Support Industrielle sensorer
Support Explosion Protection

Segment Protector R2-SP-IC*

FieldConnex® Fieldbus
R2-SP-IC*
  • 4 ... 12 outputs Ex ic (FISCO or Entity) or non-incendive (Div 2)
  • Advanced fault isolation at the spur
  • Segment Protector in Zone 2/Div. 2
  • Instruments in Zone 2/Div. 2 or Zone 1/Div. 1
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • Advanced Diagnostics at the spur
  • Power, Com, Diagnostics, and Error LEDs
  • T-connector for easy installation and maintenance
  • Test points for easy troubleshooting

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Hent hele databladet som PDF:


Uddrag af datablad: Tekniske data for   R2-SP-IC*

Produkt beskrivelse
Segment protector, junction box for fieldbus with short-circuit and fault protection, field junction box, electronic component for control cabinet installation
General specifications
Design / MountingCabinet installation
Installation in hazardous areaZone 2 / Div. 2
Fieldbus connection
Main cable (Trunk)
Rated voltage9 ... 31 V DC
10.5 V DC minimum input voltage acc. to FF-846
Rated currentmax. 4.5 A
Outputs
Number of outputssee table "Technical data depending on model"
Number of devices per output1
Rated voltagemax. 31 V
Rated currentmax. 32 mA switch 1, position 1
max. 43 mA switch 1, position 2
Short-circuit current46 mA switch 1, position 1
57 mA switch 1, position 2
Self current consumptionsee table "Technical data depending on model"
Voltage drop main cable/outputsmax. 1.2 V
Voltage drop trunk In/Out0 V
Terminating resistorexternal type M-FT 100 Ω +/- 10 %
Surge protectionTrunk overvoltage protection if voltage exceeds typ. 39 V, max. 41 V
Indicators/operating means
Switchconfiguration of short-circuit current/rated current
LED PWRgreen: Fieldbus voltage > 10 V and fieldbus terminator is deactivated
LED COM/ERRyellow: flashing: fieldbus communication status and physical layer diagnostic status
LED SPURSred: 2 Hz flashing in short-circuit condition
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013
Standard conformity
Electromagnetic compatibilityNE 21:2011
Degree of protectionIEC 60529
Fieldbus standardIEC 61158-2
Climatic conditionsIEC 60721
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperature-50 ... 70 °C (-58 ... 158 °F)
Storage temperature-50 ... 85 °C (-58 ... 185 °F)
Relative humidity< 95 % non-condensing
Shock resistance15 g 11 ms
Vibration resistance1 g , 10 ... 150 Hz
Corrosion resistanceacc. to ISA-S71.04-1985, severity level G3
Mechanical specifications
Connection typescrew terminal , pluggable or spring terminal , pluggable
Core cross sectionsee table 2
Housing materialPolycarbonate
Degree of protectionIP20
Masssee table "Technical data depending on model"
Dimensionssee table "Technical data depending on model"
MountingDIN rail mounting
Data for application in connection with hazardous areas
EU-type examination certificateTÜV 12 ATEX 098651 X
MarkingEx-Hexagon II 3G Ex nA [ic] IIC T4 Gc
Ex-Hexagon II (3)D [Ex ic Dc] IIIC
Supply
Maximum safe voltage35 V
Outputs
Voltage32 V
Current46 mA switch 1, position 1
65 mA switch 1, position 2
Inductance0.125 mH switch 1, position 1
0.25 mH switch 1, position 2
Capacitance60 nF
Directive conformity
Directive 2014/34/EUEN IEC 60079-0:2018+AC:2020 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
UL approvalE106378
Control drawing116-0406
Approved forClass I, Division 2, Groups A, B, C, D
IECEx approvalIECEx TUN 12.0015X
Approved forEx nA [ic] IIC T4 Gc
[Ex ic Dc] IIIC
General information
Supplementary informationStatement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027242610
ECLASS 12.027242610
ECLASS 11.027242610
ECLASS 10.0.127242610
ECLASS 9.027242610
ECLASS 8.027242610
ECLASS 5.127242601
ETIM 9.0EC001601
ETIM 8.0EC001601
ETIM 7.0EC001601
ETIM 6.0EC001601
ETIM 5.0EC001604
UNSPSC 12.139121008

