Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Hent hele databladet som PDF:
Uddrag af datablad: Tekniske data for
6000-TEMP-01
Produkt beskrivelse |
Temperature Hub for 6000 Series Purge system |
General specifications |
Series | 6000 Series |
System | Type X Purge ; Ex pxb Purge |
Electrical specifications |
Connection | |
| Power | Intrinsically Safe back to 6000 control unit |
| Signal | BUS back to 6000 control unit |
| Connection | Intrinsically Safe cabeling |
Rated voltage | 13 V DC |
Rated current | max. 10 mA |
Distance | 20 m to 6000 Control Unit |
Ambient conditions |
Ambient temperature | -20 ... 85 °C (-4 ... 185 °F) |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
Relative humidity | < 95 % non-condensing |
Vibration resistance | 1 g , 10 ... 100 Hz , all axes |
Impact resistance | 30 g, 11 ms, all axes |
Mechanical specifications |
Connection type | screw terminals |
Core cross section | 12 ... 30 AWG |
Housing material | Akulon S225-KS |
Degree of protection | IP20 |
Mass | approx. 110 g |
Dimensions | 99 mm x 52 mm x 23 mm |
Mounting | panel or DIN rail mounting |
Data for application in connection with hazardous areas |
EU-type examination certificate | UL/Demko 07 ATEX 0705753X |
International approvals |
UL approval | File no: E184741 |
| cULus | File no: E184741 |
IECEx approval | IECEx UL 08.0003X |
Classifications
System | Classcode |
ECLASS 13.0 | 27180591 |
ECLASS 12.0 | 27180591 |
ECLASS 11.0 | 27180591 |
ECLASS 10.0.1 | 27299090 |
ECLASS 9.0 | 27299220 |
ECLASS 8.0 | 27299220 |
ECLASS 5.1 | 40050501 |
ETIM 9.0 | EC000243 |
ETIM 8.0 | EC000243 |
ETIM 7.0 | EC000243 |
ETIM 6.0 | EC000243 |
ETIM 5.0 | EC000243 |
UNSPSC 12.1 | 39121303 |
Details:
6000-TEMP-01
Product Documentation:
6000-TEMP-01