Serviceline Industriële Sensoren
Serviceline Explosiebeveiliging
Niet beschikbaar voor verkoop
Niet beschikbaar voor verkoop

Solenoid Driver KFD2-RCI-Ex1

KFD2-RCI-Ex1
  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Output 20.4 mA at 13.5 V DC
  • 19 V DC ... 30 V DC input
  • Line fault detection (LFD)
  • Conformal coating
  • Up to SIL 3 acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

De complete datasheet als PDF downloaden:


Technische gegevens  KFD2-RCI-Ex1

General specifications
Signal typeDigital Output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Supply
ConnectionPower Rail or terminals 14+, 15-
Rated voltage19 ... 30 V DC
Rated current< 35 mA
Power consumption< 0.8 W
Input
Connection sidecontrol side
Connectionterminals 10+, 11-
Input current40 mA at 19 ... 30 V DC
Signal level1-signal: 19 ... 30 V DC
0-signal: 0 ... 5 V DC
Power consumption< 1.2 W
Operating modeloop powered
Output
Connection sidefield side/control side
Connectionterminals 1+, 3- (terminals 1+, 2 for test loop)
Internal resistorapprox. 275 Ω
Current≤ 20.4 mA
Voltage≥ 13.5 V
Open loop voltage> 16 V
Voltage1-signal: > 13.5 V
Current1-signal: 20.4 A
0-signal: 4.2 mA
Loadmax. 650 Ω
Response time< 40 ms input to output
Line fault detectionshort circuit voltage < 1 V , open circuit voltage > 16 V
Output II
Connectionterminal 7: source (-) or sink (+), terminal 8: source (+), terminal 9: sink (-)
Current11 mA (source or sink mode)
Voltage9 ... 30 V sink mode from external supply
Loadmax. 650 Ω , source mode , for HART ≥ 230 Ω
Communicationpass-through of HART signal between input II and output
Galvanic isolation
Input/power supplyfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Output II/power supplyfunctional insulation acc. to IEC 62103, rated insulation voltage 50 Veff
Indicators/settings
Display elementsLEDs
Control elementsDIP switch
Configurationvia DIP switches
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2012
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 150 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Height119 mm
Width20 mm
Depth115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateCESI 09 ATEX 037
MarkingEx-Hexagon II (1)GD [Ex ia] IIC; [Ex iaD] [circuit(s) in zone 0/1/2/20/21/22]
Equipmentterminals 1+, 2 / 3-
Voltage24.5 V
Current93.6 mA
Power595 mW (linear characteristic)
Supply
Maximum safe voltage253 V (Attention! The rated voltage can be lower.)
Input
Maximum safe voltage253 V (Attention! The rated voltage can be lower.)
Collective error message
Maximum safe voltage253 V (Attention! The rated voltage can be lower.)
CertificatePF 09 CERT 1438 X
MarkingEx-Hexagon II 3G Ex nA IIC T4 Gc
Galvanic isolation
Output I/other circuitssafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
CSA approval
Control drawing116-0335
IECEx approval
IECEx certificateIECEx CES 09.0008
IECEx marking[Ex ia] IIC , [Ex iaD]
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210101
ECLASS 12.027210190
ECLASS 11.027210190
ECLASS 10.0.127210190
ECLASS 9.027210190
ECLASS 8.027210190
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121008

Details: KFD2-RCI-Ex1

Product Documentation: KFD2-RCI-Ex1

Taalkeuze:
Product informationTaalBestandstypeBestandsgrootte
Application Guideline Solenoid DriversENGPDF734 KB
Safety and Security Documentation
HandleidingHOLPDF72 KB
Safety ManualENGPDF597 KB
Manuals
ManualENGPDF3685 KB

Design / Simulation: KFD2-RCI-Ex1

Taalkeuze:
CADTaalBestandstypeBestandsgrootte
CAD 3-D / CAD 3-DALLSTP2510 KB
CAE
EPLAN macro EDZ / EPLAN Makro EDZALLEDZ75 KB

Approvals: KFD2-RCI-Ex1

Taalkeuze:
CertificatesCertificaatnummerTaalBestandstypeBestandsgrootte
CESI IECEx Certificate of ConformityIECEx CES 09.0008ALLLINK---
Canada FMCoC 3037174CALLPDF52 KB
Europe CESI ATEX Category (1) GDCESI 09 ATEX 037ALLPDF989 KB
Europe Pepperl+Fuchs Certificate of Compliance ATEX Category 3PF 09 CERT 1438 XALLPDF197 KB
USA FMCoC 3037174ALLPDF52 KB
exida Functional Safety AssessmentP+F 0905-35R1-C R015 V1R0ALLPDF599 KB
exida Functional Safety AssessmentP+F 08-07-21 R033 V1R0ALLPDF119 KB
Control Drawings
Control drawing FM / Control drawing FM   ALLPDF111 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0906BALLPDF54 KB

Aanverwante producten: KFD2-RCI-Ex1

Matching System Components

Interface for Power Rail, Supply current ≤ 4 A, Replaceable fuse, Relay contact output, reversible, LED status indicationpa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 2 m (6 foot), simple to customize to application space, Eliminates daisy-chainspa

35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 0.8 m (2.6 ft), simple to customize to application space, Eliminates daisy-chainspa
35 mm DIN mounting rail with 3-conductor insert, Provides DC supply voltage to all equipped K-System modules, Standard length 1.6 m (5 foot), simple to customize to application space, Eliminates daisy-chainspa
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Cable trunking with integrated Power Rail UPR-03, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Provides DC supply voltage to all equipped K-System modules, Standard length 1.8 m (5.8 ft), simple to customize to application space, With end caps UPR-E, cover and mounting aidspa
Accessories
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces greenpa
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces bluepa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa