Ladda ned datablad som PDF::
Utdrag ur datablad: Tekniska data för
CJ2-18GK-N
General specifications |
Switching function | Normally open (NO) |
Output type | NAMUR |
Rated operating distance | 2 mm |
Installation | non-flush |
Assured operating distance | 0 ... 1.44 mm |
Output type | 2-wire |
Nominal ratings |
Installation conditions | |
| A | 15 mm |
| B | 30 mm |
| C | 20 mm |
| F | 120 mm |
Nominal voltage | 8.2 V (Ri approx. 1 kΩ) |
Operating voltage | 7 ... 12 V |
Switching frequency | 0 ... 1 Hz |
Current consumption | |
| Measuring plate not detected | ≤ 1 mA |
| Measuring plate detected | ≥ 2.4 mA |
Functional safety related parameters |
MTTFd | 5030 a |
Mission Time (TM) | 20 a |
Diagnostic Coverage (DC) | 0 % |
Compliance with standards and directives |
Standard conformity | |
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
| Standards | EN IEC 60947-5-2 |
Approvals and certificates |
IECEx approval | |
| Equipment protection level Ga | IECEx TUN 20.0014X |
| Equipment protection level Gb | IECEx TUN 20.0014X |
| Equipment protection level Da | IECEx TUN 20.0014X |
ATEX approval | |
| Equipment protection level Ga | TÜV 03 ATEX 2003 X |
| Equipment protection level Gb | TÜV 03 ATEX 2003 X |
| Equipment protection level Da | TÜV 03 ATEX 2003 X |
FM approval | |
| Control drawing | 116-0165 |
UL approval | cULus Listed, General Purpose |
Ambient conditions |
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
Mechanical specifications |
Connection type | cable |
Housing material | PBT |
Sensing face | PBT |
Degree of protection | IP68 |
Cable | |
| Cable diameter | 6 mm ± 0.2 mm |
| Bending radius | > 10 x cable diameter |
| Material | PVC |
| Core cross section | 0.75 mm2 |
| Length | 2 m |
Dimensions | |
| Length | 80 mm |
| Diameter | 18 mm |
General information |
Use in the hazardous area | see instruction manuals |
Classifications
System | Classcode |
ECLASS 13.0 | 27274201 |
ECLASS 12.0 | 27274201 |
ECLASS 11.0 | 27270102 |
ECLASS 10.0.1 | 27270102 |
ECLASS 9.0 | 27270102 |
ECLASS 8.0 | 27270102 |
ECLASS 5.1 | 27270102 |
ETIM 9.0 | EC002715 |
ETIM 8.0 | EC002715 |
ETIM 7.0 | EC002715 |
ETIM 6.0 | EC002715 |
ETIM 5.0 | EC002715 |
UNSPSC 12.1 | 39121550 |
Details:
CJ2-18GK-N
Product Documentation:
CJ2-18GK-N
Safety and Security Documentation | Language | File Type | File Size |
Manual | SWE | PDF | 177 KB
|
Design / Simulation:
CJ2-18GK-N
Associated Products:
CJ2-18GK-N
Accessories |
|
|
|
Mounting flange, 18 mm, Retainer for all cylindrical sensors with M18 thread, Simple installation and exact setting, Large sensing range (max. 20 mm)fa |
|