Pressure Transmitter PPC-M51

PPC-M51
  • Device for absolute pressure and gauge pressure measurement in gases, steams or liquids
  • Large selection of process connections: universal use
  • Temperature range up to 130 °C (266 °F)
  • Pressure range up to 40 bar (600 psi)
  • Easy commissioning without the need for an operating tool
  • Configurable by PACTware

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  PPC-M51

General specifications
Construction typesensor: ceramic sensor
ceramic diaphragm
SeriesPPC-M51
Supply
Rated voltageversions for safe area:
11.5 ... 45 V DC, 2-wire
11.5 ... 35 V DC, HART, 2-wire
9 ... 32 V DC, PROFIBUS PA
version for hazardous area see safety information (SI)
Input
Measured variableabsolute or relative pressure
Measuring range0.1 ... 40 bar
max. turn down: 100:1
Output
Output signal4 ... 20 mA , analog , 2-wire
4 ... 20 mA with superimposed digital communication protocol HART 6.0, 2-wire
digital communication signal PROFIBUS PA (Profile 3.02)
Communication4 ... 20 mA HART (standard)
PROFIBUS PA (option)
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2006 , EN 61326-2-3:2006 , EN 61326-2-5:2006
Low voltage
Directive 2014/35/EUEN 61010-1:2010
Conformity
Degree of protectionIEC 60529:2001
Measurement accuracy
Accuracyreference accuracy: ±0.15 % (standard), ±0.075 % (platinum)
The reference accuracy comprises the non-linearity according to limit point setting, hysteresis and non-reproducibility acc. to IEC 60770. The data refer to the calibrated span.
Long-term driftup to ±0.1 % of upper range limit (URL)/year
Operating conditions
Process conditions
Process temperature-40 ... 100 °C (-40 ... 212 °F)
hygienic versions: -40 ... 130 °C (-40 ... 266 °F), 150 °C/1h (302 °F/1h)
Ambient conditions
Ambient temperature-40 ... 85 °C (-40 ... 185 °F)
with display : -20 ... 70 °C (-4 ... 158 °F)
Mechanical specifications
Degree of protectionIP66, NEMA 4X
IP68, NEMA 6P (24 hours in water 1.83 m (6 ft) deep)
IP69K (with separate housing and FEP cable)
Connectiongland M20
thread M20, G1/2, NPT1/2
device plug M12
HAN7D Harting connector, angled
valve connector acc. ISO 4400, cable 5 m
Materialmaterials in contact with process : Al2O3 ceramic (ultrapure 99.9 %)
housing:
- die-cast aluminum with protective powder-coating on polyester base, housing F31
- stainless steel AISI 316L (1.4404), housing F15
measuring cell seal: Viton, EPDM, NBR, Kalrez
Process connectionthreads ISO 228: G1/2, G1, G1-1/2, G2
threads ANSI: NPT1/2, NPT1, NPT1-1/2, NPT2
hygienic process connections: Clamp, Varivent, DRD, DIN 11851, DIN 11864, NEUMO, APV, uni adapter
flanges: EN 1092-1: DN 25 ... DN 80, ANSI 16.5: 1 ... 4 inch, JIS B2220
Data for application in connection with hazardous areas
EU-type examination certificatesee instruction manuals (SI)
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-31:2009
International approvals
FM approvalsee instruction manuals (SI)
CSA approvalsee instruction manuals (SI)
IECEx approvalsee instruction manuals (SI)
Certificates and approvals
Drinking water approvalNSF61 approval
General information
Supplementary documentationtechnical information (TI)
manuals, brief instructions (BA, KA)
instruction manuals (SI)
control drawings (ZD)
approval (ZE)
Supplementary informationEC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.
Accessories
Designationsee technical information (TI)

Classifications

SystemClasscode
ECLASS 13.027200516
ECLASS 12.027200516
ECLASS 11.027200516
ECLASS 10.0.127200516
ECLASS 9.027200516
ECLASS 8.027200516
ECLASS 5.127200516
ETIM 9.0EC001447
ETIM 8.0EC001447
ETIM 7.0EC001447
ETIM 6.0EC001447
ETIM 5.0EC001447
UNSPSC 12.141111950

Details: PPC-M51

Function

The device is used for absolute pressure and gauge pressure measurement in gases, steams or liquids.

The device has a capacitive measuring cell and a ceramic process isolating diaphragm.

The ceramic sensor is a dry sensor. The process pressure acts directly on the robust ceramic process isolating diaphragm and deflects it. A pressuredependent change in capacitance is measured at the electrodes of the ceramic substrate and the process isolating diaphragm. The measuring range is determined by the thickness of the ceramic process isolating diaphragm.

