KFD2-VR4-Ex1.26 Voltage Repeater

Key Benefits at a Glance

  • 1-channel isolated barrier
  • 24 V DC supply (Power Rail)
  • Voltage input 0 V ... -20 V
  • Vibration sensor inputs
  • Voltage/current field supply
  • Voltage output 0 V ... -20 V
  • Up to SIL 2 acc. to IEC/EN 61508

Show more

Please contact us for exact delivery estimation.11 237,85 ZAR Net price—your individual price will be shown during checkout process.
Approval
Product Compliance: Europe – CE
Approval
Product Compliance: USA - cULus
Functional Safety: Safety Integrity Level - 2
Note

All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.

EN
  • DE
  • EN
  • ES
  • FR
  • PL

Technical data of KFD2-VR4-Ex1.26

Signal typeAnalog input
Safety Integrity Level (SIL)SIL 2
ConnectionPower Rail or terminals 11+, 12-
Rated voltageUr19 ... 30 V DC
Ripplewithin the supply tolerance
Power dissipation≤ 1.2 W
Power consumption≤ 1.6 W
Connection sidefield side
Connectionterminals 4 (common), 1, 3 and 5 (supply -), 2 and 6 (signal -)
Input resistance10 kΩ terminals 4 (common), 6-/2-
Output currentterminals 4 (common), 5-: > 10 mA at -21 V or > 20 mA at -18 V
terminals 4 (common), 1-: 5.3 mA ±0.4 mA at -10 V
terminals 4 (common), 3-: 3.6 mA ±0.7 mA at -10 V, 20 °C (68 °F)
Transmission range-20 ... 0 V
Connection sidecontrol side
Connectionterminals 7-, 8+
Voltage-20 ... 0 V
Load≥ 9 kΩ (3-wire sensor), ≥ 2 kΩ (2-wire sensor)
Output resistance24 Ω typ., 27 Ω maximum
Since this is much less than the end-to-end resistance of a zener barrier, it may be necessary to specify a monitor intended for use without a barrier. Please follow the advice of the monitor manufacturer.
Cut-off frequency10 kHz (-0,1 dB)
20 kHz (-1 dB)
DeviationDC transfer error (with 10 kΩ load) < 10mV
After calibrationadditional error with AC superimposed is ±5 mV at 20 °C (68 °F) at any point within the span, provided that the alternating component of the input voltage is not excessive, e. g.
- square waves (0 ... 20 kHz): 5 Vpp
- sine waves (0 ... 20 kHz): the full span of 20 Vpp (= 100 g peak acceleration at 100 mV/g) is acceptable.
Influence of ambient temperature(< 100 ppm of span)/K at any point within the span
Time delay relative to input7.1 ±0.3 µs
Ripplein 200 kHz bandwidth < 20 mVrms
in 20 kHz bandwidth < 3 mVrms
Output/power supplyfunctional insulation, rated insulation voltage 50 V AC
Display elementsLED
Labelingspace for labeling at the front
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Electromagnetic compatibilityNE 21:2017
EN IEC 61326-3-2:2018
Degree of protectionIEC 60529
Protection against electrical shockUL 61010-1
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 125 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) (W x H x D) , housing type B2
Height119 mm
Width20 mm
Depth115 mm
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
EU-type examination certificateBAS 02 ATEX 7206
MarkingEx-Hexagon II (1)G [Ex ia Ga] IIC , [exsign] II (1)D [Ex ia Da] IIIC
InputEx ia Ga, Ex ia Da
VoltageUo-26.4 V
CurrentIo90 mA
PowerPo570 mW
Supply
Maximum safe voltageUm253 V (Attention! The rated voltage can be lower.)
Output
Maximum safe voltageUm253 V (Attention! The rated voltage is lower.)
EU-type examination certificateDMT 01 ATEX E 133
MarkingEx-Hexagon I (M1) [Ex ia] I
CertificateTÜV 99 ATEX 1499 X
MarkingEx-Hexagon II 3G Ex nA II T4
Galvanic isolation
Input/Outputsafe galvanic isolation acc. to IEC 60079-11, voltage peak value 375 V
Input/power supplysafe galvanic isolation acc. to IEC 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000
UL approval
Control drawing116-0316 (cULus)
IECEx approval
IECEx certificateIECEx BAS 05.0078
IECEx BAS 10.0085X
IECEx marking[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I
Ex nA II T4 Gc
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.