General specifications |
Design / Mounting | Cabinet installation |
Installation in hazardous area | Zone 2 / Div. 2 |
Fieldbus connection |
Main cable (Trunk) | |
| Rated voltage | 9 ... 31 V DC 10.5 V DC minimum input voltage acc. to FF-846 |
| Rated current | max. 4.5 A |
Outputs | |
| Number of outputs | see table "Technical data depending on model" |
| Number of devices per output | 1 |
| Rated voltage | max. 31 V |
| Rated current | max. 32 mA switch 1, position 1 max. 43 mA switch 1, position 2 |
| Short-circuit current | 46 mA switch 1, position 1 57 mA switch 1, position 2 |
Self current consumption | see table "Technical data depending on model" |
Voltage drop main cable/outputs | max. 1.2 V |
Voltage drop trunk In/Out | 0 V |
Terminating resistor | external type M-FT 100 Ω +/- 10 % |
Surge protection | Trunk overvoltage protection if voltage exceeds typ. 39 V, max. 41 V |
Indicators/operating means |
Switch | configuration of short-circuit current/rated current |
LED PWR | green: Fieldbus voltage > 10 V and fieldbus terminator is deactivated |
LED COM/ERR | yellow: flashing: fieldbus communication status and physical layer diagnostic status |
LED SPURS | red: 2 Hz flashing in short-circuit condition |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 |
Standard conformity |
Electromagnetic compatibility | NE 21:2011 |
Degree of protection | IEC 60529 |
Fieldbus standard | IEC 61158-2 |
Climatic conditions | IEC 60721 |
Shock resistance | EN 60068-2-27 |
Vibration resistance | EN 60068-2-6 |
Ambient conditions |
Ambient temperature | -50 ... 70 °C (-58 ... 158 °F) |
Storage temperature | -50 ... 85 °C (-58 ... 185 °F) |
Relative humidity | < 95 % non-condensing |
Shock resistance | 15 g 11 ms |
Vibration resistance | 1 g , 10 ... 150 Hz |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 |
Mechanical specifications |
Connection type | screw terminal , pluggable or spring terminal , pluggable |
Core cross section | see table 2 |
Housing material | Polycarbonate |
Degree of protection | IP20 |
Mass | see table "Technical data depending on model" |
Dimensions | see table "Technical data depending on model" |
Mounting | DIN rail mounting |
Data for application in connection with hazardous areas |
EU-type examination certificate | TÜV 12 ATEX 098651 X |
| Marking | II 3G Ex nA [ic] IIC T4 Gc II (3)D [Ex ic Dc] IIIC |
Supply | |
| Maximum safe voltage | 35 V |
Outputs | |
| Voltage | 32 V |
| Current | 46 mA switch 1, position 1 65 mA switch 1, position 2 |
| Inductance | 0.125 mH switch 1, position 1 0.25 mH switch 1, position 2 |
| Capacitance | 60 nF |
Directive conformity | |
| Directive 2014/34/EU | EN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals |
UL approval | E106378 |
| Control drawing | 116-0406 |
| Approved for | Class I, Division 2, Groups A, B, C, D |
IECEx approval | IECEx TUN 12.0015X |
| Approved for | Ex nA [ic] IIC T4 Gc [Ex ic Dc] IIIC |
General information |