Serviceline Industrial Sensors
Serviceline Explosion Protection

Type Z & Ex pzc purge and pressurization system 5500 Control Unit

5500 Control Unit
  • 100% automatic purge and pressurization system including purging, temperature and leakage control, alarming and system power
  • Third party approvals for Class I, II, Div. 2 and Zone 2/22
  • Universal mounting
  • RTD inputs for temperature alarm and control
  • Five standard purge programs

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Ladda ned datablad som PDF::


Utdrag ur datablad: Tekniska data för  5500 Control Unit

Product Description
Bebco EPS 5500 series Type Z & Ex pzc purge and pressurization control unit
General specifications
Operating modefully automatic (FA)
Series5500
SystemType Z Purge ; Ex pzc Purge
Number of volume exchanges4 ... 19
Hazardous environmentgas or dust
Supply
Rated voltage100 ... 240 V AC, 0.05 A, 50 ... 60 Hz
20 ... 30 V DC, 0.2 A
Power consumption100 ... 240 V AC - 2.3 VA (without digital valve)
20 ... 30 V DC - 2.5 W (without digital valve)
Electrical specifications
Fuse ratingF2:
AC: max. 2 A
DC: max. 3.15 A
F1:
AC: max. 0.08 A
DC: max. 0.5 A
Input
Input ITemperature, up to 2 RTDs per unit
ConnectionPt100, 2-wire-connection
Input typetemperature input
Input accuracy: 2.5% of the measurement value + PT100 error
Input II1 Bypass
Connectionpassive contact (switch)
Input typemechanical contact
Output
Output I
ConnectionK1, terminals: K1/N0, K1/N0
Output typeenclosure power, (1) SPST
Inrush current6 A
Contact loading6 A at 250 V AC , 30 V DC resistive load, 6 A at 30 V DC
Output II
ConnectionK2, terminals: K2 (NO, C, NC)
Output typealarm, (1) SPDT
Inrush current3 A
Contact loading3 A at 250 V AC , 30 V DC resistive load, 3 A at 30 V DC
Output III
Connectiondigital valve, terminals SV
Output type(1) SPST, powered contacts from supply
5.0 A at 250 VAC or 30 VDC
Inrush current5 A
Indicators/settings
LED indicationMembrane Pad
K1: Green - Contact K1 is energized
K2: Amber - Contact K2 is energized
SV/encl press.: Blue for safe pressure, Amber for valve on
Bypass: Amber when bypass is active
PT100 error: Red when fault in PT100 sensor
Pneumatic parameters
Protective gas supplyinstrument grade air or inert gas
Safe pressure- gas 0.7 mbar (0.3 in w.c.)
- dust 1.6 mbar (0.65 in w.c.)
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
RoHS
Directive 2011/65/EU (RoHS)EN IEC 63000:2018
Conformity
Degree of protectionEN 60529
Shock resistanceEN 60068-2
Ambient conditions
Ambient temperature-20 ... 40 °C (-4 ... 104 °F) at T6
-20 ... 60 °C (-4 ... 140 °F) at T4
Relative humidity5 ... 95 %, non-condensing
Vibration resistance5 ... 100 Hz , 1 g, 12 m/s2, all axes
Impact resistance30 g, 11 ms, all axes
Mechanical specifications
Connection typeHigh pressure port: 1/8" NPTF
Low pressure port: 1/8" NPTF
Cable glandCable size
M12 diameter 3 - 6.5 mm
M20 diameter 10 - 12 mm
RTD/Bypass: (3) M12x1.5
K1, K2, SV: 'P_C' (3) M20x1.5
Degree of protectionType 4X, IP66
MaterialHousing: 316 stainless steel
Cable Gland: 316 stainless steel or Nickel Plated Brass
Pressure Ports: 316 stainless steel
Membrane Pad: Autotex F200XE
O-ring: EPDM
Massapprox. 2.7 kg (6 lb)
Dimensions165 x 124 x 90 mm (6.5 x 4.9 x 3.5 in)
Height203 mm
Width165 mm
Depth105 mm
Data for application in connection with hazardous areas
CertificateDEMKO 14 ATEX 1282X
MarkingEx-Hexagon II 3 (3) G Ex ic ec nC [ic Gc] [pzc Gc] IIC T4 Gc (-20 °C ≤ Ta ≤ 60 °C)
Ex-Hexagon II 3 (3) G Ex ic ec nC [ic Gc] [pzc Gc] IIC T6 Gc (-20 °C ≤ Ta ≤ 40 °C)
Ex-Hexagon II 3 (3) D Ex ic tc [ic IIIC Dc] [pzc Dc] IIIB T80 °C Dc (-20 °C ≤ Ta ≤ 60 °C) (external version)
Ex-Hexagon II 3 (3) D Ex ic tc [ic IIIC Dc] [pzc Dc] IIIB T60 °C Dc (-20 °C ≤ Ta ≤ 40 °C) (external version)
Ex-Hexagon II 3 (3) D Ex ic tc [ic Dc] [pzc Dc] IIIC T80 °C Dc (-20 °C ≤ Ta ≤ 60 °C) (internal version)
Ex-Hexagon II 3 (3) D Ex ic tc [ic Dc] [pzc Dc] IIIC T60 °C Dc (-20 °C ≤ Ta ≤ 40 °C) (internal version)
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018 , EN 60079-11:2012 , EN 60079-15:2019 , EN 60079-2:2014 ,
EN 60079-7:2015+A1:2018 , EN 60079-31:2014
International approvals
UL approval
cULusUL File E184741
Class I, Division 2, Groups A, B, C, D T4 (-20 °C ≤ Ta ≤ 60 °C)
Class II, Division 2, Groups F, G, T4 (-20 °C ≤ Ta ≤ 60 °C)
Class I, Division 2, Groups A, B, C, D T6 (-20 °C ≤ Ta ≤ 40 °C)
Class II, Division 2, Groups F, G T6 (-20 °C ≤ Ta ≤ 40 °C)
IECEx approvalIECEx UL 14.0019X
Ex ic ec nC [ic Gc] [pzc Gc] IIC T4 Gc (-20 °C ≤ Ta ≤ 60 °C)
Ex ic ec nC [ic Gc] [pzc Gc] IIC T6 Gc (-20 °C ≤ Ta ≤ 40 °C)
Ex ic tc [ic IIIC Dc] [pzc Dc] IIIB T80 °C Dc (-20 °C ≤ Ta ≤ 60 °C) (external version)
Ex ic tc [ic IIIC Dc] [pzc Dc] IIIB T60 °C Dc (-20 °C ≤ Ta ≤ 40 °C) (external version)
Ex ic tc [ic Dc] [pzc Dc] IIIC T80 °C Dc (-20 °C ≤ Ta ≤ 60 °C) (internal version)
Ex ic tc [ic Dc] [pzc Dc] IIIC T60 °C Dc (-20 °C ≤ Ta ≤ 40 °C) (internal version)
General information
Supplementary informationType Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027180508
ECLASS 12.027180508
ECLASS 11.027180508
ECLASS 10.0.127180508
ECLASS 9.027180508
ECLASS 8.027180508
ECLASS 5.140050501
ETIM 9.0EC000243
ETIM 8.0EC000243
ETIM 7.0EC000243
ETIM 6.0EC000243
ETIM 5.0EC000243
UNSPSC 12.139121301

