General specifications |
Signal type | Digital Input |
Supply |
Connection | terminals 14, 15 |
Rated voltage | 103.5 ... 126 V AC , 45 ... 65 Hz |
Rated current | 12 mA |
Power consumption | < 1.2 W |
Input |
Connection side | field side |
Connection | terminals 1 (mass), 2 (min), 3 (max) |
Control input | min./max. control system: terminals 1, 2, 3 on/off control system: terminals 1, 3 |
Response sensitivity | 1 ... 150 kΩ , adjustable via potentiometer |
Output |
Connection side | control side |
Connection | terminals 7, 8, 9; 10, 11, 12 |
Switching power | max. 192 W , 2000 VA |
Output | relay |
Contact loading | 253 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load |
Time constant for signal damping | 0.5 s, 2 s, 5 s, 10 s |
Galvanic isolation |
Input/Output | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Input/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Indicators/settings |
Display elements | LEDs |
Control elements | DIP switch potentiometer |
Configuration | via DIP switches via potentiometer |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Low voltage | |
| Directive 2014/35/EU | EN 61010-1:2010 |
Conformity |
Electromagnetic compatibility | NE 21:2006 |
Degree of protection | IEC 60529:2001 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) extended ambient temperature range up to 70 °C (158 °F), refer to manual for necessary mounting conditions |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals , max. 2.5 mm2 |
Mass | approx. 150 g |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 |
| Height | 119 mm |
| Width | 20 mm |
| Depth | 115 mm |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |