Serviceline Industriële Sensoren
Serviceline Explosiebeveiliging

I/O hub ICA-16DI-G16-IO

ICA-16DI-G16-IO
  • IO-Link Class A
  • IO-Link 1.1.4
  • LED for switching state and fault indication
  • Configuration and control via IO-Link
  • Supply from IO-Link
  • 16 digital inputs

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

De complete datasheet als PDF downloaden:


Technische gegevens  ICA-16DI-G16-IO

Productbeschrijving
I/O hub with IO-Link interface for 16 digital inputs
Indicators/operating means
LED PWRLED green: flashing with short break (1 Hz) - IO-Link mode
LED IOSwitch state (IO); multicolor LED
yellow: only IO pin 4 is active
blue: only IO pin 2 is active
green: both IO pin 4 and pin 2 are active
red: overload at sensor supply or output
Electrical specifications
Operating voltage18 ... 30 V DC, PELV
Current limitation of the supply max. 4 A
No-load supply current≤ 25 mA
Operating currentmax. 4 A
Interface
Interface typeIO-Link
IO-Link revision1.1
Device profileIdentification and Diagnosis - I&D
Firmware update
Process dataInputs 3 Byte
- Input signals 16 Bit
- diagnosis signals 5 Bit
Vendor ID1 (0x0001)
Device ID985857 (0x0F0B01)
Data transfer rateCOM3 (230.4 kbits/s)
Min. cycle time1 ms
SIO mode supportno
Compatible master port typeClass A
Input
Number/Type16 Inputs for 3-wire sensors (PNP), DC (IN1 ... IN16)
Supplyfrom IO-Link
Current loading capacity180 mA , overload and short-circuit protected
Input current≤ 5 mA (limited internally)
Switching pointType 3 according to IEC 61131-2
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
EN 55011:2016
Conformity
Communication interfaceIEC 61131-9:2013
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardEN 61131-9:2013
InputEN 61131-2:2007
Communication interfaceIEC 61131-9 / IO-Link V1.1.4
Emitted interferenceEN 61000-6-4:2007
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006
Approvals and certificates
UL approval
Load specification DC General Use / DC Pilot Duty
Degree of protection not tested by UL; tested by Pepperl+Fuchs SE
Ambient conditions
Ambient temperature-30 ... 70 °C (-22 ... 158 °F)
Storage temperature-30 ... 70 °C (-22 ... 158 °F)
Relative humidity85 % non-condensing
Climatic conditionsFor indoor use only
Altitude≤ 5000 m above MSL
Shock and impact resistance30 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks
Vibration resistance0.35 mm / 5 g 5 ... 500 Hz
Pollution degree3
Mechanical specifications
Degree of protectionIP67 / IP68 / IP69k
ConnectionIO-Link: M12 round plug connector in accordance with EN 61076-2-101, LM type (4-pin, connector contacts, screw-locking, A-coded)
Female connector: LF type or similar
IN: M8 round plug connector in accordance with EN 61076-2-104, LF type (4-pin, socket contacts, screw-locking, A-coded)
Mating connector: LM type or similar
Material
HousingPBT
Mass110 g
Tightening torque, cable gland0.4 Nm (M12 connector),
0.2 Nm (M8 connector)
Dimensions
Height29.35 mm
Width30 mm
Length143 mm
Mountingscrew mounting

Classifications

SystemClasscode
ECLASS 13.027242604
ECLASS 12.027242604
ECLASS 11.027242604
ECLASS 10.0.127242604
ECLASS 9.027242604
ECLASS 8.027242604
ECLASS 5.127242604
ETIM 9.0EC001597
ETIM 8.0EC001597
ETIM 7.0EC001597
ETIM 6.0EC001597
ETIM 5.0EC001597
UNSPSC 12.132151705

Details: ICA-16DI-G16-IO

Product Documentation: ICA-16DI-G16-IO

Taalkeuze:
Parameter InformationTaalBestandstypeBestandsgrootte
IO-Link Parameter Datasheet ICA-16DI-G16-IOENGPDF338 KB

Approvals: ICA-16DI-G16-IO

Taalkeuze:
Declaration of ConformityCertificaatnummerTaalBestandstypeBestandsgrootte
EU Declaration of Conformity (P+F)TDOC-7805_HOLHOLPDF194 KB
UK Declaration of Conformity (P+F)TDOC-7806_ENGENGPDF171 KB

Software: ICA-16DI-G16-IO

Taalkeuze:
Device Description Files/DriversVrijgave-informatieBestandstypeBestandsgrootte
IODD for ICA-16DI-G16-IO / IODD für ICA-16DI-G16-IOV1.00.000 / 2024-10-25ZIP215 KB
Software Tools
IO-Link Offline Parameterization Tool / IO-Link Offline-ParametriertoolV1.00.006 / 2022-07-10ZIP96138 KB
Gratis Download: Whitepaper over TCP-gebaseerde communicatieprotocollen (pdf)

Dit gratis whitepaper vergelijkt de verschillende TCPgebaseerde -communicatieprotocollen (AMQP, OPC UA, MQTT, REST API) die zich overal hebben ingeburgerd en als sleuteltechnologieën voor IIoT en Industrie 4.0 worden beschouwd. Download uw gratis exemplaar!

AS-i-schakelkastmodule KE5 – Gebruiksgemak en verbeterde bestuurbaarheid

Het unieke behuizingsconcept van de nieuwe KE5-schakelkastmodule biedt duidelijke zichtbaarheid en vereenvoudigt montage, aansluiting en onderhoud in schakelkasten en junction boxes.

As-interface productportfolio

Ontdek ons volledig As-interface productportfolio.