Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
Datasheet excerpt: Technical data of
NJ6-F-N
General specifications |
Switching function | Normally closed (NC) |
Output type | NAMUR |
Rated operating distance | 6 mm |
Installation | flush |
Assured operating distance | 0 ... 4.8 mm |
Actual operating distance | 5.4 ... 6.6 mm typ. |
Reduction factor rAl | 0.4 |
Reduction factor rCu | 0.3 |
Reduction factor r304 | 0.7 |
Output type | 2-wire |
Nominal ratings |
Nominal voltage | 8.2 V (Ri approx. 1 kΩ) |
Switching frequency | 0 ... 5000 Hz |
Hysteresis | 0 ... 0.3 mm typ. 5 % |
Reverse polarity protection | reverse polarity protected |
Current consumption | |
| Measuring plate not detected | min. 3 mA |
| Measuring plate detected | ≤ 1 mA |
Functional safety related parameters |
MTTFd | 4540 a |
Mission Time (TM) | 20 a |
Diagnostic Coverage (DC) | 0 % |
Compliance with standards and directives |
Standard conformity | |
| Standards | EN IEC 60947-5-2 |
Approvals and certificates |
IECEx approval | |
| Equipment protection level Gb | IECEx PTB 11.0021X |
| Equipment protection level Da | IECEx PTB 11.0021X |
| Equipment protection level Mb | IECEx PTB 11.0021X |
ATEX approval | |
| Equipment protection level Gb | PTB 00 ATEX 2032 X |
| Equipment protection level Da | PTB 00 ATEX 2032 X |
UL approval | cULus Listed, General Purpose |
CCC approval | |
| Hazardous Location | 2020322315002302 |
NEPSI approval | |
| NEPSI certificate | GYJ16.1394X |
CML approval | on request |
ANZEx | 19.3001X |
Ambient conditions |
Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
Storage temperature | -40 ... 100 °C (-40 ... 212 °F) |
Mechanical specifications |
Connection type | cable |
Housing material | PBT |
Sensing face | PBT |
Degree of protection | IP67 |
Cable | |
| Wire end ferrules | yes |
| Cable diameter | 4.8 mm ± 0.2 mm |
| Bending radius | > 10 x cable diameter |
| Material | PUR |
| Color | blue |
| Number of cores | 2 |
| Core cross section | 0.34 mm2 |
| Length | 2 m |
Mass | 78 g |
Dimensions | |
| Height | 30 mm |
| Width | 45 mm |
| Length | 12 mm |
General information |
Use in the hazardous area | see instruction manuals |
Classifications
System | Classcode |
ECLASS 13.0 | 27274001 |
ECLASS 12.0 | 27274001 |
ECLASS 11.0 | 27270101 |
ECLASS 10.0.1 | 27270101 |
ECLASS 9.0 | 27270101 |
ECLASS 8.0 | 27270101 |
ECLASS 5.1 | 27270101 |
ETIM 9.0 | EC002714 |
ETIM 8.0 | EC002714 |
ETIM 7.0 | EC002714 |
ETIM 6.0 | EC002714 |
ETIM 5.0 | EC002714 |
UNSPSC 12.1 | 39121550 |
Details:
NJ6-F-N
Product Documentation:
NJ6-F-N
Design / Simulation:
NJ6-F-N