General specifications |
Design / Mounting | Cabinet installation |
Installation in hazardous area | Zone 2 / Div. 2 |
Supply |
Connection | Power Rail or terminals 59+, 60-, 58 FE |
Rated voltage | 20 ... 35 V DC |
Ripple | ≤ 10 % |
Rated current | 190 mA ... 430 mA |
Fieldbus connection |
Number of segments | 1 |
Rated voltage | 24 ... 26 V |
PROFIBUS PA | |
| Connection | terminals 3, 18+; 2, 17- |
| Rated voltage | 12.6 ... 13.4 V |
| Rated current | max. 100 mA |
| Terminating impedance | 100 Ω , integrated |
PROFIBUS DP | PROFIBUS with RS-485 transmission technology |
| Connection | Terminals 40 RxD/TxD-P, 41 RxD/TxD-N, 42 screen/FE, 55 DGND, 56 CNTR-P, 57 VP |
| Baud rate | 93.75 kBit/s |
| Terminating impedance | with rotary switch (S1) switchable: 1 = on; 0 = off |
Galvanic isolation |
PROFIBUS DP/PROFIBUS PA | safe galvanic isolation acc. to EN 50020, voltage peak value 375 V |
PROFIBUS DP/Supply | functional insulation acc. to DIN EN 50178, rated insulation voltage 50 Veff |
PROFIBUS PA/Supply | safe galvanic isolation acc. to EN 50020, voltage peak value 375 V |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 |
Standard conformity |
Galvanic isolation | EN 50178 |
Electromagnetic compatibility | NE 21:2006 |
Degree of protection | IEC 60529 |
Fieldbus standard | EN 50170/2 |
Climatic conditions | IEC 60721 |
Ambient conditions |
Classification | 3K3 |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
Relative humidity | < 75 % |
Pollution degree | max. 2, according to IEC 60664 |
Mechanical specifications |
Connection type | screw terminal , pluggable |
Core cross section | up to 2.5 mm2 |
Housing | 100 mm x 115 mm x 107 mm |
Housing material | Polycarbonate |
Degree of protection | IP20 |
Mass | 650 g |
Mounting | DIN rail mounting |
Data for application in connection with hazardous areas |
EU-type examination certificate | PTB 99 ATEX 2142 , for additional certificates see www.pepperl-fuchs.com |
| Marking | II (1) G [Ex ia] IIC Ga , II (1) D [Ex ia] IIIC Da |
Supply | |
| Maximum safe voltage | 253 V AC / 125 V DC (Attention! Um is no rated voltage.) |
PROFIBUS PA | |
| Voltage | 15 V |
| Current | 207.2 mA |
| Power | 1.93 W |
| Maximum safe voltage | 60 V |
Certificate | PF 15 CERT 3527 X |
| Marking | II 3G Ex ec II T4 Gc |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-7:2015 , EN 60079-11:2012 |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |