Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Hent hele databladet som PDF:
Uddrag af datablad: Tekniske data for
F.FB1.P14.A**.1.*.***.***.****
General specifications |
Design / Mounting | Outside installation |
Installed components | FieldBarrier R4D0-FB-IA* For technical data on installed electronic component see data sheet. |
Conformity |
Degree of protection | EN 60529 |
Impact resistance | EN 60079-0 |
Ambient conditions |
Ambient temperature | -30 ... 55 °C (-22 ... 131 °F) , (extended temperature range available on request) |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) |
Relative humidity | < 75 % (annual mean) < 95 % (30 d/year), no moisture condensation |
Impact resistance | 7J |
Mechanical specifications |
Enclosure cover | detachable cover with retaining screws |
Degree of protection | IP66 |
Cable entry | cable gland and stopping plug options see separate table |
Material | |
| Housing | polyester , impact resistant, glass fiber reinforced |
| Grounding plate | brass |
| Surface | black (RAL 9011) |
| Surface resistance | < 109 Ω |
| Water absorption | < 6 % |
| Seal | silicone , one-piece |
| Material thickness | grounding plate: 3 mm |
Dimensions | (W x H x D) 405 x 400 x 200 mm |
Mounting | thru-holes Ø6.5 mm |
Grounding | grounding bolt M6 , brass |
Data for application in connection with hazardous areas |
EU-type examination certificate | PTB 07 ATEX 1061 X (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com |
| Marking | II 2(1)G Ex db eb ib mb [ia Ga] IIC T4 Gb
II 2(1)D Ex tb [ia Da] IIIC T135°C Db Note: The marking is based on the maximum value and can be reduced depending on the selected options accordingly. |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-1:2014 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-18:2009 , EN 60079-31:2014 |
International approvals |
IECEx approval | IECEx PTB 07.0036 X , suitable Junction Box on request |
INMETRO approval | TÜV 13.1143 |
General information |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
Classifications
System | Classcode |
ECLASS 13.0 | 27242605 |
ECLASS 12.0 | 27242605 |
ECLASS 11.0 | 27242605 |
ECLASS 10.0.1 | 27242605 |
ECLASS 9.0 | 27242605 |
ECLASS 8.0 | 27242605 |
ECLASS 5.1 | 27242605 |
ETIM 9.0 | EC001601 |
ETIM 8.0 | EC001601 |
ETIM 7.0 | EC001601 |
ETIM 6.0 | EC001601 |
ETIM 5.0 | EC001604 |
UNSPSC 12.1 | 39121008 |
Details:
F.FB1.P14.A**.1.*.***.***.****
Product Documentation:
F.FB1.P14.A**.1.*.***.***.****
Approvals:
F.FB1.P14.A**.1.*.***.***.****
Tilhørende produkter:
F.FB1.P14.A**.1.*.***.***.****
Matching System Components |
|
|
|
FieldConnex® FieldBarrier®, 8 ... 12 outputs Ex ia IIC, FISCO and Entity, Advanced fault isolation and diagnostics at the spur, FieldBarrier in Zone 1/Div. 2, Instruments in Zone 0...1/Div. 1, For FOUNDATION Fieldbus H1 and PROFIBUS PA, IECEx approval, Dust protection, International, Europe, USA, Device coupler location: Zone 2 - high-power trunk Zone 1 - high-power trunk Division 2 - high-power trunk Division 1 - high-power trunkpa |
|