Details: 5500 Control Unit

Product Documentation: 5500 Control Unit

Language Selection:
Product informationLanguageFile TypeFile Size
Basic Explosion Protection Compendium - Type of Protection "Purge and Pressurization"ENGPDF3860 KB
Brief Instructions
Purge & Pressurization Smart App - Users Guide / Purge & Pressurization Smart App - Users GuideALLPDF1771 KB
5500 Series Purge and Pressurization Quick GuideENGPDF1140 KB
Safety and Security Documentation
ManualSWEPDF161 KB
Manuals
User Manual for the 5500 Series Purge and Pressurization SystemENGPDF2706 KB

Design / Simulation: 5500 Control Unit

Language Selection:
CADLanguageFile TypeFile Size
DWG and STP files for the Purge 5500, External Mount Version "EXT1" / CAD 2-DALLZIP2832 KB
DWG and STP files for the Purge 5500, Internal Mount Version "PM01" and "PM02" / CAD 2-DALLZIP2800 KB

Approvals: 5500 Control Unit

Language Selection:
CertificatesCert No.LanguageFile TypeFile Size
ATEX CertificateDEMKO 14 ATEX 1282XALLPDF129 KB
China SITIIAS CCC Ex Certificate2020322304002488 (Katy, TX USA)ALLPDF1580 KB
IECEx Certificate of ConformityIECEx UL 14.0019XALLLINK---
India PESO (India) CCOEA/P/HQ/KA/104/5761 (P471351)ALLPDF563 KB
Korea KOSHA16-AV4BO-0139XALLPDF530 KB
UL Hazardous LocationE184741 (RFPW, RFPW7)ALLLINK431 KB
Control Drawings
5500 Pz, Type Z Purge System control drawing / Control drawing UL   ALLPDF130 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-B020FALLPDF162 KB
UK Declaration of Conformity (P+F) / UK-Konformitäterklärung (P+F)DOC-B0G0AALLPDF159 KB

Associated Products: 5500 Control Unit

Accessories
Bebco EPS 5500 series ventpa
Manifold valve used in FM and CSA certificated installationpa
Manifold valve used in UL certified installationpa
pa
Manifold valve used in ATEX and IECEx certificated installationpa
Manifold valve used in UL certified installationpa
Manifold valve used in UL certified installationpa
Manifold valve used in UL certified installationpa

Get to know the smartest way to ensure hazardous location protection and configure your individual purge and pressurization system!

Our interactive app gives you a step-by-step programming simulation for your purge and pressurization system. Download the free-of-charge app for iOS or Android devices now …

Ex p Purge Units