|
Fusing | external fusing 4 A | |
Power consumption | AC: < 5 VA DC: < 5 W |
|
Indicators/operating means | ||
Type | 4-digit, 7-segment red display, 7 mm digit height | |
Display interval | 0.002 ... 9999 Hz or 0.01 ... 9999 min-1 |
|
Parameter assignment | keypad-driven menu | |
Input 1 | ||
Connection | terminals 8-, 9+ | |
Connectable sensor types | NAMUR sensors according to DIN EN 60947-5-6 | |
Open loop voltage | 8.2 V DC | |
Short-circuit current | 6.5 mA | |
Switching point | 1.2 ... 2.1 mA Switching hysteresis approx. 0.2 mA | |
Impedance | 1.2 kOhm | |
Input 2 | ||
Switching point | high: 16 ... 30 V DC; max.10 mA; Ri ≅ 3 kOhm low: 0 ... 6 V DC |
|
Connection | terminals 7+, 13- sensor supply terminals 14, 15 NPN/PNP input (galvanically isolated) |
|
Connectable sensor types | 2-, 3-, or 4-wire proximity sensors and incremental rotary encoder | |
Sensor supply | 19 ... 28 V DC non-stabilised; ≤ 30 mA short-circuit protected | |
Output | ||
Analog voltage output | 0 ... 10 V DC; 2 ... 10 V DC; 30 mA max.; resolution: 12 mV; Ri ≥ 330 Ω (terminal 5+, 6-) | |
Analog current output | 0 ... 20 mA; 4 ... 20 mA; resolution: 25 µA; Ri ≤ 600 Ω (terminal 4-, 5+) | |
Digital incrementing | ≥ (Ub -3 V), 20 mA, short-circuit proof (Terminals 1-, 2+) with frequency division Fin /1 ... Fin /9999 |
|
Transfer characteristics | ||
Input frequency | ≤ 40000 Hz, pulse pause/pulse length: ≥ 12 µs | |
Deviation | ≤ 0.2 % of full-scale value | |
Changing interval | 5 ms (Internal processing time) | |
Standard conformity | ||
Electromagnetic compatibility | acc. to EN 50081-2 / EN 50082-2 | |
Ambient conditions | ||
Ambient temperature | -25 ... 40 °C (-13 ... 104 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | max. 80 %, not condensing | |
Altitude | 0 ... 2000 m | |
Operating conditions | The device has only to be used in an indoor area. | |
Mechanical specifications | ||
Connection assembly | Caution: Please be aware that the device may only be connected to a switchable power supply. The switch or circuit breaker must be easy to reach and identified as the separator for the device. | |
Degree of protection | IP20 | |
Connection | coded, removable terminals , max. core cross section 0.34 ... 2.5 mm2 | |
Construction type | modular terminal housing in Makrolon, System KF For use in the switch cabinet/switch cabinet module |
|
Mounting | snap-on to 35 mm standard rail or screw fixing |
System | Classcode |
---|---|
ECLASS 13.0 | 27210904 |
ECLASS 12.0 | 27210904 |
ECLASS 11.0 | 27210904 |
ECLASS 10.0.1 | 27210904 |
ECLASS 9.0 | 27210904 |
ECLASS 8.0 | 27210904 |
ECLASS 5.1 | 27210904 |
ETIM 9.0 | EC002918 |
ETIM 8.0 | EC002918 |
ETIM 7.0 | EC002918 |
ETIM 6.0 | EC002918 |
ETIM 5.0 | EC002475 |
UNSPSC 12.1 | 39121007 |
The KFU8-FSSP-1.D frequency-voltage/current converter is a device for displaying and monitoring periodic signals, which occur in almost all areas of the automation and processing industry, i.e. frequencies in general and rotational speeds in particular.
Input pulses are evaluated according to the cycle method, i.e. by measurement of the periodicity, and are converted into a frequency or rotational speed by a μ controller. Depending on the measurement range value selected, the μ controller calculates a voltage or current value proportionate to the input frequency and exports this value via a digital-analog converter.
The following analogue signals are available for selection: 0 V ... 10 V, 2 V ... 10 V, 0 mA ... 20 mA, 4 mA ... 20 mA
The serially switched output provides the input frequency which can be subdivided by the adjustable factor (1 ... 9999).
Special consideration was given to the frequently occurring special case of rotational speed measurement during the development of the device. This makes it possible for the display and inputs to be either Hz or in min -1.
In addition, in applications with signal encoders that return multiple pulses per revolution, it is possible to operate automatically at the actual speed of the drive by assigning the number (1 ... 1200).
The frequency/voltage/current converter is supplied with 115 VAC, 230 VAC or 24 VDC. When it is connected with alternating voltage it provides an unstabilised 24-VDC source of power for the signal encoder.
All commonly available two- three- or four-wire proximity switches and incremental encoders on the input galvanically separated by an optical coupler are accepted as a signal source. In addition, two terminals are reserved for connecting proximity switches or incremental encoders in accordance with DIN 19234 (NAMUR).
The input signal frequency in Hz or the speed in min -1 - or the output signal voltage in V or current in mA - appears in a 4-place 7-segment LED display on the front of the device. Parameters can be set with 4 buttons underneath the display.
Manuals | Language | File Type | File Size |
---|---|---|---|
Manual KFU8-FSSP-1.D | ENG | 1041 KB |
CAD | Language | File Type | File Size |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 2019 KB |
CAE | |||
CAE EPLAN Data Portal / CAE EPLAN Data Portal | ALL | LINK | --- |
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZ | ALL | EDZ | 1699 KB |
Certificates | Certificate No. | Language | File Type | File Size |
---|---|---|---|---|
Canada, USA CSA | 80078445 | ALL | 198 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-1838C | ALL | 117 KB | |
UK Declaration of Conformity (P+F) / UK-Konformitäterklärung (P+F) | DOC-6863 | ALL | 107 KB |