Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
General specifications | ||
---|---|---|
Design / Mounting | Outside installation | |
Installation in hazardous area | Zone 1 / Div. 1 | |
Electronic component | Temperature Multi-Input Device RD0-TI-Ex8.PA* For technical data on installed electronic component see datasheet. | |
Fieldbus connection | ||
Fieldbus type | PROFIBUS PA | |
Input | ||
Number | 8 | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | ||
Galvanic isolation | EN 60079-11 | |
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | see table 1 | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | ≤ 95 % non-condensing | |
Shock resistance | 15 g , 11 ms | |
Vibration resistance | 10 g , 10 ... 150 Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Connection type | plug-in terminals , spring terminal and screw terminal | |
Core cross section | ||
Bus | up to 2.5 mm2 | |
Inputs | up to 2.5 mm2 | |
Cable diameter | see table 2 | |
Cable gland | sensor inputs M16, fieldbus M20 | |
Housing material | Aluminum | |
Degree of protection | IP67 | |
Mass | 1800 g | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | PTB 03 ATEX 2237 | |
Marking | II 2 (1) G Ex ia [ia Ga] IIC T4 Gb , II (1) G [Ex ia Ga] IIC , II (1) D [Ex ia Da] IIIC , II 3 G Ex ic IIC T4 Gc | |
Bus | FISCO see EC-Type Examination Certificate | |
Voltage | 24 V | |
Inputs | see EC-Type Examination Certificate | |
Certificate | PTB 03 ATEX 2238 X | |
Marking | II 3 G Ex nA IIC T4 Gc | |
Galvanic isolation | ||
Bus | see Statement of Conformity | |
Input | see EC-Type Examination Certificate | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | CoC 3025732 | |
CSA approval | CoC 3025732C | |
IECEx approval | IECEx PTB 05.0001 , IECEx PTB 05.0002X | |
Approved for | Ex ia [ia Ga] IIC T4 Gb , [Ex ia Ga] IIC , [Ex ia Da] IIIC , Ex ic IIC T4 Gc , Ex nA IIC T4 Gc | |
Certificates and approvals | ||
Marine approval | DNV A-14038 | |
General information | ||
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27242610 |
ECLASS 12.0 | 27242610 |
ECLASS 11.0 | 27242610 |
ECLASS 10.0.1 | 27242610 |
ECLASS 9.0 | 27242610 |
ECLASS 8.0 | 27242610 |
ECLASS 5.1 | 27242610 |
ETIM 9.0 | EC001601 |
ETIM 8.0 | EC001601 |
ETIM 7.0 | EC001601 |
ETIM 6.0 | EC001601 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121008 |
This fieldbus junction box holds a temperature multi-input device for transferring signals from resistance temperature measuring sensors and thermocouples, as well as resistance and millivolt signals via PROFIBUS PA. The fieldbus junction box with 8 inputs can be installed in Zone 1/Div. 1 with sensors located in Zone 0/Div. 1.
The housing, type F2, is made of sturdy cast aluminum for installation in rough environments. Fieldbus and field device entrances can be selected individually from a range of cable glands. Optionally, either screw terminals or spring terminals can be chosen. A tag plate is available as option.
Literature | Language | File Type | File Size |
---|---|---|---|
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-Synchrotron | ENG | 361 KB | |
Application Report - Digital Communication in Steel-Plate Manufacturing | ENG | 470 KB |
Safety and Security Documentation | Language | File Type | File Size |
---|---|---|---|
Instruction manual | ENG | 235 KB | |
Manuals | |||
Manual | ENG | 4255 KB | |
Software Information | |||
Release information Device Description (EDDL) for Siemens SIMATIC PDM | ENG | 403 KB |
CAD | Language | File Type | File Size |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 5195 KB |
Certificates | Certificate No. | Language | File Type | File Size |
---|---|---|---|---|
Brasil TUV Rheinland Brazil | TÜV 13.1136 | ALL | 1200 KB | |
Brasil TUV Rheinland Brazil | TÜV 13.1134 X | ALL | 1198 KB | |
Canada FM | CoC 3025732C | ALL | 316 KB | |
China SITIIAS CCC Ex Certificate | 2020322314002489 (Singapore) | ALL | 2152 KB | |
DNV Marine | TAA0000272 | ALL | 100 KB | |
Europe PTB ATEX Category 2 (1) | PTB 03 ATEX 2237 | ALL | 884 KB | |
Europe PTB ATEX Category 3 G | PTB 03 ATEX 2238X | ALL | 617 KB | |
India PESO (India) CCOE | A/P/HQ/KA/104/5828 (P489740) | ALL | 79 KB | |
PTB IECEx Certificate of Conformity | IECEx PTB 05.0001 | ALL | LINK | --- |
PTB IECEx Certificate of Conformity | IECEx PTB 05.0002X | ALL | LINK | --- |
South Africa MASC | MASC S/18-2698 | ALL | 608 KB | |
USA FM | CoC 3025732 | ALL | 316 KB | |
Control Drawings | ||||
Control drawing FM / Control drawing FM | ALL | 249 KB | ||
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-0148F | ALL | 2042 KB |
Device Description Files/Drivers | Release Info | File Type | File Size |
---|---|---|---|
GSD / GSD | Rev. 1.0 | ZIP | 6 KB |
DTM Collection FieldConnex / DTM Collection FieldConnex | 1.9.0.2268 | ZIP | 35363 KB |
Device Description (EDDL) for Siemens SIMATIC PDM / Gerätebeschreibung (EDDL) für Siemens SIMATIC PDM | 1.0.0.585 | ZIP | 473 KB |
Matching System Components | ||||||
---|---|---|---|---|---|---|
|
||||||
Accessories | ||||||
|
||||||
|
||||||
|
||||||
|
FieldConnex® Multi-Input/Output
The FieldConnex Multi-Input/Output opens up new possibilities for users to capture digital input and output signals in process automation …