Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
Product Description |
---|
Surge protector, Ethernet-APL, control cabinet installation, Ex ia, Ex ec, direct shield grounding |
General specifications | ||
---|---|---|
Design / Mounting | Cabinet installation | |
Installation in hazardous area | Zone 1 | |
Ethernet Interface | ||
Interface type | Ethernet-APL auxiliary device | |
Electrical specifications | ||
Rated voltage | 30 V | |
Rated current | 500 mA | |
Impulse rating | 2 kV/1 kA (category C1) per line 10 kV/5 kA (category C2) per line 1 kA (category D1) per line |
|
Impulse discharge current (10/350 µs) | 0.5 kA per line | |
Nominal discharge current (8/20 µs) | ||
per line | 5 kA | |
total | 10 kA | |
Shield | 10 kA | |
Max. surge current (8/20 µs) | 10 kA overstressed fault mode 3 acc. to IEC 61643-21 | |
Voltage protection level | ||
Line/Earth | max. 1500 V C1 , 1 kA per line max. 2100 V C2 , 5 kA per line max. 50 V C3 , 50 A per line max. 1300 V B2 , 50 A per line |
|
Standard conformity | ||
Degree of protection | IEC/EN 60529 | |
Climatic conditions | IEC 60721 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Surge protection | IEC 61643-21 | |
Ethernet | Ethernet-APL , IEEE 802.3 for 10BASE-T1L |
|
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Storage temperature | -50 ... 90 °C (-58 ... 194 °F) | |
Relative humidity | ≤ 95 % non-condensing | |
Shock resistance | 15 g 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Mechanical specifications | ||
Connection type | screw terminals | |
Core cross section | solid wire 0.5 ... 2.5 mm2 , stranded wire 0.5 ... 1.5 mm2 |
|
Housing material | Polyamide PA 6.6 | |
Degree of protection | IP20 | |
Mass | 32 g | |
Mounting | DIN mounting rail | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | TÜV 22 ATEX 8786 X , TÜV 22 ATEX 8816 X | |
Marking | 2-WISE auxiliary device , FISCO | |
Marking | ll 3 G Ex ec llC T6 Gc , ll 2 (1) G Ex ia [ia Ga] IIC T6 Gb , ll 2 (1) D Ex ia [ia Da] lIIC T80°C Db , l M2 (M1) Ex ia [ia Ma] l Mb |
|
Voltage | 30 V | |
Current | 500 mA | |
Internal capacitance | negligible 0 nF | |
Internal inductance | negligible 0 µH | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2018 , EN 60079-11:2012 , IEC TS 60079-47:2021 |
|
Supplementary information | ||
International approvals | ||
IECEx approval | IECEx TUR 22.0017X | |
Approved for | Ex ec llC T6 Gc , Ex ia [ia Ga] IIC T6 Gb , Ex ia [ia Da] lIIC T80°C Db , Ex ia [ia Ma] l Mb |
|
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27171202 |
ECLASS 12.0 | 27171202 |
ECLASS 11.0 | 27130805 |
ECLASS 10.0.1 | 27130805 |
ECLASS 9.0 | 27130805 |
ECLASS 8.0 | 27130805 |
ECLASS 5.1 | 27130801 |
ETIM 9.0 | EC000941 |
ETIM 8.0 | EC000941 |
ETIM 7.0 | EC000941 |
ETIM 6.0 | EC000941 |
ETIM 5.0 | EC000941 |
UNSPSC 12.1 | 39121610 |
The surge protector protects spur ports of Ethernet-APL field switches used with Ethernet-APL field devices and PROFIBUS PA field devices.
The surge protector directs power from voltage surges and lightning to earth via gas discharge tubes.
For direct grounding of both ends of the cable shield, the surge protector connects the cable shield directly to ground.
The device is certified intrinsically safe for circuits in explosion-hazardous areas Zone 0 ... 2 according to 2‑WISE and FISCO. The surge protector can be installed in Zone 1 ... 2.
Mounting on a 35 mm DIN mounting rail permits installation in cabinets or fieldbus junction boxes.
Literature | Language | File Type | File Size |
---|---|---|---|
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-Synchrotron | ENG | 361 KB | |
Application Report - Digital Communication in Steel-Plate Manufacturing | ENG | 470 KB |
Safety and Security Documentation | Language | File Type | File Size |
---|---|---|---|
Instruction manual | ENG | 164 KB | |
Manuals | |||
Manual | ENG | 1648 KB |
CAD | Language | File Type | File Size |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 3749 KB |
Certificates | Certificate No. | Language | File Type | File Size |
---|---|---|---|---|
China SITIIAS CCC Ex Certificate | 2022322304004748 (Singapore) | ALL | 1107 KB | |
Europe TUV Rheinland ATEX Certificate Surge Protective Device ATEX Category 2 (1) | TÜV 22 ATEX 8786 X | ALL | 1538 KB | |
Europe TUV Rheinland Surge Protective Device ATEX Category 3 G TÜV Atex | TÜV 22 ATEX 8816 X | ALL | 171 KB | |
Worldwide TUV Rheinland Surge Protective Device IECEx Certificate of Conformity | IECEx TUR 22.0017X | ALL | LINK | --- |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) | TDOC-5856_ENG | ENG | 176 KB |