Serviceline Industrial Sensors
Serviceline Explosion Protection

Solenoid Driver KCD0-SD3-Ex2.1545-Y1

KCD0-SD3-Ex2.1545-Y1
  • 2-channel isolated barrier
  • 24 V DC supply (loop powered)
  • Current limit 45 mA at 15 V DC
  • Test pulse immunity
  • Housing width 12.5 mm

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Download the complete datasheet as a PDF:


Datasheet excerpt: Technical data of  KCD0-SD3-Ex2.1545-Y1

General specifications
Signal typeDigital Output
Supply
Rated voltageloop powered
Power dissipation< 2 W
Power consumption
Input
Connection sidecontrol side
Connectionterminals 5+, 6-; 7+, 8-
limited electrical values : max. 30 V , max. 5 A
Test pulse lengthmax. 2 ms from DO card
Signal level1-signal: 18 ... 30 V DC
0-signal: 0 ... 5 V DC
Rated voltage18 ... 30 V DC
Rated current0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card)
1-signal: ≥ 20 mA (minimum load current DO card)
Inrush current≤ 200 mA after 100 µs
Output
Connection sidefield side
Connectionterminals 1+, 2-; 3+, 4-
Internal resistorapprox. 167 Ω
Currenttyp. 45 mA
Voltage≥ 15 V
Current limit45 mA
Open loop voltagetyp. 23.8 V
Switching frequencymax. 10 Hz
Energized/De-energized delay≤ 20 ms / ≤ 20 ms
Galvanic isolation
Input/Outputreinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elementsLED
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2017 , EN IEC 61326-1:2021 (industrial locations) , EN IEC 61326-3-2:2018
For further information see system description.
Degree of protectionIEC 60529:2013
Protection against electrical shockUL 61010-1:2019
Ambient conditions
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 95 g
Dimensions12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2
Height119 mm
Width12.5 mm
Depth114 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateUL 23 ATEX 3027 X
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC
Ex-Hexagon II (1)D [Ex ia Da] IIIC
Ex-Hexagon I (M1) [Ex ia Ma] I
OutputEx ia
Refer to certificate for alternative parameters.
Voltage25.3 V
Current52 mA
Power850 mW (angular characteristic curve)
Internal resistance167 Ω
Input
Maximum safe voltage250 V (Attention! The rated voltage can be lower.)
CertificateUL 23 ATEX 3065 X
MarkingEx-Hexagon II 3G Ex ec IIC T4 Gc
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, rated insulation voltage 300 Vrms
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012
International approvals
UL approvalE106378
Control drawing116-0496 (cULus)
IECEx approval
IECEx certificateIECEx ULD 23.0016X
IECEx marking[Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I
Ex ec IIC T4 Gc
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210101
ECLASS 12.027210190
ECLASS 11.027210190
ECLASS 10.0.127210190
ECLASS 9.027210190
ECLASS 8.027210190
ECLASS 5.127210121
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.139121008

Details: KCD0-SD3-Ex2.1545-Y1

Function

This isolated barrier is used for intrinsic safety applications.

The device supplies power to solenoids, LEDs and audible alarms located in the explosion-hazardous area.

The device simulates a minimum load of 20 mA at the input.

The device is loop powered, so the available energy at the output is received from the input signal. The output signal has a resistive characteristic. As a result the output voltage and current are dependent on the load and the input voltage

At full load, 15 V at 45 mA is available for the hazardous area application.

Informative Literature: KCD0-SD3-Ex2.1545-Y1

Language Selection:
LiteratureLanguageFile TypeFile Size
Application Guideline Solenoid DriversENGPDF1982 KB
Product Overview - KCD* dual channel solenoid driverENGPDF507 KB

Product Documentation: KCD0-SD3-Ex2.1545-Y1

Language Selection:
Safety and Security DocumentationLanguageFile TypeFile Size
Instruction manualENGPDF171 KB
Manuals
ManualENGPDF3685 KB

Design / Simulation: KCD0-SD3-Ex2.1545-Y1

Language Selection:
CADLanguageFile TypeFile Size
CAD 3-D / CAD 3-DALLSTP3088 KB
CAE
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZALLEDZ1964 KB

Approvals: KCD0-SD3-Ex2.1545-Y1

Language Selection:
CertificatesCert No.LanguageFile TypeFile Size
Canada UL cUL Hazardous Location UL E106378CoC UL-CA-2414398-0 Rep Ref E106378-20240510ALLPDF218 KB
Canada UL cUL Hazardous Location UL E106378CoC UL-CA-2414399-0 Rep Ref E106378-20240510ALLPDF218 KB
Europe UL ATEX Category (1) D ATEX Category (M1) ATEX Category (1) GUL 23 ATEX 3027XALLPDF108 KB
Europe United Kingdom UL ATEX Category 3 GUL 23 ATEX 3065XALLPDF83 KB
USA UL UL E106378 Hazardous Location ULCoC UL-US-2417714-0 Rep Ref E106378-20240510ALLPDF255 KB
USA UL UL E106378 Hazardous Location ULCoC UL-US-2417718-0 Rep Ref E106378-20240510ALLPDF218 KB
Worldwide UL IECEx Certificate of ConformityIECEx ULD 23.0016XALLLINK---
Declaration of Conformity
EU-Declaration of conformityTDOC-7688AENGENGPDF151 KB

Associated Products: KCD0-SD3-Ex2.1545-Y1

Matching System Components
Cable trunking is integrated in the mounting profile, Safe spacious separation of safe and hazardous signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Accessories
2-pin screw terminal, For KC modules of K-System, Packaging unit: 5 pieces greenpa
2-pin screw terminal, For KC modules of K-System, Packaging unit: 5 pieces bluepa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.