Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
Product Description |
---|
Firmware variant from ICE3-8IOL-G65L-V1D with Modbus enabled by default |
General specifications | ||
---|---|---|
UL File Number | E360395 | |
Indicators/operating means | ||
LED indication | see manual | |
Rotary switch | Setting the IP address | |
Electrical specifications | ||
Rated operating voltage | 20 ... 30 V DC | |
General information | M12, L-coded | |
Nominal voltage | 24 V DC | |
Current consumption | typ. 120 mA | |
Current loading capacity | Max. 2 x 16 A per module (Loop-through current via L-coded power supply) Total current: max. 6.7 A per module |
|
Galvanic isolation | between US and UA | |
Interface 1 | ||
Interface type | Industrial Ethernet | |
Physical | M12, D-coded | |
Protocol | PROFINET IO with media redundancy protocol (MRP) + Modbus TCP + OPC UA + MQTT Modbus max PDI: 33 times / sec OPC UA max PDI update rate: 20 times / sec MQTT max PDI update rate: 10 times / sec |
|
Transfer rate | 10/100 Mbps | |
Inputs/Outputs | ||
Number/Type | 8 x IO-Link Class A (X1 – X8) Configurable as: Max. 8 IO-Link and 8 digital inputs Max. 16 digital inputs Max. 8 digital inputs and 8 digital outputs short-circuit protected |
|
Sensor supply | Port 1: max. 1.6 A Via L+ (pin 1) Port 3: max. 1 A via L+ (pin 1) Ports 2 and 4 – 8: max. 500 mA per port via L+ (pin 1) |
|
Output current | max. 200 mA Per port via C/Q (pin 4) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61000-6-2 , EN 61000-6-4 | |
Standard conformity | ||
Degree of protection | EN 60529 | |
Fieldbus standard | IEC 61131-2 | |
Electrical safety | CSA C22.2 No. 61010-1-12 UL 61010-1, IEC 61010-2-201 |
|
Emitted interference | EN 61000-6-4, FCC Part 15 Subpart B, ICES-001, AS/NZS CISPR 11 | |
Noise immunity | EN 61000-6-2 , EN 61131-2 , EN 61131-9 | |
Shock resistance | EN 60068-2-27 | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | max. 95 % | |
Altitude | 0 ... 2000 m | |
Shock and impact resistance | 15g, 11ms, half-sine | |
Mechanical specifications | ||
Degree of protection | IP67 | |
Connection | Power Supply M12, L-coded Fieldbus M12, D-coded Inputs/Outputs M12, A-coded |
|
Material | ||
Housing | Molded Polyamide 66 | |
Mass | 454 g | |
Tightening torque, fastening screws | 8 Nm | |
Tightening torque, cable gland | 0.6 Nm | |
Dimensions | 65 mm 30 mm 212 mm | |
Height | 212 mm | |
Width | 65 mm | |
Length | 30 mm | |
Mounting | Machine or panel |
System | Classcode |
---|---|
ECLASS 13.0 | 27242608 |
ECLASS 12.0 | 27242608 |
ECLASS 11.0 | 27242608 |
ECLASS 10.0.1 | 27242608 |
ECLASS 9.0 | 27242608 |
ECLASS 8.0 | 27242608 |
ECLASS 5.1 | 27242608 |
ETIM 9.0 | EC001597 |
ETIM 8.0 | EC001597 |
ETIM 7.0 | EC001597 |
ETIM 6.0 | EC001597 |
ETIM 5.0 | EC001597 |
UNSPSC 12.1 | 32151705 |
The module is a PROFINET IO fieldbus module with 8 type A IO-Link master ports according to IO-Link standard V1.1.
The fieldbus module serves as an interface between the controller of a PROFINET IO fieldbus system and IO-Link devices in the field level. The integrated web server and IODD interpreter enabling complete configuration of the fieldbus module and attached IO-Link devices without the need for special software tools. Information regarding the status of the module is also displayed and network parameters such as the IP address and subnet mask can be configured. The module is capable of storing all configuration enabling stand-alone usage without a higher-level PLC. MutliLink simultaneously provides data access via different communication protocols like PROFINET IO, Modbus/TCP and OPC UA to multiple controllers. An L-coded M12 connector plug used for supplying power enables a current rating of up to 2 x 16 A.
The inputs and outputs are equipped with A-coded M12 connector plugs. Connection to the fieldbus is achieved using a D-coded M12 connector plug.
Status information for each channel is displayed via LEDs as a diagnostic function.
Literature | Language | File Type | File Size |
---|---|---|---|
Product Overview - IO-Link-Master with OPC UA Interface | ENG | 1504 KB | |
Application Report - Industrial Communication - IO-Link Master - CNC Machines | ENG | 757 KB | |
Application Report - Seamless Communication from the Sensor to the Cloud | ENG | 171 KB |
Manuals | Language | File Type | File Size |
---|---|---|---|
ICE3-8IOL-G65L-V1D and ICE3-8IOL-K45S-RJ45 Manual | ENG | 26657 KB | |
IO-Link Master Modbus Read/Write Example | ENG | 1028 KB | |
REST API Addendum | ENG | 3039 KB |
CAD | Language | File Type | File Size |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 6572 KB |
CAD Portal / CAD Portal | ALL | LINK | --- |
CAE | |||
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZ | ALL | EDZ | 63 KB |
Certificates | Cert No. | Language | File Type | File Size |
---|---|---|---|---|
Canada, USA UL UL | E360395 | ALL | LINK | --- |
Korea | R-R-PF1-C0087 | ALL | 316 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-4275E | ALL | 111 KB | |
UK Declaration of Conformity (P+F) / UK-Konformitäterklärung (P+F) | DOC-5810A | ALL | 108 KB |
Device Description Files/Drivers | Release Info | File Type | File Size |
---|---|---|---|
PROFINET GSDML files (GSDML-V2.35-Pepperl+Fuchs-ICE38IOL-Y-20210801) / PROFINET GSDML-Dateien (GSDML-V2.35-Pepperl + Fuchs-ICE38IOL-Y-20210801) | September 2021 | ZIP | 15 KB |
Software Tools | |||
PortVision DX v6.02 / PortVision DX v6.02 | 2020-08 | ZIP | 29584 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|