Datasheet excerpt: Technical data of
PMI14V-F166-U
General specifications |
Switching element function | Analog voltage output |
Object distance | 0.5 ... 2 mm |
Measuring range | 0 ... 14 mm |
Nominal ratings |
Operating voltage | 18 ... 30 V DC |
Reverse polarity protection | reverse polarity protected |
Linearity error | ± 0.3 mm |
Repeat accuracy | ± 0.05 mm |
Resolution | 33 µm |
Temperature drift | ± 0.3 mm (With a target distance of 0.5 mm) |
No-load supply current | ≤ 20 mA |
Functional safety related parameters |
MTTFd | 830 a |
Mission Time (TM) | 20 a |
Diagnostic Coverage (DC) | 0 % |
Analog output |
Output type | 1 voltage output: 0 ... 10 V |
Load resistor | ≥ 1000 Ω |
Short-circuit protection | current limit |
Compliance with standards and directives |
Standard conformity | |
| Standards | EN 60947-5-2:2007 IEC 60947-5-2:2007 EN 60947-5-7:2003 |
Approvals and certificates |
UL approval | cULus Listed, Class 2 Power Source, Type 1 enclosure |
Ambient conditions |
Ambient temperature | -10 ... 70 °C (14 ... 158 °F) |
Storage temperature | -20 ... 70 °C (-4 ... 158 °F) |
Mechanical specifications |
Connection type | 5 x 0.14 mm2 , screened 2 m PUR cable |
Degree of protection | IP65 |
Material | |
| Housing | Zinc diecast, nickel-plated cover , PBT |
| Target | mild steel, e. g. 1.0037, SR235JR (formerly St37-2) |
Cable | |
| Cable diameter | 4.8 mm |
| Bending radius | > 10 x cable diameter |
Mass | 95 g |
Dimensions | |
| Height | 17.7 mm |
| Width | 30 mm |
| Length | 39 mm |
Classifications
System | Classcode |
ECLASS 13.0 | 27274004 |
ECLASS 12.0 | 27274004 |
ECLASS 11.0 | 27270702 |
ECLASS 10.0.1 | 27270702 |
ECLASS 9.0 | 27270702 |
ECLASS 8.0 | 27270702 |
ECLASS 5.1 | 27270702 |
ETIM 9.0 | EC001852 |
ETIM 8.0 | EC001852 |
ETIM 7.0 | EC001852 |
ETIM 6.0 | EC001852 |
ETIM 5.0 | EC001852 |
UNSPSC 12.1 | 39121550 |
Details:
PMI14V-F166-U
Design / Simulation:
PMI14V-F166-U
Associated Products:
PMI14V-F166-U
Accessories |
|
|
|
Damping element for sensors of type F90, F112, and F166; side holefa |
|
|
|
|
Damping element for sensors of type F90, F112, and F166; front holefa |
|
|
|
|
Programming unit, Programming unit for PMI14V "F166 family", Connection type: cable with V15 connector (power supply) cable with V15 socket (sensor), Degree of protection: IP20fa |
|