General specifications |
Signal type | Digital Output |
Functional safety related parameters |
Safety Integrity Level (SIL) | SIL 3 |
Systematic capability (SC) | SC 3 |
Performance level (PL) | PL e |
Supply |
Connection | Power Rail or terminals 14+, 15- |
Rated voltage | 19 ... 26.4 V DC |
Input current | max. 35 mA at 24 V DC , max. 44 mA at 19 V DC , with enabled internal fault detection |
Power consumption | < 1.7 W , includes the power consumption of the digital input , see derating curves |
Input |
Connection side | control side |
Connection | terminals 7+, 8- |
Pulse/Pause ratio | min. 150 ms / min. 150 ms with disabled internal fault detection min. 1 s / min. 1 s with enabled internal fault detection |
Test pulse length | max. 2 ms from DO card |
Signal level | 0-signal: -5 ... 5 V DC 1-signal: 19 ... 26.4 V DC |
Rated current | 0-signal: typ. 1.6 mA at 1.5 V DC; typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: ≥ 36 mA (minimum load current DO card) |
Inrush current | < 200 mA after 100 µs |
Output |
Connection side | field side |
Connection | external voltage : terminals 4+/L, 5+/L, 2-/N load : terminals 6, 3 |
Connectable voltage | 50 ... 230 V AC 60 ... 110 V DC |
Power dissipation | < 3.3 W at 5 A , see derating curves |
Contact loading | 253 V AC/5 A/cos φ 0.7; 30 V DC/5 A resistive load , see derating curves |
Minimum switch current | 10 mA |
Mechanical life | 5 x 106 switching cycles |
Line fault detection | low voltage < 35 V AC undercurrent: 10 mA AC; overcurrent: 5.5 A AC (relay energized) breakage: 48 kΩ; short-circuit: 29 Ω (load, relay de-energized) |
Fuse rating | 2.5 A (scope of delivery) max. 5 AT, recommended maximum utilization of the fuse: 80 % |
Fault indication output |
Connection | terminals 10, 11 |
Contact loading | 30 V DC/ 0.5 A resistive load |
Reaction time | < 2 s |
Mechanical life | 105 switching cycles |
Transfer characteristics |
Switching frequency | < 3 Hz with disabled internal fault detection < 0.5 Hz with enabled internal fault detection |
Galvanic isolation |
Input/power supply | basic insulation according to IEC/EN 61010-1, rated insulation voltage 60 Veff |
Input/fault indication output | basic insulation according to IEC/EN 61010-1, rated insulation voltage 30 Veff |
Output/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Indicators/settings |
Display elements | LEDs |
Control elements | DIP switch |
Configuration | via DIP switches |
Labeling | space for labeling at the front |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Low voltage | |
| Directive 2014/35/EU | EN 61010-1:2010 |
Machinery Directive | |
| Directive 2006/42/EC | EN 62061:2005+AC:2010+A1:2013+A2:2015 , EN/ISO 13849-1:2015 |
Conformity |
Electromagnetic compatibility | NE 21:2017 , IEC/EN 61326-3-2:2018 , EN 61326-3-1:2017 |
Degree of protection | IEC 60529:2013 |
Ambient conditions |
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) Observe the temperature range limited by derating, see section derating. |
Mechanical specifications |
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 142 g |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2 |
| Height | 119 mm |
| Width | 20 mm |
| Depth | 115 mm |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General information |
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com. |