Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
Product Description |
---|
G20 IO-Link module for 16 freely configurable digital inputs/outputs |
General specifications | ||
---|---|---|
UL File Number | E223772 | |
MTBF | 149 a | |
Indicators/operating means | ||
LED green | <--, -->: IO1..8 / IO9..16 bank indication | |
LED yellow/red | IO1 ... IO16: inputs/outputs status, IO-Link status | |
Electrical specifications | ||
Operating voltage | 18 ... 30 V DC, PELV Current limitation of the supply max. 4 A |
|
No-load supply current | ≤ 25 mA | |
Operating current | max. 4 A | |
Interface | ||
Interface type | IO-Link | |
IO-Link revision | 1.1 | |
Device profile | Identification and Diagnosis - I&D Firmware update |
|
Process data | Inputs 3 Byte - Input signals 16 Bit - diagnosis signals 5 Bit Outputs 2 Byte - Output signals 16 Bit |
|
Vendor ID | 1 (0x0001) | |
Device ID | 985345 (0x0F0901) | |
Data transfer rate | COM3 (230.4 kbits/s) | |
Min. cycle time | 1 ms |
|
SIO mode support | no | |
Compatible master port type | Class A |
|
Input | ||
Number/Type | 16 Inputs for 3-wire sensors (PNP), DC (IO1 ... IO16) | |
Supply | from IO-Link | |
Current loading capacity | 200 mA , overload and short-circuit protected | |
Input current | ≤ 5 mA (limited internally) | |
Switching point | Type 3 according to IEC 61131-2 | |
Output | ||
Number/Type | 16 electronic outputs, PNP (IO1 … IO16), overload-proof and short-circuit-proof | |
Supply | from IO-Link | |
Voltage | ≥ (UB - 1.5 V) | |
Current | 200 mA per output | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 EN 55011:2016 |
|
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 61131-9:2013 | |
Input | EN 61131-2:2007 | |
Communication interface | IEC 61131-9:2013 / IO-Link V1.1.3 | |
Emitted interference | EN 61000-6-4:2007 | |
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006 | |
Approvals and certificates | ||
UL approval | UL 61010-1, UL 61010-2-201 Load specification DC General Use / DC Pilot Duty Degree of protection not tested by UL; tested by Pepperl+Fuchs SE |
|
Ambient conditions | ||
Ambient temperature | -30 ... 70 °C (-22 ... 158 °F) | |
Storage temperature | -30 ... 70 °C (-22 ... 158 °F) | |
Relative humidity | 85 % non-condensing | |
Climatic conditions | For indoor use only | |
Altitude | ≤ 5000 m above MSL | |
Shock and impact resistance | 30 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks | |
Vibration resistance | 0.35 mm / 5 g 5 ... 500 Hz | |
Pollution degree | 2 | |
Mechanical specifications | ||
Degree of protection | IP54 according to EN 60529 | |
Connection | IO-Link: M12 round plug connector in accordance with EN 61076-2-101, LM type (4-pin, connector contacts, screw-locking, A-coded) Female connector: LF type or similar IO: M8 round plug connector in accordance with EN 61076-2-104, LF type (4-pin, bushing contacts, screw-locking, A-coded) Mating connector: LM type or similar |
|
Mass | 310 g | |
Dimensions | ||
Height | 27.5 mm | |
Width | 131.5 mm | |
Length | 54 mm | |
Mounting | 2 clips with ∅ 8 mm drill hole The module must be secured to a solid, continuous surface using the two lugs |
|
Cable length | 1 m (IO-Link) 0.2 m (IO1/2, IO15/16), 0.3 m (IO3/4, IO13/14) 0.4 m (IO5/6, IO11/12); 0.5 m (IO7/8, IO9/10) max. 10 m |
System | Classcode |
---|---|
ECLASS 13.0 | 27242602 |
ECLASS 12.0 | 27242602 |
ECLASS 11.0 | 27242602 |
ECLASS 10.0.1 | 27242602 |
ECLASS 9.0 | 27242602 |
ECLASS 8.0 | 27242602 |
ECLASS 5.1 | 27242602 |
ETIM 9.0 | EC001597 |
ETIM 8.0 | EC001597 |
ETIM 7.0 | EC001597 |
ETIM 6.0 | EC001597 |
ETIM 5.0 | EC001597 |
UNSPSC 12.1 | 32151705 |
The ICA-16IO-G20-IO-P16 is an IO-Link field module with 16 freely configurable digital inputs/outputs. The compact housing can be mounted directly in support profiles or cable ducts.
The module and the inputs and outputs are supplied with voltage via IO-Link.
The inputs and outputs are connected via cable outlets with 4-pin M8 sockets. IO-Link is connected via a cable outlet with 4-pin M12 connector.
The current switching state or an overload of the inputs or outputs is indicated via the IN or OUT LEDs.
Brief Instructions | Language | File Type | File Size |
---|---|---|---|
Instruction leaflet / Beipackzettel | ALL | 91 KB | |
Manuals | |||
Manual | ENG | 635 KB |
Certificates | Cert No. | Language | File Type | File Size |
---|---|---|---|---|
Canada, USA UL | 2019-2-25, 2019-07-29 (A1/C0), 2020-10-21 (A2/C0); 2024-08-28 (A3/C0)-E223772 | ALL | 523 KB | |
IO-Link Manufacturer Declaration | CERT-7194 | ALL | 173 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) | TDOC-7463_ENG | ENG | 196 KB | |
UK Declaration of Conformity (P+F) | TDOC-7464_ENG | ENG | 171 KB |
Device Description Files/Drivers | Release Info | File Type | File Size |
---|---|---|---|
IODD for ICA-16IO-G20-IO-P16 / IODD für ICA-16IO-G20-IO-P16 | V1.02.000 / 2024-08-12 | ZIP | 231 KB |
Software Tools | |||
IO-Link Offline Parameterization Tool / IO-Link Offline-Parametriertool | V1.00.006 / 2022-07-10 | ZIP | 96138 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|