General specifications | ||
---|---|---|
Signal type | Analog input/analog output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Systematic capability (SC) | SC 3 | |
Supply | ||
Connection | Power Rail or terminals 9+, 10- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | max. 10 % | |
Rated current | max. 88 mA at 24 V | |
Power dissipation | max. 1.4 W | |
Power consumption | max. 2.1 W | |
Analog input | ||
Number of channels | 2 | |
Suitable field devices | 2-wire SMART transmitters | |
Signal | 0/4 ... 20 mA , limited to approx. 30 mA | |
Field circuit | terminals 1+, 2-, 3+, 4- | |
Available voltage | min. 15 V at 20 mA min. 18 V at 4 mA |
|
Control circuit | terminals 5-, 6+; 7-, 8+ limited electrical values : max. 30 V , max. 2 A |
|
Input voltage | Voltage across terminals 10 ... 30 V. If the current is supplied from a source > 24 V, series resistance of ≥ (V - 24)/0.02 Ω is needed, where V is the source voltage. The maximum value of the resistance is (V - 10)/0.02 Ω. (sink output) |
|
Load | max. 350 Ω (source output) | |
Ripple | 20 mV eff | |
Analog output | ||
Number of channels | 2 | |
Suitable field devices | SMART I/P converters (positioner), on-site-displays | |
Signal | 0/4 ... 20 mA , limited to approx. 30 mA | |
Field circuit | terminals 1+, 2-, 3+, 4- | |
Load | max. 650 Ω | |
Voltage | min. 13 V at 20 mA | |
Ripple | 20 mV eff , on all signal terminals | |
Control circuit | terminals 5-, 6+; 7-, 8+ limited electrical values : max. 30 V , max. 2 A |
|
Voltage drop | max. 6 V | |
Line fault detection | > 100 kΩ at max. 30 V, with field wiring open | |
Transfer characteristics | ||
Deviation | max. 20 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage | |
Influence of ambient temperature | < 2 µA/K (-40 ... 70 °C (-40 ... 158 °F)) | |
Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) |
|
Settling time | max. 200 ms | |
Rise time/fall time | max. 100 ms (10 ... 90 %) | |
Galvanic isolation | ||
Field circuit/control circuit | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Control circuit/control circuit | functional isolation, rated voltage: 50 V | |
Field circuit/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Control/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Indicators/settings | ||
Display elements | LED | |
Factory setting | analog input with source output | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2017 EN 61326-3-2:2018 |
|
Degree of protection | IEC 60529:2001 | |
Protection against electrical shock | UL 61010-1:2019 | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 115 g | |
Dimensions | 12.5 x 124 x 114 mm (0.5 x 4.9 x 4.5 inch) (W x H x D) , housing type A2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | UL 22 ATEX 2786 X | |
Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
|
Output | Ex ia, Ex iaD | |
Voltage | 25.2 V | |
Current | 100 mA | |
Power | 630 mW | |
Internal capacitance | 1.05 nF | |
Internal inductance | 0 | |
Supply | ||
Maximum safe voltage | 250 V rms (Attention! The rated voltage can be lower.) | |
Input | ||
Maximum safe voltage | 250 V rms (Attention! The rated voltage can be lower.) | |
Certificate | UL 22 ATEX 2787 X | |
Marking | II 3G Ex ec IIC T4 Gc [device in zone 2] | |
Galvanic isolation | ||
Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Field circuit/power supply | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN IEC 60079-0:2018 , EN 60079-11:2012 , EN IEC 60079-7:2015+A1:2018 | |
International approvals | ||
UL approval | E106378 | |
Control drawing | 116-0490 (cULus) | |
IECEx approval | ||
IECEx certificate | IECEx ULD 22.0020X | |
IECEx marking | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
|
General information | ||
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27210120 |
ECLASS 12.0 | 27210120 |
ECLASS 11.0 | 27210120 |
ECLASS 10.0.1 | 27210120 |
ECLASS 9.0 | 27210120 |
ECLASS 8.0 | 27210120 |
ECLASS 5.1 | 27210120 |
ETIM 9.0 | EC002653 |
ETIM 8.0 | EC002653 |
ETIM 7.0 | EC002653 |
ETIM 6.0 | EC002653 |
ETIM 5.0 | EC001485 |
UNSPSC 12.1 | 32101514 |
This isolated barrier is used for intrinsic safety applications.
Each device channel works as a transmitter power supply or a current driver.
The device transfers data by using a current signal.
The device supports a bi-directional communication for SMART devices that use current modulation to transmit data and voltage modulation to receive data.
For current driver operation, an open field circuit presents a high impedance to the control side to allow lead breakage to be monitored by control systems.
Literature | Language | File Type | File Size |
---|---|---|---|
Application Report - Generating Electricity in Coal-Fired Power Plants | ENG | 412 KB | |
Application Report - Screening Systems in Sewage Treatment Plants | ENG | 577 KB |
Safety and Security Documentation | Language | File Type | File Size |
---|---|---|---|
Instruction manual | ENG | 173 KB | |
Functional Safety Manual | ENG | 1938 KB | |
Manuals | |||
Manual | ENG | 3685 KB |
CAD | Language | File Type | File Size |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 3085 KB |
CAE | |||
CAE EPLAN Data Portal / CAE EPLAN Data Portal | ALL | LINK | --- |
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZ | ALL | EDZ | 2043 KB |
Certificates | Certificate No. | Language | File Type | File Size |
---|---|---|---|---|
China SITIIAS CCC Ex Certificate | 2023322316005022 (Singapore) | ALL | 1280 KB | |
DNV Marine | TAA00001WX | ALL | 106 KB | |
Europe UL ATEX Category (1) D ATEX Category (M1) ATEX Category (1) G | UL 22 ATEX 2786X | ALL | 333 KB | |
Europe United Kingdom UL ATEX Category 3 G | UL 22 ATEX 2787X | ALL | 319 KB | |
USA Canada UL Hazardous Location cULus UL E106378 | CoC E106378 Rep Ref E106378-20221122 | ALL | 420 KB | |
United Kingdom UL UKEX Category (1) D UKEX Category (1) G UKEX Category (M1) | UL22UKEX2497X | ALL | 280 KB | |
Worldwide TUV Rheinland Functional Safety Certificate | 968_FSP_2456_00_en_el | ALL | 620 KB | |
Worldwide UL IECEx Certificate of Conformity | IECEx ULD 22.0020X | ALL | LINK | --- |
Control Drawings | ||||
Control drawing UL / Control drawing UL | ALL | 138 KB | ||
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) | TDOC-6902AENG | ENG | 232 KB | |
UK Declaration of Conformity (P+F) / UK-Konformitäterklärung (P+F) | DOC-6973 | ALL | 128 KB |
Matching System Components | ||||||
---|---|---|---|---|---|---|
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
|
||||||
Accessories | ||||||
|
||||||
|
||||||
|
||||||
|