Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Hent hele databladet som PDF:
Produkt beskrivelse |
---|
G11 analog module, 2 analog outputs |
General specifications | ||
---|---|---|
Node type | Standard node | |
AS-Interface specification | V3.0 | |
Required gateway specification | ≥ V2.1 | |
Profile | S-7.3.5 | |
IO code | 7 | |
ID code | 3 | |
ID1 code | F | |
ID2 code | 5 | |
UL File Number | E223772 | |
Indicators/operating means | ||
LED AS-i/FAULT | Status display; multi-colour LED Green: normal operation Red: communication fault Flashing yellow/red: address 0 Flashing green/red: peripheral fault |
|
LED ANALOG | Status of output signal; yellow LED Yellow: 0 mA ≤ I ≤ 23 mA Yellow flashing: lead breakage or I > 23 mA |
|
LED AUX | ext. auxiliary voltage UAUX; dual LED green/red green: voltage OK red: reverse voltage |
|
Electrical specifications | ||
Auxiliary voltage (output) | 24 V DC ± 15 % PELV | |
Rated operating voltage | 26.5 ... 31.6 V from AS-Interface | |
Rated operating current | ≤ 35 mA | |
Protection class | III | |
Surge protection | UAUX, Uin: Over voltage category III, safe isolated power supplies (PELV) | |
Output | ||
Number/Type | 2 analog outputs (current), 0 ... 20 mA | |
Supply | from AUX | |
Load | max. 600 Ω | |
Current loading capacity | ≤ 700 mA (signal current + actuator supply) from external bulk power supply UAUX, overload and short-circuit protected | |
Resolution | 6 µA | |
Accuracy | 0.15 % of full-scale value | |
Temperature influence | 1 µA/K | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 62026-2:2013 | |
Standard conformity | ||
Degree of protection | EN 60529:2000 | |
Fieldbus standard | EN 62026-2:2013 | |
Emitted interference | EN 61000-6-4:2007 | |
AS-Interface | EN 62026-2:2013 | |
Noise immunity | EN 61000-6-2:2005, EN 61326-1:2006, IEC 62026-2:2008 | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 85 % , noncondensing | |
Climatic conditions | For indoor use only | |
Altitude | ≤ 2000 m above MSL | |
Pollution degree | 3 | |
Mechanical specifications | ||
Degree of protection | IP68 / IP69K | |
Connection | AS-Interface/UAUX: M12 round connector Outputs: M12 round connector |
|
Material | ||
Housing | PBT PC | |
Mounting screw | Stainless steel 1.4305 / AISI 303 | |
Mass | 200 g | |
Tightening torque, housing screws | 1.8 Nm | |
Tightening torque, cable gland | 0.4 Nm | |
Dimensions | ||
Height | 35 mm | |
Diameter | 85 mm | |
Mounting | Mounting plate |
System | Classcode |
---|---|
ECLASS 13.0 | 27242601 |
ECLASS 12.0 | 27242601 |
ECLASS 11.0 | 27242601 |
ECLASS 10.0.1 | 27242601 |
ECLASS 9.0 | 27242601 |
ECLASS 8.0 | 27242601 |
ECLASS 5.1 | 27242601 |
ETIM 9.0 | EC001596 |
ETIM 8.0 | EC001596 |
ETIM 7.0 | EC001596 |
ETIM 6.0 | EC001596 |
ETIM 5.0 | EC001596 |
UNSPSC 12.1 | 39121535 |
Literature | Sprog | Fil type | Fil størrelse |
---|---|---|---|
Application Report - Automating Material Handling Systems for Airports with AS-Interface | ENG | 272 KB |
Brief Instructions | Sprog | Fil type | Fil størrelse |
---|---|---|---|
Instruction leaflet / Beipackzettel | ALL | 803 KB | |
Manuals | |||
Manual VBA-2A-G11-I* & VBA-4A-G11-I/U-F | ENG | 3049 KB |
Certificates | Certifikat nr. | Sprog | Fil type | Fil størrelse |
---|---|---|---|---|
Canada, USA UL | CoC 20141115-E223772 | ALL | 342 KB | |
Worldwide AS-International Association AS-Interface | 95304 | ALL | 109 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F) | DOC-2931B | ALL | 119 KB |
Accessories | ||||||
---|---|---|---|---|---|---|
|
||||||
|
AS-Interface Switch Cabinet Module KE5 – Simple Handling and Improved Manageability
The unique housing design of the new KE5 switch cabinet module enables distinct visibility and simplifies mounting, wiring, and maintenance inside switch cabinets and junction boxes.