Support Industrielle sensorer
Support Explosion Protection

SMART Transmitter Power Supply/Current Driver HiD2024

HiD2024
  • 4-channel isolated barrier
  • 24 V DC supply (bus powered)
  • Analog in or analog out signals
  • Sink and source mode outputs
  • SMART pass-through
  • Up to SIL 2 acc. to IEC/EN 61508

Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

Hent hele databladet som PDF:


Uddrag af datablad: Tekniske data for   HiD2024

General specifications
Signal typeAnalog input/analog output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
ConnectionSL1: 1a(-), 1b(-); 2a(+), 2b(+)
Rated voltage20.4 ... 30 V DC bus powered via Termination Board
Ripple≤ 10 %
Rated current140 mA at 24 V and 20 mA
Power dissipation≤ 1.8 W at 20 mA
Power consumption≤ 3.3 W at 20 mA
Control circuit
ConnectionSL1: 8a(+), 7a(-); 10a(+), 9a(-); 9b(+), 10b(-); 8b(+), 7b(-)
Voltage dropapprox. 6 V or internal resistance 300 Ω at 20 mA
Ripple200 mV eff
Input
Signal4 ... 20 mA
Resistor> 100 kΩ at max. 23 V, with field wiring open
Output
Signal4 ... 20 mA or 1 ... 5 V (on 250 Ω, 0.1 % internal shunt)
4 ... 20 mA (sink mode), operating voltage 15 ... 26 V
Load0 ... 300 Ω (source mode)
Field circuit
ConnectionSL2: 5a(+), 5b(-); 1a(+), 1b(-); 3a(+), 3b(-); 7a(+), 7b(-)
Voltage≥ 15 V at 20 mA
Input
Signal4 ... 20 mA , limited to approx. 30 mA
Output
Signal4 ... 20 mA
Load0 ... 650 Ω
Transfer characteristics
Deviationat 20 °C (68 °F)
≤ ± 0.1 % incl. non-linearity and hysteresis (source mode 4 ... 20 mA)
≤ ± 0.2 % incl. non-linearity and hysteresis (sink mode 4 ... 20 mA)
≤ ± 0.2 % incl. non-linearity and hysteresis (source mode 1 ... 5 V)
≤ ± 0.2 % incl. non-linearity and hysteresis (analog output mode 4 ... 20 mA)
Influence of ambient temperature< 2 µA/K (0 ... 60 °C (32 ... 140 °F)); < 4 µA/K (-20 ... 0 °C (-4 ... 32 °F))

Frequency rangefield side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB)
Rise time10 to 90 % ≤ 20 ms
Galvanic isolation
Output/power supplybasic insulation according to IEC 62103, rated insulation voltage 50 Veff
Indicators/settings
Display elementsLED
Control elementsDIP switch
potentiometer
Factory settinganalog input with source output
Configurationvia DIP switches
via potentiometer
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2006
For further information see system description.
Degree of protectionIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Massapprox. 140 g
Dimensions18 x 114 x 130 mm (0.7 x 4.5 x 5.1 inch) (W x H x D)
Height114 mm
Width18 mm
Depth130 mm
Mountingon termination board
Codingpin 1 and 3 trimmed
For further information see system description.
Data for application in connection with hazardous areas
EU-type examination certificateCESI 02 ATEX 086
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC , Ex-Hexagon II (1)D [Ex ia Da] IIIC
InputEx ia, Ex iaD
Supply
Maximum safe voltage250 V AC (Attention! Um is no rated voltage.)
Equipment
Voltage25.2 V
Current93 mA
Power586 mW
Internal capacitance1.2 nF
Internal inductancenegligible
CertificatePF 11 CERT 2109 X
MarkingEx-Hexagon II 3G Ex nA IIC T4 Gc
Galvanic isolation
Input/Outputsafe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V
Input/power supplysafe electrical isolation acc. to EN 60079-11: 2007, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
IECEx approval
IECEx certificateIECEx TUN 04.0012
IECEx marking[Ex ia] IIC
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.

Classifications

SystemClasscode
ECLASS 13.027210119
ECLASS 12.027210119
ECLASS 11.027210119
ECLASS 10.0.127210119
ECLASS 9.027210119
ECLASS 8.027210119
ECLASS 5.127210119
ETIM 9.0EC001485
ETIM 8.0EC001485
ETIM 7.0EC001485
ETIM 6.0EC001485
ETIM 5.0EC001485
UNSPSC 12.132101514

Details: HiD2024

Product Documentation: HiD2024

Language Selection:
Safety and Security DocumentationSprogFil typeFil størrelse
Instruktions manualDANPDF163 KB
Functional Safety ManualENGPDF518 KB
Manuals
System ManualENGPDF5438 KB

Design / Simulation: HiD2024

Language Selection:
CADSprogFil typeFil størrelse
CAD 2-D / CAD 2-DALLZIP16364 KB
CAE
EPLAN macros H-System devices (EMA) / EPLAN-Makros Geräte H-System (EMA)ALLZIP3536 KB

Approvals: HiD2024

Language Selection:
CertificatesCertifikat nr.SprogFil typeFil størrelse
Europe CESI ATEX Category (1) D ATEX Category (1) GCESI 02 ATEX 086ALLPDF3887 KB
Europe Pepperl+Fuchs ATEX Category 3 GPF 11 CERT 2109 XALLPDF446 KB
TUV Nord IECEx Certificate of ConformityIECEx TUN 04.0012ALLLINK---
Declaration of Conformity
EU Declaration of Conformity (P+F) / EU-Konformitäterklärung (P+F)DOC-0905BALLPDF48 KB
Safety Products Selector

Choose from various selection criteria like safety integrity level, performance level, device function, and signal type and find the SIL/PL assessed device that you are looking for.