Details: R2-SP-IC*

Informative Literature: R2-SP-IC*

Language Selection:
LiteratureSprogFil typeFil størrelse
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-SynchrotronENGPDF361 KB
Application Report - Digital Communication in Steel-Plate ManufacturingENGPDF470 KB
Application Report - Intelligent Fault Protection between Segment and FieldENGPDF210 KB

Product Documentation: R2-SP-IC*

Language Selection:
System DescriptionsSprogFil typeFil størrelse
Conformity matrix for R2-SP-IC* and F2-SP-IC* with motherboards: MB*-, MBHD*, FBTA-228-BPFB-8, FBTA-228-BPFB-R-4R and power supply modules: HD2-FBPS-*ENGPDF73 KB
Conformity matrix for R2-SP-IC* and F2-SP-IC* with motherboards: MBHC*, FBTA-228-BPFB-R-8R and power supply modules: HCD2-FBPS-*ENGPDF143 KB
Safety and Security Documentation
Instruktions manualDANPDF224 KB
Manuals
ManualENGPDF3049 KB

Design / Simulation: R2-SP-IC*

Language Selection:
CADSprogFil typeFil størrelse
DXF drawings / DXF ZeichungenALLZIP1975 KB

Approvals: R2-SP-IC*

Language Selection:
CertificatesCertifikat nr.SprogFil typeFil størrelse
Brasil TUV Rheinland BrazilTÜV 14.1593 XALLPDF1122 KB
China SITIIAS CCC Ex Certificate2020322310002500 (Singapore)ALLPDF1291 KB
DNV MarineTAA0000272ALLPDF100 KB
Europe TUV Nord II 3 GTUV 12 ATEX 098651 XALLPDF664 KB
India PESO (India) CCOEA/P/HQ/KA/104/6086 (P576914)ALLPDF105 KB
TUV Nord Zone 2 IECEx Certificate of ConformityIECEx TUN 12.0015XALLLINK---
USA Canada UL Hazardous Location Certificate of Compliance cULus UL E106378CoC E106378 RepRef E106378-20141126ALLPDF413 KB
Worldwide Fieldbus FoundationDC084300ALLPDF56 KB
Control Drawings
Control drawing UL / Control drawing UL   ALLPDF389 KB
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0603DALLPDF1042 KB

Tilhørende produkter: R2-SP-IC*

Matching System Components
4 ... 12 outputs Ex ic (FISCO or Entity), Glass fiber reinforced polyester, impact resistant, IP66, Configurable cable entries for trunk and spurs, International approvals, For FOUNDATION Fieldbus H1 and PROFIBUS PA, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk, Device coupler location [2]: Zone 2 - high-power trunk, Instrument location / spur protection: non-explosion hazardous area
Zone 2 - all relevant types of protection
Zone 1 - increased safetypa
Segment Protector Junction Box, Brushed Stainless Steel, 4 ... 12 outputs Ex ic (FISCO or Entity), Brushed enclosure, IP66, Configurable cable entries for trunk and spurs, International approvals, For FOUNDATION Fieldbus H1 and PROFIBUS PA, Device coupler location: non-explosion hazardous area
Zone 2 - high-power trunk, Device coupler location [2]: Zone 2 - high-power trunkpa
Accessories
FieldConnex® Fieldbus, Surge protector, pluggable module for trunk installation on segment protector, Pluggable, mounts between device coupler and trunk cable, Intrinsically safe (Ex ia), FISCO, Entity, DART Fieldbus, or general-purpose, Optional diagnostics for wear, Grounding of shield via gas-discharge tube, For FOUNDATION Fieldbus H1 and PROFIBUS PA, IECEx approval, Europe, USA, Canadapa
FieldConnex® Fieldbus, Surge protector, pluggable module for spur installation on segment protector, Pluggable, mounts between device coupler and spur cable, Intrinsically safe (Ex ia), FISCO, Entity, DART Fieldbus, or general-purpose, Optional diagnostics for wear, Grounding of shield via gas-discharge tube, For FOUNDATION Fieldbus H1 and PROFIBUS PA, IECEx approval, Europe, USA, Canadapa