General specifications | ||
---|---|---|
Signal type | Digital Output | |
Supply | ||
Connection | Power Rail or terminals 9+, 10- bus powered | |
Rated voltage | 18 ... 30 V DC | |
Power dissipation | < 2 W | |
Power consumption | max. 3.5 W at 45 mA output current | |
Input | ||
Connection side | control side | |
Connection | terminals 5+, 6-; 7+, 8- limited electrical values : max. 30 V , max. 5 A |
|
Test pulse length | max. 2 ms from DO card | |
Signal level | loop powered 1-signal: 18 ... 30 V DC (current limited to ≥ 20 mA) 0-signal: 0 ... 5 V DC bus powered 1-signal: 15 ... 24 V DC (current limited at 5 mA) 0-signal: 0 ... 5 V DC |
|
Rated current | loop powered 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ≥ 20 mA (minimum load current DO card) bus powered 1-signal: 5 mA |
|
Inrush current | ≤ 200 mA after 100 µs | |
Output | ||
Connection side | field side | |
Connection | terminals 1+, 2-; 3+, 4- | |
Internal resistor | approx. 167 Ω | |
Current | ≤ 45 mA | |
Voltage | ≥ 15 V | |
Current limit | 45 mA | |
Open loop voltage | min. 23.6 V | |
Load | nominal 0.05 ... 20 kΩ , valid range for line fault detection (LFD) | |
Energized/De-energized delay | ≤ 20 ms / ≤ 20 ms | |
Line fault detection | ||
Test current | max. 350 µA , calculated by ILFD = 3.3 V / (10 kΩ + RLoad) | |
Galvanic isolation | ||
Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Power supply/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2017 , EN IEC 61326-1:2021 (industrial locations) , EN IEC 61326-3-2:2018 For further information see system description. |
|
Degree of protection | IEC 60529:2013 | |
Protection against electrical shock | UL 61010-1:2019 | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | spring terminals | |
Mass | approx. 105 g | |
Dimensions | 12.5 x 124 x 114 mm (0.5 x 4.9 x 4.5 inch) (W x H x D) , housing type A2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | UL 23 ATEX 3027 X | |
Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
|
Output | Ex ia Refer to certificate for alternative parameters. |
|
Voltage | 25.3 V | |
Current | 52 mA | |
Power | 850 mW (angular characteristic curve) | |
Internal resistance | 167 Ω | |
Supply | ||
Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) | |
Input | ||
Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) | |
Collective error message | ||
Maximum safe voltage | 250 V (Attention! The rated voltage can be lower.) | |
Certificate | UL 23 ATEX 3065 X | |
Marking | II 3G Ex ec IIC T4 Gc | |
Galvanic isolation | ||
Input/Output | safe electrical isolation acc. to IEC/EN 60079-11, rated insulation voltage 300 Vrms | |
Output/power supply | safe electrical isolation acc. to IEC/EN 60079-11, rated insulation voltage 300 Vrms | |
Directive conformity | ||
Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-7:2015+A1:2018 , EN 60079-11:2012 | |
International approvals | ||
UL approval | E106378 | |
Control drawing | 116-0496 (cULus) | |
IECEx approval | ||
IECEx certificate | IECEx ULD 23.0016X | |
IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
|
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27210101 |
ECLASS 12.0 | 27210190 |
ECLASS 11.0 | 27210190 |
ECLASS 10.0.1 | 27210190 |
ECLASS 9.0 | 27210190 |
ECLASS 8.0 | 27210190 |
ECLASS 5.1 | 27210121 |
ETIM 9.0 | EC001485 |
ETIM 8.0 | EC001485 |
ETIM 7.0 | EC001485 |
ETIM 6.0 | EC001485 |
ETIM 5.0 | EC001485 |
UNSPSC 12.1 | 39121008 |
This isolated barrier is used for intrinsic safety applications.
The device supplies power to solenoids, LEDs and audible alarms located in the explosion-hazardous area.
The device is controlled with a loop powered signal or a bus powered logic signal.
The device is immune to the test pulses of various control systems.
The device simulates a minimum load at the input. The minimum load is set via the mode of operation. In the loop-powered mode of operation, a minimum load of 20 mA is simulated. In the bus-powered mode of operation, a minimum load of 5 mA is simulated.
The line fault transparency function can display a line fault in the field by a change in impedance at the switching input of the solenoid driver.
A fault is indicated by LEDs and output via a fault indication output.
Product information | Language | File Type | File Size |
---|---|---|---|
Application Guideline Solenoid Drivers | ENG | 734 KB | |
Safety and Security Documentation | |||
Instruction manual | ENG | 171 KB | |
Manuals | |||
Manual | ENG | 3685 KB |
CAD | Language | File Type | File Size |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 3048 KB |
Certificates | Cert No. | Language | File Type | File Size |
---|---|---|---|---|
Canada UL cUL Hazardous Location UL E106378 | CoC UL-CA-2414398-0 Rep Ref E106378-20240510 | ALL | 218 KB | |
Canada UL cUL Hazardous Location UL E106378 | CoC UL-CA-2414399-0 Rep Ref E106378-20240510 | ALL | 218 KB | |
Europe UL ATEX Category (1) D ATEX Category (M1) ATEX Category (1) G | UL 23 ATEX 3027X | ALL | 108 KB | |
Europe United Kingdom UL ATEX Category 3 G | UL 23 ATEX 3065X | ALL | 83 KB | |
USA UL UL E106378 Hazardous Location UL | CoC UL-US-2417714-0 Rep Ref E106378-20240510 | ALL | 255 KB | |
USA UL UL E106378 Hazardous Location UL | CoC UL-US-2417718-0 Rep Ref E106378-20240510 | ALL | 218 KB | |
Worldwide UL IECEx Certificate of Conformity | IECEx ULD 23.0016X | ALL | LINK | --- |
Declaration of Conformity | ||||
EU-Declaration of conformity | TDOC-7688AENG | ENG | 151 KB |
Matching System Components | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||