Support Industrielle sensorer
Support Explosion Protection

RTD Converter KFD0-TR-1

KFD0-TR-1
  • 1-channel signal conditioner
  • 24 V DC supply (loop powered)
  • 2- or 3-wire Pt100 RTD input
  • Output 4 mA ... 20 mA, temperature linearization selectable
  • DIP switch selectable ranges
  • Sensor breakage detection

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Hent hele databladet som PDF:


Uddrag af datablad: Tekniske data for   KFD0-TR-1

General specifications
Signal typeAnalog input
Supply
Rated voltage12 ... 35 V DC loop powered
Power dissipation0.4 W
Input
Connection sidefield side
Connectionterminals 1, 2-, 3+
suitable for Pt100, 2- and 3-wire connection
Lead resistancemax. 100 Ω per line
Measuring currentapprox. 1 mA
Output
Connection sidecontrol side
Connectionterminals 9+, 8-
Load(U -12 V) / 0.02 A
Current output4 ... 20 mA , limited to ≤ 35 mA
Fault signalsensor burnout: upscaling ≥ 22 mA , limited to ≤ 35 mA
Transfer characteristics
Measuring rangespan without linearization 25 ... 800 °C (77 ... 1472 °F)/ with linearisation 25 ... 375 °C (77 ... 707 °F)
zero point without linearization -200 ... 400 °C (-328 ... 752 °F)/ with linearisation -30 ... 375 °C (-22 ... 707 °F)
span and zero point adjustable
Deviation
After calibration0.1 % of full-scale value
Influence of ambient temperaturespan and zero point 0.015 % / K or ± 10 mΩ / K
Influence of supply voltage6.5 ppm/V
Rise time250 ms
Galvanic isolation
Input/Outputsafe isolation acc. to DIN VDE 0106, rated insulation voltage 253 Veff
Indicators/settings
Control elementsDIP switch
rotary switch
Configurationvia DIP switches
via rotary switch
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Insulation coordinationEN 50178
Galvanic isolationEN 50178
Degree of protectionIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
extended ambient temperature range up to 70 °C (158 °F), refer to manual for necessary mounting conditions
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 150 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Height119 mm
Width20 mm
Depth115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210129
ECLASS 12.027210129
ECLASS 11.027210129
ECLASS 10.0.127210129
ECLASS 9.027210129
ECLASS 8.027210190
ECLASS 5.127210107
ETIM 9.0EC002919
ETIM 8.0EC002919
ETIM 7.0EC002919
ETIM 6.0EC002919
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: KFD0-TR-1

Informative Literature: KFD0-TR-1

Language Selection:
LiteratureSprogFil typeFil størrelse
Application Report - Biological Cleaning of Wastwater and Secondary Sedimentation StageENGPDF566 KB
Application Report - Generating Electricity in Coal-Fired Power PlantsENGPDF412 KB
Application Report - Reliable Signal Conversion at High Ambient TemperaturesENGPDF291 KB
Application Report - Sand Trap and Preliminary Sedimentation StageENGPDF448 KB
Application Report - Screening Systems in Sewage Treatment PlantsENGPDF577 KB

Product Documentation: KFD0-TR-1

Language Selection:
Safety and Security DocumentationSprogFil typeFil størrelse
Instruktions manualDANPDF47 KB
Manuals
System ManualENGPDF3694 KB

Design / Simulation: KFD0-TR-1

Language Selection:
CADSprogFil typeFil størrelse
CAD 3-D / CAD 3-DALLSTP2510 KB
CAD Portal / CAD PortalALLLINK---
CAE
CAE EPLAN Data Portal / CAE EPLAN Data PortalALLLINK---
CAE EPLAN macro EDZ / CAE EPLAN Makro EDZALLEDZ938 KB

Approvals: KFD0-TR-1

Language Selection:
Declaration of ConformityCertifikat nr.SprogFil typeFil størrelse
EU Declaration of Conformity (P+F)TDOC-2203ADANDANPDF169 KB

Tilhørende produkter: KFD0-TR-1

Matching System Components
Cable trunking is integrated in the mounting profile, Safe spacious separation of field and control signals, No additional cable guides necessary, Standard length 1.8 m (5.8 ft), simple to customize to application space, With mounting aidspa
Accessories
3-pin screw terminal, For KF modules of K-System, Packaging unit: 5 pieces greenpa
Coding of K-System terminal blocks, Coding of LB/FB-System front sockets, Packaging unit: 20 x 6 coding pinspa
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.