Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Hent hele databladet som PDF:
Produkt beskrivelse |
---|
Fieldbus terminator, threaded, for installation via threaded inlet in field housing (Ex ia / Ex d), IP67 |
General specifications | ||
---|---|---|
Design / Mounting | Outside installation | |
Installation in hazardous area | Zone 1 / Div. 1 | |
Fieldbus connection | ||
Connection | 2-wire cable, red+, black- | |
Rated voltage | max. 32 V DC | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | ||
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC/EN 60529 | |
Fieldbus standard | IEC 61158-2 | |
Ambient conditions | ||
Ambient temperature | -50 ... 85 °C (-58 ... 185 °F) | |
Storage temperature | -50 ... 85 °C (-58 ... 185 °F) | |
Mechanical specifications | ||
Core cross section | 0.75 mm2 | |
Housing | 77 mm x 22 mm | |
Degree of protection | IP67 | |
Mass | 100 g | |
Mounting | 20 mm ISO thread PG13.5 thread 1/2 NPT thread |
|
Data for application in connection with hazardous areas | ||
EU-type examination certificate | DMT 01 ATEX 104 X | |
Marking | II 1G Ex ia IIC T6 ... T4 Ga , II 2G Ex db ia IIC T6 ... T4 Gb , II 2G Ex db mb IIC T6 ... T4 Gb , max. permissible explosion (reference) pressure of the Ex d enclosure: 20 bar | |
Temperature class | T6 for ambient temperature ≤ 60 °C T5 for ambient temperature ≤ 75 °C T4 for ambient temperature ≤ 85 °C |
|
Maximum values | acc. to FISCO | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-1:2014 , EN 60079-11:2012 , EN 60079-18:2015 | |
International approvals | ||
IECEx approval | IECEx BVS 10.0022X | |
Approved for | Ex ia IIC T6 ... T4 Ga , Ex db ia IIC T6 ... T4 Gb , Ex db mb IIC T6 ... T4 Gb | |
General information | ||
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27242692 |
ECLASS 12.0 | 19170104 |
ECLASS 11.0 | 27242692 |
ECLASS 10.0.1 | 27242692 |
ECLASS 9.0 | 27242692 |
ECLASS 8.0 | 27242692 |
ECLASS 5.1 | 27242692 |
ETIM 9.0 | EC002584 |
ETIM 8.0 | EC002584 |
ETIM 7.0 | EC002584 |
ETIM 6.0 | EC002584 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121008 |
Literature | Sprog | Fil type | Fil størrelse |
---|---|---|---|
Application Report - Controlling and Monitoring liquid Helium at the Deutsches Elektronen-Synchrotron | ENG | 361 KB | |
Application Report - Digital Communication in Steel-Plate Manufacturing | ENG | 470 KB |
Safety and Security Documentation | Sprog | Fil type | Fil størrelse |
---|---|---|---|
Instruktions manual | DAN | 124 KB |
Certificates | Certifikat nr. | Sprog | Fil type | Fil størrelse |
---|---|---|---|---|
BVS IECEx Certificate of Conformity | IECEx BVS 10.0022X | ALL | LINK | --- |
Europe DEKRA EXAM ATEX Category 1 G ATEX Category 2 G | DMT 01 ATEX E 104X | ALL | 1948 KB | |
South Africa MASC | MASC S/18-0737X | ALL | 647 KB | |
Declaration of Conformity | ||||
EU Declaration of Conformity (P+F) | TDOC-2854DDAN | DAN | 1139 KB |