The data is transmitted to the control via analog signal, HART protocol or PROFIBUS PA.

The device is easily configured by the use of keypad or with the PACTware configuration software.

The device is designed modular and offers a variety of process connections, a replaceable display and a universal electronics.

Product Documentation: PPC-M51

Language Selection:
Product informationLanguageFile TypeFile Size
TI00436O, Technical Information LHC, PPCENGPDF8119 KB
Brief Instructions
KA1030O, brief instructions LHC-M51, PPC-M51 4 mA ... 20 mA HARTENGPDF1633 KB
KA1031O, brief instructions LHC-M51, PPC-M51 PROFIBUS PAENGPDF5215 KB
KA1036O, brief instructions LHC-M51, PPC-M51 4 mA ... 20 mA AnalogENGPDF802 KB
Safety and Security Documentation
SI00466O, Instruction manual LHC-M51, PPC-M51ENGPDF1246 KB
SI00469O, Instruction manual LHC-M51, PPC-M51ENGPDF675 KB
SI00489O, Instruction manual LHC-M51, PPC-M51ENGPDF836 KB
Safety ManualENGPDF1256 KB
Safety ManualENGPDF1268 KB
Safety ManualENGPDF1293 KB
Manuals
BA382O, Manual LHC-M51, PPC-M51 4 mA ... 20 mA HARTENGPDF2974 KB
BA383O, Manual LHC-M51, PPC-M51 PROFIBUS PAENGPDF2820 KB
BA385O, Manual LHC-M51, PPC-M51 4 mA ... 20 mA AnalogENGPDF1512 KB

Design / Simulation: PPC-M51

Language Selection:
CADLanguageFile TypeFile Size
CAD 3-D / CAD 3-DALLSTP776 KB
CAD 3-D additional / CAD 3-D additionalALLSTP766 KB
CAD 3-D additional / CAD 3-D additionalALLSTP798 KB
CAD Portal / CAD PortalALLLINK---

Approvals: PPC-M51

Language Selection:
CertificatesCertificate No.LanguageFile TypeFile Size
Canada, USA CSACSA 14.70009779ALLPDF100 KB
DEKRA Ex ia Ex ta Ex ic IECEx Certificate of ConformityIECEx DEK 13.0056ALLLINK---
Europe DEKRA ATEX Category 1/2 D ATEX Category 2 G ATEX Category 1/2 GDEKRA 13 ATEX 0142ALLPDF306 KB
Europe Pepperl+Fuchs ATEX Category 3 G CertificatePF 13 CERT 2814 XALLPDF193 KB
Europe Pepperl+Fuchs ATEX Category 3 G CertificatePF 13 CERT 2815ALLPDF225 KB
Control Drawings
Control drawing CSA / Control drawing CSA   ALLPDF112 KB
Control drawing CSA / Control drawing CSA   ALLPDF100 KB
SI00563O, Instruction manual FM LHC-M51, PPC-M51 4 ... 20 mA HART   ENGPDF156 KB
SI00564O, Instruction manual FM LHC-M51, PPC-M51 PROFIBUS PA   ENGPDF169 KB
Control drawing CSA / Control drawing CSA   ALLPDF108 KB
Control drawing CSA / Control drawing CSA   ALLPDF99 KB
SI00556O, Instruction manual CSA LHC-M51, PPC-M51 4 ... 20 mA HART   ENGPDF154 KB
SI00558O, Instruction manual CSA LHC-M51, PPC-M51 PROFIBUS PA   ENGPDF164 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0213EALLPDF257 KB
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0251BALLPDF107 KB
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0249BALLPDF120 KB
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0247BALLPDF121 KB
Contamination Declaration
Contamination declaration / Kontaminationserklärung   ALLPDF137 KB

Software: PPC-M51

Language Selection:
Device Description Files/DriversRelease InfoFile TypeFile Size
GSD / GSDPF__0E3A.GSDZIP11 KB

Associated Products: PPC-M51

Accessories
Universal DTM host platform, For all DTMs of Pepperl+Fuchs, Approved FDT/DTM technology, Free of charge, Download from Pepperl+Fuchs websitepa
Device DTM, For level devices, Frame application, like e. g. PACTware, must be installed separatelypa
Functional Safety Hub from Pepperl+Fuchs

Several hundred products with a SIL/PL assessment, free tools, and brochures in one place: the "Functional Safety Hub" is your starting point when you have to implement safety functions.