Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
Product Description |
---|
Segment protector, junction box for fieldbus with short-circuit and fault protection, field junction box, stand-alone device in aluminum housing for field installation |
General specifications | ||
---|---|---|
Design / Mounting | Outside installation | |
Installation in hazardous area | Zone 2 / Div. 2 | |
Fieldbus connection | ||
Main cable (Trunk) | ||
Cable entry type | see table 2 | |
Rated voltage | 9 ... 31 V DC 10.5 V DC minimum input voltage acc. to FF-846 |
|
Rated current | max. 4.5 A | |
Outputs | ||
Number of outputs | see table "Technical data depending on model" | |
Cable entry type | see table 2 | |
Number of devices per output | 1 | |
Rated voltage | max. 31 V | |
Rated current | max. 32 mA jumper 1, position 2 max. 43 mA jumper 1, position 1 |
|
Short-circuit current | 46 mA jumper 1, position 2 57 mA jumper 1, position 1 |
|
Self current consumption | see table "Technical data depending on model" | |
Voltage drop main cable/outputs | max. 1.2 V | |
Voltage drop trunk In/Out | 0 V | |
Terminating resistor | selectable via Jumper 100 Ω +/- 10 % | |
Surge protection | trunk, spurs overvoltage protected if voltage exceeds typ. 39 V, max. 41 V | |
Indicators/operating means | ||
LED PWR | green: Fieldbus voltage > 10 V and fieldbus terminator is deactivated | |
LED PWR/TERM | green: Fieldbus voltage > 10 V and fieldbus terminator is activated | |
LED COM/ERR | yellow: flashing: fieldbus communication status and physical layer diagnostic status | |
LED SPURS | red: 2 Hz flashing in short-circuit condition | |
Jumper 1 | configuration of short-circuit current/rated current | |
Jumper 2 | configuration of grounding option for trunk and cable screen/shield | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | ||
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Climatic conditions | IEC 60721 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | see table 2 | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | < 95 % non-condensing | |
Shock resistance | 15 g , 11 ms | |
Vibration resistance | 5 g , 10 ... 150 Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Connection type | screw terminal , fixed screw terminal , pluggable spring terminal |
|
Core cross section | max. 2.5 mm2 /AWG 12-24 | |
Cable diameter | see table 3 | |
Housing | see figure 1 | |
Housing material | Aluminum | |
Degree of protection | IP66 | |
Mass | max 2.6 kg , depending on model | |
Dimensions | see table 2 | |
Mounting | wall mounting | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | TÜV 13 ATEX 107689 X | |
Marking | II 3G Ex nA [ic] IIC T4 Gc , II 2(3)D Ex tb [ic Dc] IIIC T130°C Db |
|
Supply | ||
Maximum safe voltage | 35 V | |
Outputs | ||
Voltage | 32 V | |
Current | 46 mA jumper 1, position 2 65 mA jumper 1, position 1 |
|
Inductance | 0.25 mH jumper 1, position 1 0.125 mH jumper 1, position 2 |
|
Capacitance | 60 nF | |
Directive conformity | ||
Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-31:2014 | |
International approvals | ||
IECEx approval | IECEx TUN 13.0004X | |
Approved for | Ex nA [ic] IIC T4 Gc , Ex tb [ic Dc] IIIC T130°C Db |
|
Certificates and approvals | ||
FOUNDATION Fieldbus | FF-846 | |
General information | ||
Supplementary information | Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
Accessories |
System | Classcode |
---|---|
ECLASS 13.0 | 27242610 |
ECLASS 12.0 | 27242610 |
ECLASS 11.0 | 27242610 |
ECLASS 10.0.1 | 27242610 |
ECLASS 9.0 | 27242610 |
ECLASS 8.0 | 27242610 |
ECLASS 5.1 | 27242601 |
ETIM 9.0 | EC001601 |
ETIM 8.0 | EC001601 |
ETIM 7.0 | EC001601 |
ETIM 6.0 | EC001601 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121008 |
The F2 Segment Protector with integrated diagnostics, a device coupler in aluminum housing, connects 4 ... 10 instruments to the segment with intrinsic safety (Ex ic, Zone 2). Device connections in Zone 1 require additional methods of ignition protection. Pre-engineering options are: cable glands in various materials; a choice of fixed or plug-in terminals with screw or spring-clamp connections. Short circuit, jabber, and bounce protection isolate most fault condition types from the segment.
The short circuit current limitation is adjustable for maximum load with Ex ic for gas groups IIB and IIC. The shield can be connected hard-to-ground or floating. A terminator with LED indication is selectable via jumper.
Short circuit protection ensures proper operation of the segment in case of unwanted faults at the spur. Intrinsic safety at the spur enables work on devices with hot work permit. The integrated fieldbus terminator features a high-availability design and can be chosen via a jumper.
Literature | Language | File Type | File Size |
---|---|---|---|
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-Synchrotron | ENG | 361 KB | |
Application Report - Digital Communication in Steel-Plate Manufacturing | ENG | 470 KB |
Safety and Security Documentation | Language | File Type | File Size |
---|---|---|---|
Instruction manual | ENG | 232 KB | |
Manuals | |||
Manual Segment Protector F2-SP-IC* | ENG | 2835 KB |
Certificates | Certificate No. | Language | File Type | File Size |
---|---|---|---|---|
Brasil TUV Rheinland Brazil | TÜV 14.1592 X | ALL | 1121 KB | |
China SITIIAS CCC Ex Certificate | 2020322310002785 (Singapore) | ALL | 1722 KB | |
DNV Marine | TAA0000272 | ALL | 100 KB | |
Europe TUV Nord ATEX II 3 G | TÜV 13 ATEX 107689X | ALL | 553 KB | |
India PESO (India) CCOE | A/P/HQ/KA/104/6097 (P579055) | ALL | 105 KB | |
TUV Nord Ex nA nC Ex tb IECEx Certificate of Conformity | IECEx TUN 13.0004X | ALL | LINK | --- |
Worldwide Fieldbus Foundation | DC084300 | ALL | 56 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-0193D | ALL | 1292 KB |
Variants | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
|
RSS Info Service for PANOS Updates
Stay informed when a new software update of PANOS, the operating system for Ethernet-APL switches, is released: With our RSS Feed you will get an email notfication in your inbox immediately after an update has been released.