General specifications |
Design / Mounting | Motherboard based |
Installation in hazardous area | Zone 2 / Div. 2 |
Supply |
Rated voltage | 19.2 ... 35 V DC SELV/PELV |
Rated current | 120 ... 70 mA |
Power dissipation | max. 2.5 W |
Fieldbus connection |
Number of segments | 4 |
Fieldbus type | FOUNDATION Fieldbus |
Physical layer profile | profile type 114 |
ITK version | 6 |
Implementation | resource block 1x RS function block 4x MDI, 1x MDO, 1x MAI, 1x DI transducer block 16x ADM TB, 1x IO TB |
Firmware update | Ethernet |
Polarity | polarity-sensitive |
Rated voltage | 9 ... 35 V |
Rated current | 0 mA |
Ethernet Interface |
Port | 100 BASE-TX |
Protocol | TCP/IP and UDP/IP |
Services | ICMP , DHCP , AutoIP , HTTP |
Connection type | RJ-45 socket, 8-pin |
Transfer rate | 100 MBit/s |
Diagnostic Bus |
Number of Diagnostic Bus Channels | 2 |
Number of Diagnostic Modules/Channel | 31 Using Ethernet Interface , 8 Using Fieldbus Interface |
Termination | integrated |
Cable length/Channel | 30 m |
Indicators/operating means |
LED ERR | red: Hardware fault |
LED PWR | green: Power on |
LINK/ACT | yellow |
CH1, CH2 | yellow: diagnostic bus activity |
Outputs |
Output I | alarm output diagnostic bus channel 1 , volt-free contact , NC contact |
| Voltage | 50 V DC |
| Current | max. 1 A |
Output II | alarm output diagnostic bus channel 2 , volt-free contact , NC contact |
| Voltage | 50 V DC |
| Current | max. 1 A |
Output III | common alarm , volt-free contact , NC contact |
| Voltage | 50 V DC |
| Current | max. 1 A |
Galvanic isolation |
All circuits/FE | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
Output I, II/other circuits | functional insulation acc. to IEC 62103, rated insulation voltage 250 Veff |
Ethernet/Supply | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
Ethernet/other circuits | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
Fieldbus/other circuits | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
Diagnostic Bus/other circuits | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 |
Standard conformity |
Galvanic isolation | IEC 62103 |
Electromagnetic compatibility | NE 21 |
Degree of protection | IEC 60529 |
Fieldbus standard | IEC 61158-2 |
Climatic conditions | DIN IEC 721 |
Shock resistance | EN 60068-2-27 |
Vibration resistance | EN 60068-2-6 |
Ethernet | IEEE 802.3 |
Ambient conditions |
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) hazardous area -40 ... 70 °C (-40 ... 158 °F) safe area horizontal DIN rail mounting
|
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
Relative humidity | < 95 % non-condensing |
Shock resistance | 15 g 11 ms |
Vibration resistance | 1 g , 10 ... 150 Hz |
Pollution degree | max. 2, according to IEC 60664 |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 |
Mechanical specifications |
Housing material | Polycarbonate |
Degree of protection | IP20 |
Mass | 470 g |
Dimensions | |
| Height | see dimensions |
| Width | see dimensions |
| Depth | see dimensions |
Mounting | DIN rail mounting |
Data for application in connection with hazardous areas |
Certificate | TÜV 14 ATEX 115980 X |
| Marking | II 3 G Ex nA IIC T4 Gc |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals |
IECEx approval | IECEx TUN 14.0003X |
| Approved for | Ex nA IIC T4 Gc |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |