Electrical specifications |
Operating voltage | 230 V AC , optional 110 V AC |
Function | elimination of electrostatic charges |
| Lens color | red and green |
| Operator action | Cable: hydrocarbon-resistant, 3x 3 mm2, length 8 m. Other lengths on request. Connection clamp: Aluminum with phosphor bronze contacts, isolating thermoplastic handles |
Mechanical specifications |
Thread type | metric ISO pitch 1.5 mm or NPT ANSI ASME B1.20.1 |
Enclosure cover | threaded round cover |
Cover fixing | flamepath thread |
Cover seal | none, O-ring for IP66/67 |
Flamepath grease | petroleum jelly |
Degree of protection | IP65 , Enclosure IP66 (IP66/IP67 with O-ring) |
Cable entry | face B |
Cable entry face B | |
| M25 quantity | 2 |
| M25 type | NPT 3/4'' |
| M25 info | as standard, other on request |
Material | |
| Enclosure | aluminum alloy |
| Finish | epoxy coated RAL 7005 (grey) |
| O-Ring | silicone |
Mass | approx. 25 kg |
Dimensions | values might differ slightly due to casting and manufacturing tolerances |
| External dimension (A) | 360 mm |
| External dimension (B) | 360 mm |
| External dimension (C) | 245 mm |
| Mounting holes distance (G) | 395 mm |
| Mounting holes distance (H) | 318 mm |
| Mounting holes diameter (J) | 10 mm |
| Number of mounting brackets | 4 |
| Maximum external dimension (K) | 430 mm |
| Maximum external dimension (K1) | 510 mm |
Grounding | M6 external grounding points |
Ambient conditions |
Ambient temperature | -20 ... 40 °C (-4 ... 104 °F) |
Data for application in connection with hazardous areas |
EU-type examination certificate | INERIS 14 ATEX 0035X |
| Marking | II 2 GD Ex db [ia Ga] IIC T6 Gb, II 2 GD Ex tb [iaD] IIIC T85°C Db |
Conformity |
Degree of protection | EN 60529 |
CE marking | 0080 or 0102, see type label |
General information |
Ordering information | This solution will be delivered completely configured and assembled ready for use. For configuration details please contact Customer Service. |
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |