Serviceline Industrial Sensors
Serviceline Explosion Protection

Ethernet-APL Surge Protector M-LBAS-IA1.IE

M-LBAS-IA1.IE
  • For Ethernet-APL spur ports
  • Intrinsically safe according to 2-WISE and FISCO
  • Installation on DIN mounting rail in cabinet or field junction box
  • Grounding of the cable shield via a gas discharge tube

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Ladda ned datablad som PDF::


Utdrag ur datablad: Tekniska data för  M-LBAS-IA1.IE

Product Description
Ethernet-APL surge protector for cabinet installation, Ex ia, Ex ec, indirect shield grounding
General specifications
Design / MountingCabinet installation
Ethernet Interface
Interface typeEthernet-APL auxiliary device
Electrical specifications
Rated voltage30 V
Rated current500 mA
Impulse rating2 kV/1 kA (category C1) per line
10 kV/5 kA (category C2) per line
1 kA (category D1) per line
Impulse discharge current (10/350 µs)0.5 kA per line
Nominal discharge current (8/20 µs)
per line5 kA
total10 kA
Shield10 kA
Max. surge current (8/20 µs)10 kA overstressed fault mode 3 acc. to IEC 61643-21
Voltage protection level
Line/Earthmax. 1500 V C1 , 1 kA per line
max. 2100 V C2 , 5 kA per line
max. 50 V C3 , 50 A per line
max. 1300 V B2 , 50 A per line
Shield/Earthmax. 1500 V C1 , max. 1800 V C2 , max. 50 V C3 , max. 1300 V B2
Standard conformity
Degree of protectionIEC/EN 60529
Climatic conditionsIEC 60721
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Surge protectionIEC 61643-21
EthernetEthernet-APL ,
IEEE 802.3 for 10BASE-T1L
Ambient conditions
Ambient temperature-40 ... 80 °C (-40 ... 176 °F)
Storage temperature-50 ... 90 °C (-58 ... 194 °F)
Relative humidity≤ 95 % non-condensing
Shock resistance15 g 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Mechanical specifications
Connection typescrew terminals
Core cross sectionsolid wire 0.5 ... 2.5 mm2 ,
stranded wire 0.5 ... 1.5 mm2
Housing materialPolyamide PA 6.6
Degree of protectionIP20
Mass32 g
Mounting35 mm DIN mounting rail
Data for application in connection with hazardous areas
EU-type examination certificateTÜV 22 ATEX 8786 X , TÜV 22 ATEX 8816 X
Marking2-WISE auxiliary device , FISCO
MarkingEx-Hexagon ll 3 G Ex ec llC T6 Gc ,
Ex-Hexagon ll 2 (1) G Ex ia [ia Ga] IIC T6 Gb ,
Ex-Hexagon ll 2 (1) D Ex ia [ia Da] lIIC T80°C Db ,
Ex-Hexagon l M2 (M1) Ex ia [ia Ma] l Mb
Voltage30 V
Current500 mA
Internal capacitancenegligible 0 nF
Internal inductancenegligible 0 µH
Directive conformity
Directive 2014/34/EUEN 60079-0:2018 ,
EN 60079-11:2012 ,
IEC TS 60079-47:2021
Supplementary information
International approvals
IECEx approvalIECEx TUR 22.0017X
Approved forEx ec llC T6 Gc ,
Ex ia [ia Ga] IIC T6 Gb ,
Ex ia [ia Da] lIIC T80°C Db ,
Ex ia [ia Ma] l Mb
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027171202
ECLASS 12.027171202
ECLASS 11.027130805
ECLASS 10.0.127130805
ECLASS 9.027130805
ECLASS 8.027130805
ECLASS 5.127130801
ETIM 9.0EC000941
ETIM 8.0EC000941
ETIM 7.0EC000941
ETIM 6.0EC000941
ETIM 5.0EC000941
UNSPSC 12.139121610

Details: M-LBAS-IA1.IE

Informative Literature: M-LBAS-IA1.IE

Language Selection:
LiteratureLanguageFile TypeFile Size
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronENGPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingENGPDF470 KB

Product Documentation: M-LBAS-IA1.IE

Language Selection:
Safety and Security DocumentationLanguageFile TypeFile Size
ManualSWEPDF161 KB
Manuals
ManualENGPDF1648 KB

Design / Simulation: M-LBAS-IA1.IE

Language Selection:
CADLanguageFile TypeFile Size
CAD 3-D / CAD 3-DALLSTP3749 KB

Approvals: M-LBAS-IA1.IE

Language Selection:
CertificatesCert No.LanguageFile TypeFile Size
China SITIIAS CCC Ex Certificate2022322304004748 (Singapore)ALLPDF1107 KB
Europe TUV Rheinland ATEX Certificate Surge Protective Device ATEX Category 2 (1)TÜV 22 ATEX 8786 XALLPDF1538 KB
Europe TUV Rheinland Surge Protective Device ATEX Category 3 G TÜV AtexTÜV 22 ATEX 8816 XALLPDF171 KB
Worldwide TUV Rheinland Surge Protective Device IECEx Certificate of ConformityIECEx TUR 22.0017XALLLINK---
Declaration of Conformity
EU Declaration of Conformity (P+F)TDOC-5856_SWESWEPDF174 KB

Ethernet-APL möjliggör kontinuerlig kommunikation över alla hierarkiska nivåer. Läs mer om den banbrytande tekniken …

RSS Info Service for PANOS Updates

Stay informed when a new software update of PANOS, the operating system for Ethernet-APL switches, is released: With our RSS Feed you will get an email notfication in your inbox immediately after an update has been released.

Från beslut till planering, installation och driftsättning till drift och underhåll: Upptäck hur du får ut det mesta av din fältbussinfrastruktur …