Please note: All product-related documents, such as certificates, declarations of conformity, etc., which were issued prior to the conversion under the name Pepperl+Fuchs GmbH or Pepperl+Fuchs AG, also apply to Pepperl+Fuchs SE.
Download the complete datasheet as a PDF:
Slots | ||
---|---|---|
Occupied slots | 1 | |
Supply | ||
Connection | backplane bus | |
Rated voltage | 12 V DC +4/-2 % , only in connection with the power supply LB9006C | |
Power dissipation | 0.5 W | |
Power consumption | 0.45 W | |
Internal bus | ||
Connection | backplane bus | |
Interface | manufacturer-specific bus to standard com unit | |
Digital output | ||
Number of channels | 2 | |
Field device interface | ||
Connection | Relay output | |
Connection | channel I: 1-2 NC, 3; channel II: 4-5 NC, 6 | |
Relay | ||
Switching voltage | 30 V DC |
|
Switching current | 1 A DC |
|
Switch power | 30 W | |
Minimum load | 5 V 10 mA | |
Electrical life | 0.03 million switching cycles at maximum load and temperature | |
Contact Material | AgPd gold plated | |
Response time | 20 ms (depending on bus cycle time) | |
Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
Indicators/settings | ||
LED indication | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: Communication error or active safety shutdown Status LED (1-2) yellow: Channel status |
|
Coding | optional mechanical coding via front socket | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1 | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1 , EN 60664-1 | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Environmental test | EN 60068-2-14 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Relative humidity | EN 60068-2-78 | |
Ambient conditions | ||
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Altitude | max. 2000 m | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
Vibration resistance | frequency range 10 ... 150 Hz; transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g; 10 cycles | |
Mechanical specifications | ||
Degree of protection | IP20 when mounted on backplane | |
Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) |
|
Mass | approx. 90 g | |
Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
Data for application in connection with hazardous areas | ||
EU-type examination certificate | FIDI 23 ATEX 0078 X | |
Marking | II 3G Ex ec nC IIC T4 Gc | |
Galvanic isolation | ||
Output/power supply, internal bus | basic insulation according to IEC/EN 61010-1, rated insulation voltage 30 V DC | |
Directive conformity | ||
Directive 2014/34/EU | EN IEC 60079-0 EN IEC 60079-7 EN IEC 60079-15 |
|
International approvals | ||
IECEx approval | ||
IECEx certificate | IECEx FIDI 23.0010X | |
IECEx marking | Ex ec nC IIC T4 Gc | |
General information | ||
System information | The module has to be mounted in appropriate backplanes (LB9***) in Zone 2 or outside hazardous areas. Here, observe the corresponding declaration of conformity. For use in hazardous areas (e. g. Zone 2 or Zone 22) the module must be installed in an appropriate enclosure. |
|
Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. |
System | Classcode |
---|---|
ECLASS 13.0 | 27210101 |
ECLASS 12.0 | 27210101 |
ECLASS 11.0 | 27210101 |
ECLASS 10.0.1 | 27210101 |
ECLASS 9.0 | 27210101 |
ECLASS 8.0 | 27210101 |
ECLASS 5.1 | 27210120 |
ETIM 9.0 | EC001485 |
ETIM 8.0 | EC001485 |
ETIM 7.0 | EC001485 |
ETIM 6.0 | EC001485 |
ETIM 5.0 | EC001485 |
UNSPSC 12.1 | 39121008 |
The device features 2 independent channels.
The device can be used to switch solenoids.
The device can perform general switching operations, such as switching auxiliary power circuits.
The outputs are galvanically isolated from the bus and the power supply.
Safety and Security Documentation | Language | File Type | File Size |
---|---|---|---|
Instruction manual | ENG | 170 KB | |
Functional Safety Manual | ENG | 2364 KB | |
Manuals | |||
Hardware Manual LB-Remote-I/O-System | ENG | 5385 KB |
CAD | Language | File Type | File Size |
---|---|---|---|
CAD 3-D / CAD 3-D | ALL | STP | 2082 KB |
Certificates | Certificate No. | Language | File Type | File Size |
---|---|---|---|---|
EU Fiditas ATEX | FIDI 23 ATEX 0078X | ALL | 2019 KB | |
Worldwide Fiditas IECEx Certificate of Conformity | IECEx FIDI 23.0010X | ALL | LINK | --- |
Declaration of Conformity | ||||
EU-Declaration of conformity | TDOC-7605_ENG | ENG | 507 KB |