General specifications |
Signal type | Digital Output |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 3 |
Systematic capability (SC) | SC 3 |
Supply |
Connection | terminals 5+, 6- loop powered Power Rail or terminals 9+, 10- bus powered |
Rated voltage | 19 ... 30 V DC loop powered |
Input current | 75 mA at 24 V , 270 Ω load |
Power dissipation | 1.3 W at 24 V , 270 Ω load |
Input |
Connection side | control side |
Connection | terminals 5+, 6- |
Test pulse length | max. 2 ms from DO card |
Signal level | loop powered 1-signal: 19 ... 30 V DC 0-signal: 0 ... 5 V DC bus powered 1-signal: 15 ... 30 V DC (current limited to 5 mA) 0-signal: 0 ... 5 V DC |
Rated current | 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ≥ 36 mA (minimum load current DO card) |
Inrush current | < 200 mA , 10 ms loop powered |
Output |
Connection side | field side |
Connection | terminals 1+, 2- |
Internal resistor | 240 Ω |
Current | typ. 45 mA |
Voltage | typ. 12 V |
Current limit | 50 mA |
Open loop voltage | typ. 24.6 V |
Load | nominal 0.05 ... 18 kΩ , valid range for line fault detection (LFD) |
Output II | fault signal |
| Connection | terminals 7, 8 , non-intrinsically safe |
| Contact loading | 30 V DC/ 0.5 A resistive load |
| Mechanical life | 105 switching cycles |
| Energized/De-energized delay | ≤ 20 ms / ≤ 20 ms |
Line fault detection | |
| Test current | max. 350 µA , calculated by ILFD = 4.7 V / (15 kΩ + RLoad) |
Galvanic isolation |
Output/other circuits | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output II/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 32 Veff |
Indicators/settings |
Display elements | LEDs |
Control elements | DIP switch |
Configuration | via DIP switches |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Conformity |
Electromagnetic compatibility | NE 21:2012 , EN 61326-3-2:2008 For further information see system description. |
Degree of protection | IEC 60529:2013 |
Protection against electrical shock | EN 61010-1:2010 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) Observe the temperature range limited by derating, see section derating. |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 150 g |
Dimensions | 12.5 x 119 x 114 mm (0.5 x 4.7 x 4.5 inch) (W x H x D) , housing type A2 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas |
EU-type examination certificate | EXA 17 ATEX 0002 X |
| Marking | II 3(1)G Ex nC ec [ia Ga] IIC T4 Gc
II (1)D [Ex ia Da] IIIC
I (M1) [Ex ia Ma] I |
| Output I | Ex ia |
| Voltage | 26 V |
| Current | 110 mA |
| Power | 715 mW |
Supply | |
| Maximum safe voltage | 60 V (Attention! The rated voltage can be lower.) |
Input | |
| Maximum safe voltage | 60 V (Attention! The rated voltage can be lower.) |
Collective error message | |
| Maximum safe voltage | 60 V (Attention! The rated voltage can be lower.) |
Galvanic isolation | |
| Output I/other circuits | safe electrical isolation acc. to IEC/EN 60079-11, rated insulation voltage 300 Vrms |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals |
UL approval | E106378 |
| Control drawing | 116-0448 (cULus) |
IECEx approval | |
| IECEx certificate | IECEx EXA 17.0001X |
| IECEx marking | Ex nC ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |