General specifications |
Design / Mounting | Outside installation |
Installation in hazardous area | Zone 1 / Div. 1 |
Electronic component | Binary multi-input/output R8D0-MIO-Ex12.PA* For technical data on installed electronic component see datasheet. |
Fieldbus connection |
Fieldbus type | PROFIBUS PA |
Digital input |
Number of inputs | 12 |
Galvanic isolation |
Foundation Fieldbus/Field circuit | safe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V |
Directive conformity |
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 |
Low voltage | |
| Directive 2014/35/EU | EN 61010-1:2010 |
Standard conformity |
Galvanic isolation | EN 60079-11 |
Electromagnetic compatibility | NE 21:2011 |
Degree of protection | IEC 60529 |
Fieldbus standard | IEC 61158-2 |
Shock resistance | EN 60068-2-27 |
Vibration resistance | EN 60068-2-6 |
Ambient conditions |
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) hazardous area |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
Relative humidity | ≤ 95 % non-condensing |
Shock resistance | 15 g , 11 ms |
Vibration resistance | 10 g , 10 ... 150 Hz |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 |
Mechanical specifications |
Connection type | plug-in terminals , spring terminal and screw terminal |
Core cross section | |
| Bus | up to 2.5 mm2 |
| Inputs | up to 2.5 mm2 |
Cable diameter | see table 2 |
Cable gland | sensor inputs M16, fieldbus M20 |
Housing material | Aluminum |
Degree of protection | IP66 |
Mass | 1800 g |
Data for application in connection with hazardous areas |
EU-type examination certificate | BVS 16 ATEX E 075 X |
| Marking | II 2 (1) G Ex ib [ia Ga] IIC T4 Gb , II 3 (1) G Ex ic [ia Ga] IIC T4 Gc , II 3 (1) G Ex ec [ia Ga] IIC T4 Gc , I (M1) [Ex ia Ma] I , II (1) D [Ex ia Da] IIIC , II 2 (1) D Ex tb [ia Da] IIIC T130 °C Db |
Bus | FISCO see EC-Type Examination Certificate |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-31:2014 |
International approvals |
FM approval | pending |
IECEx approval | IECEx BVS 16.0051X |
| Approved for | Ex ib [ia Ga] IIC T4 Gb , Ex ic [ia Ga] IIC T4 Gc , Ex ec [ia Ga] IIC T4 Gc , [Ex ia Ma] I , [Ex ia Da] IIIC , Ex tb [ia Da] IIIC T130 °C Db |
Certificates and approvals |
Marine approval | pending |
General information |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |