Support Industrielle sensorer
Support Explosion Protection

AS-Interface printed circuit board VBA-2E1A-CB-N/E2-S

VBA-2E1A-CB-N/E2-S
  • A/B node with extended addressing possibility for up to 62 nodes
  • Communication monitoring
  • Inputs according to NAMUR in acc. with EN 60947-5-6
  • Power supply of inputs and the output from AS-Interface
  • Function display for bus and inputs
  • Lead breakage and short-circuit monitoring of the output
  • Connection via screw terminals

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Hent hele databladet som PDF:


Uddrag af datablad: Tekniske data for   VBA-2E1A-CB-N/E2-S

Produkt beskrivelse
Printed circuit board module
2 NAMUR inputs and 1 electronic output
General specifications
Node typeA/B node
Indicators/operating means
LED PWR/FAULTdual LED green/red
LED 1 green: AS-Interface voltage OK
LED 1 red: communication error or address is 0
LED 1 green/red flashing: short-circuit or lead breakage
LED IN2 LEDs yellow;
LED 2 yellow illuminated: switching state IN1 ON, otherwise OFF
LED 3 yellow illuminated: switching state IN2 ON, otherwise OFF
Electrical specifications
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current≤ 40 mA (without sensors) / max. 150 mA
Protection classIII
Input
Number/Type2 inputs for NAMUR Sensors
Supplyfrom AS-Interface
Voltage8 V
Input current≤ 8 mA (limited internally)
Switching pointOFF ≤ 1.2 mA
ON ≥ 2.1 mA
according to DIN EN 60947-5-6
Output
Number/Type1 electronic output, switched low, overload and short-circuit proof, lead breakage and short-circuit monitored
Supplyfrom AS-Interface
Voltage21 ... 31 V
Currentmax. 100 mA
Standard conformity
Degree of protectionEN 60529:2000
AS-InterfaceEN 62026-2:2013
Programming instructions
ProfileS-D.A.E
IO codeD
ID codeA
ID1 code7
ID2 codeE
Data bits (function via AS-Interface)InputOutput
D0 - OUT1
D1 - -
D2 IN1 -
D3 IN2 -
Parameter bits (programmable via AS-i)function
P0not used
P1not used
P2not used
P3not used
Ambient conditions
Ambient temperature-25 ... 60 °C (-13 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Degree of protectionIP20 (completely fitted) according to EN 60529
Connectionscrew terminal strip
max. conductor cross section 1 mm2
Mass20 g
Dimensions
Height1.6 mm
Width55 mm
Length51 mm

Classifications

SystemClasscode
ECLASS 13.027242604
ECLASS 12.027242604
ECLASS 11.027242604
ECLASS 10.0.127242604
ECLASS 9.027242604
ECLASS 8.027242604
ECLASS 5.127242604
ETIM 9.0EC001599
ETIM 8.0EC001599
ETIM 7.0EC001599
ETIM 6.0EC001599
ETIM 5.0EC001599
UNSPSC 12.139121535

Details: VBA-2E1A-CB-N/E2-S

Product Documentation: VBA-2E1A-CB-N/E2-S

Language Selection:
Brief InstructionsSprogFil typeFil størrelse
Instruction leaflet / BeipackzettelALLPDF267 KB

Approvals: VBA-2E1A-CB-N/E2-S

Language Selection:
Declaration of ConformityCertifikat nr.SprogFil typeFil størrelse
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-2715BALLPDF116 KB

Tilhørende produkter: VBA-2E1A-CB-N/E2-S

Accessories

AS-Interface Handheld with accessoryfa
Free Download: White Paper on TCP-Based Communication Protocols (PDF)

This free PDF white paper compares the different TCP-based communication protocols (AMQP, OPC UA, MQTT, REST API) that have found their way up and are considered the enablers of IIoT and Industry 4.0. Get your free download now!

AS-Interface Switch Cabinet Module KE5 – Simple Handling and Improved Manageability

The unique housing design of the new KE5 switch cabinet module enables distinct visibility and simplifies mounting, wiring, and maintenance inside switch cabinets and junction boxes.

AS-Interface Product Range

Get to know our full range of AS-Interface products.