Voltage Adjustment Module KLD0-SAA

FieldConnex® Fieldbus
KLD0-SAA
  • Series voltage reducing module
  • Removable terminals
  • Polarity reversal protected
  • Installation in cabinet on DIN mounting rail
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  KLD0-SAA

Product Description
Module for use with Segment Protectors
General specifications
Design / MountingCabinet installation
Installation in hazardous areaZone 2 / Div. 2
Fieldbus connection
Field-side
Connectionterminals 10+, 11-, 12S
Rated voltageUin - Uout 0.9 ... 1.8 V
Rated currentmax. 1 A
Host-side
Connectionterminals 7+, 8-, 9S
Rated voltage9 ... 32 V DC
Rated currentmax. 1 A
Power dissipationmax. 1.8 W
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity< 75 %
Pollution degreemax. 2, according to IEC 60664
Mechanical specifications
Connection typeTerminals
Core cross sectionup to 2.5 mm2
Housing20 mm x 115 mm x 107 mm
Degree of protectionIP20
Massapprox. 100 g
MountingDIN rail mounting
Data for application in connection with hazardous areas
CertificatePF 16 CERT 1030 X
MarkingEx-Hexagon II 3 G Ex ec IIC T4 Gc
Directive conformity
Directive 2014/34/EUEN 60079-0:2012 , EN 60079-7:2015
General information
Supplementary informationStatement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242692
ECLASS 12.019170104
ECLASS 11.027242692
ECLASS 10.0.127242692
ECLASS 9.027242692
ECLASS 8.027242692
ECLASS 5.127242692
ETIM 9.0EC002584
ETIM 8.0EC002584
ETIM 7.0EC002584
ETIM 6.0EC002584
ETIM 5.0EC001604
UNSPSC 12.139121008

Details: KLD0-SAA

Function

Pepperl+Fuchs Segment Protectors feature a safety switch off for explosion protection at typically 31.5 V.

In rare cases the tolerances in other manufacturers’ power modules in combination with very short cable lengths with little or no voltage drop lead to a switch off of the Segment Protector.

The KLD0-SAA is used to limit the voltage to uncritical values.

The KLD0-SAA is installed in close proximity to the power supply within the control cabinet.

Informative Literature: KLD0-SAA

Language Selection:
LiteratureLanguageFile TypeFile Size
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronENGPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingENGPDF470 KB

Product Documentation: KLD0-SAA

Language Selection:
Safety and Security DocumentationLanguageFile TypeFile Size
Instruction manualENGPDF51 KB

Approvals: KLD0-SAA

Language Selection:
CertificatesCertificate No.LanguageFile TypeFile Size
Europe Pepperl+Fuchs ATEX Category 3 G Declaration of ConformityPF16CERT1030XALLPDF192 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-2528CALLPDF1039 KB

Ethernet-APL enables continuous communication across all hierarchy levels. Learn more about the pioneering technology …

RSS Info Service for PANOS Updates

Stay informed when a new software update of PANOS, the operating system for Ethernet-APL switches, is released: With our RSS Feed you will get an email notfication in your inbox immediately after an update has been released.

From decisions to planning, installation, and commissioning up to operation and maintenance: Discover how to make the most out of your fieldbus infrastructure …